Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/12/2025 Last Data Refresh: 05/11/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Marine/Coastal Fuel Storage | ||||||||
County | Citrus | Status | OPEN | ||||||||
ID | 8626552 | Latitude | 28° 54' 13.944 | ||||||||
Name |
TWIN RIVERS MARINA 2880 N SEA BREEZE PT (CR 44 W) |
Longitude | 82° 38' 29.6149 | ||||||||
CRYSTAL RIVER, FL 34429 | LL Method | DPHO | |||||||||
Contact | ANDREW J HUPP | LL Status | REVIEWED | ||||||||
Phone | (352) 795-3552 | Status Date | 02/07/2003 | ||||||||
Account Owner Information | |||||||||||
Name | TWIN RIVERS HOLDING LLC 907 S FORT HARRISON AVE #102 CLEARWATER, FL 33756 |
Effective Date | 06/05/2020 | ||||||||
Contact | ANDREW J HUPP | ||||||||||
Phone | (727) 210-1900 | ||||||||||
AHUPP@ONEOAKDEV.COM | |||||||||||
Placard # / Date | 705497 - 04/07/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | TWIN RIVERS HOLDING LLC 907 S FORT HARRISON AVE #102 CLEARWATER, FL 33756 |
Effective Date | 04/22/2020 | ||||||||
Contact | ANDREW J HUPP | ||||||||||
Phone | (727) 210-1900 | ||||||||||
AHUPP@ONEOAKDEV.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10000 | Vehicular Diesel (D) | 02/01/2004 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (M) Spill containment bucket (O) Tight fill |
(A) Abv, no soil contact (B) Steel/galvanized metal (F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 2000 | Vehicular Diesel (D) | 04/01/2014 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall |
(F) Double wall | (J) Monitor piping/liner space | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Unleaded Gas (B) | 07/01/2019 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (X) No piping associated w/tank | (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1000 | Vehicular Diesel (D) | 07/01/1983 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment (N) Flow shut-Off |
(F) Double wall | (E) Monitor UST/liner space (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 1000 | Unleaded Gas (B) | 07/01/1985 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment (O) Tight fill |
(B) Steel/galvanized metal (F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(4) Visual inspect dispenser liners (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 3000 | Unleaded Gas (B) | 02/01/1994 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment (O) Tight fill |
(B) Steel/galvanized metal (F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(4) Visual inspect dispenser liners (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Vehicular Diesel (D) | 04/01/1994 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment (O) Tight fill |
(B) Steel/galvanized metal (F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(4) Visual inspect dispenser liners (K) Monitor dbl wall pipe space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 12/23/2019 | 12/23/2020 | AXIS SURPLUS INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2018 | 04/24/2019 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2017 | 04/24/2018 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2016 | 04/24/2017 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2015 | 04/24/2016 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2014 | 04/24/2015 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2013 | 04/24/2014 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 04/24/2012 | 04/24/2013 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||||||
INSURANCE | 04/24/2011 | 04/24/2012 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||||||
INSURANCE | 04/24/2010 | 04/24/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 04/24/2009 | 04/24/2010 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 10/27/2005 | 10/28/2005 | IN-COMPLIANCE | MOLLI_SA | 1/0 | COMPLIANCE ASSURANCE | |||||
DPRI | 06/06/2005 | 06/06/2005 | IN-COMPLIANCE | MOLLI_SA | 0/0 | TERMINAL FACILITY PROJECT | |||||
TCR | 11/05/2004 | 11/09/2004 | IN-COMPLIANCE | MOLLI_SA | 1/0 | COMPLIANCE ASSURANCE | |||||
CWOE | 11/05/2004 | 10/28/2005 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 10/27/2004 | 11/09/2004 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/22/2004 | 11/09/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | MOLLI_SA | 1/0 | COMPLIANCE ASSURANCE | |||||
TIN | 10/22/2004 | 12/20/2004 | IN-COMPLIANCE | MOLLI_SA | 1/0 | COMPLIANCE ASSURANCE | |||||
CWOE | 08/18/2004 | 08/27/2004 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TXI | 08/18/2004 | 08/27/2004 | IN-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOVAL OF THREE ASTS. EXISTING PIPING IS TO BE USED WITH NEW DW AST. | |||||||||||
TCI | 07/17/2003 | 07/18/2003 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes DOUBLE WALLED ENVIRON GEOFLEW GREEN OUTER WHITE INNER PIPING | |||||||||||
NCLI | 07/17/2003 | 07/18/2003 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/17/2002 | 07/17/2002 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
NCLI | 07/17/2002 | 07/17/2002 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
DPRI | 07/17/2002 | 07/17/2002 | SUMNER_C | 3/0 | TERMINAL FACILITY PROJECT | ||||||
NCLI | 04/04/2002 | 04/04/2002 | SUMNER_C | 0/0 | TERMINAL FACILITY PROJECT | ||||||
DPRI | 04/04/2002 | 04/04/2002 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 0/0 | TERMINAL FACILITY PROJECT | |||||
TCR | 02/22/2002 | 02/22/2002 | IN-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
CWOE | 02/22/2002 | 02/22/2002 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 07/09/2001 | 07/09/2001 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/05/2001 | 07/09/2001 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TCI | 10/25/2000 | 10/25/2000 | IN-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TCR | 03/06/2000 | 03/07/2000 | IN-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
CWOE | 03/06/2000 | 03/31/2000 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/11/2000 | 03/01/2000 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/11/2000 | 02/16/2000 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TCI | 01/18/1999 | 03/04/1999 | IN-COMPLIANCE | CHRONISTER_D | 3/0 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Record Document | 05/18/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 04/12/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 04/12/2023 | Major Out of Compliance | MULLIGAN_PC_1 | 2/0 | Routine Compliance | ||||||
Phone Conversation | 04/10/2023 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||||||
Phone Conversation | 04/07/2023 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||||||
Record Document | 05/13/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 05/11/2021 | Satisfied | FABRIZIO_J | Enforcement | |||||||
Electronic Communication | 03/23/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Enforcement Referral | 03/22/2021 | Accepted | MULLIGAN_PC_1 | Enforcement | |||||||
Electronic Communication | 03/17/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Phone Conversation | 03/17/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Phone Conversation | 03/17/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 03/17/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 12/17/2020 | Major Out of Compliance | MULLIGAN_PC_1 | 2/0 | Routine Compliance | ||||||
Electronic Communication | 12/17/2020 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||||||
Letter | 12/17/2020 | Satisfied | MULLIGAN_PC_1 | Non-Compliance | |||||||
Site Inspection | 12/17/2020 | Major Out of Compliance | MULLIGAN_PC_1 | 2/0 | Installation | ||||||
Letter | 12/17/2020 | Satisfied | MULLIGAN_PC_1 | Non-Compliance | |||||||
Letter | 04/23/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 04/23/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 04/03/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 02/18/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 01/25/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 01/25/2019 | Major Out of Compliance | MULLIGAN_PC_1 | 2/0 | Routine Compliance | ||||||
Electronic Communication | 01/14/2019 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||||||
Site Inspection | 09/15/2016 | In Compliance | ANTON_TM_1 | 2/0 | Routine Compliance | ||||||
Site Inspection | 06/22/2015 | In Compliance | HECKMAN_DA_1 | 2/0 | Installation | ||||||
Site Inspection | 06/22/2015 | In Compliance | HECKMAN_DA_1 | 2/0 | Non-Compliance | ||||||
Site Inspection | 03/20/2015 | Minor Out of Compliance | HECKMAN_DA_1 | 1/0 | Routine Compliance | ||||||
Letter | 03/20/2015 | Satisfied | HECKMAN_DA_1 | Non-Compliance | |||||||
Site Inspection | 05/15/2013 | In Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 05/23/2012 | In Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||||||
Document Management | 04/10/2012 | Complete | COLSON_NJ_1 | Incident | |||||||
Site Inspection | 11/01/2010 | In Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 09/01/2009 | In Compliance | BAUER_DR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 09/18/2008 | In Compliance | BAUER_DR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 11/27/2007 | In Compliance | OSTENSEN_SA_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 01/19/2007 | In Compliance | BAUER_DR_1 | 1/0 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/10/2023 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Monthly visual inspections should be performed at least once per month, no more than 35 days apart and must be provided at time of inspection. Submit previous logs if available. If inspections were not performed or logs are not available begin performing and recording inspections and submit logs for the next two months (May and June of 2023) to Citrus County Environmental Health. | |||||||
04/10/2023 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Registration should be submitted within 10 days of a change or product. Submit registration form or use the DEP ESSA Portal to update the 10,000 gallon compartmented tank (tank 5) from diesel to B – Unleaded Gasoline (No ethanol). | |||||||
04/10/2023 | 7090 | Minor | 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. | Remove all water from dispenser 1 diesel and 2/3 non-ethanol liners and submit pictures or a work order to Citrus County Environmental Health. | |||||||
04/10/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Submit previous test results if available. If testing was not performed or documentation is not available perform operability testing of the Krueger leak gauges and submit results to Citrus County Environmental Health and the Southwest District Enforcement Office. | |||||||
04/10/2023 | 7011 | Minor | 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. | Financial responsibility documentation must be kept on site for the life of the system and must be provided at time of inspection. Submit financial responsibility documentation covering from 12/23/2020 – current to Citrus County Environmental Health and the Southwest District Enforcement Office. | |||||||
04/10/2023 | 7089 | Minor | 1.11 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Integrity testing of all below-grade dispenser liners shall be performed at least once every 3 years, no more than 36 months apart. Submit previous test results if available. If testing was not performed or documentation is not available perform integrity testing of all below-grade dispenser liners and submit results to Citrus County Environmental Health. | |||||||
12/17/2020 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | Replace the shear valve cross bar and mounting bracket on dispenser 2/3 (non-eth) and submit results to Citrus County Environmental Health. | |||||||
12/17/2020 | 5043 | SNC-B | 3.23 Shop fabricated storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. | All storage tanks shall be installed with a spill containment system at each storage tank fill connection. Install a registered, approved, spill containment device on the 2,000 gallon diesel tank. Perform integrity testing of the spill bucket at time of installation. Submit pictures or a work order showing a spill bucket was added along with the name of the product or EQ information and integrity testing to Citrus County Environmental Health. | |||||||
12/17/2020 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Add overfill protection to the 2,000 gallon non-eth tank and perform operability testing on the overfill devices on all 3 tanks. Submit results to Citrus County Environmental Health. | |||||||
12/17/2020 | 5093 | SNC-A | 3.6 Shop fabricated storage tank systems not provided with a release detection method to detect a new release from any portion of the system, including interstitial spaces. | Any component of a storage tank system with an interstice shall have a method of interstitial monitoring which shall be conducted in accordance with this section. Interstitial monitoring can be performed with vacuum, pressure, hydrostatic (liquid-level sensing), sensors or probes, or visual release detection methods. Either add an interstitial monitoring device and perform operability testing at time of installation or gain access to an interstitial monitoring port to manually check that the interstice is dry. Submit pictures or a work order to Citrus County Environmental Health. | |||||||
12/17/2020 | 5060 | SNC-B | 3.33 Valves not installed as required for small diameter integral piping. | Any storage tank system, regardless of the date of installation of the storage tank system, located at an elevation that produces a gravity head on small diameter integral piping positioned below the product level in the tank must be installed and maintained with an isolation block valve. The valve should be installed as close as possible to the storage tank before the anti siphon device. Install an in line isolation block valve as close as possible to the storage tank before the anti siphon device and submit pictures or a work order to Citrus County Environmental Health. | |||||||
12/17/2020 | 5001 | Minor | 1.1 For a new system, Registration Form not submitted. | For facilities with existing registered storage tank systems, a completed Registration Form shall be submitted in electronic or paper format to the Department no later than seven days prior to regulated substances being put into any new storage system. A registration form was provided with the inspection report, either add the tank to the registration using the attached form or the DEP ESSA Portal and inform Citrus County Environmental Health when registration has been updated. | |||||||
12/17/2020 | 5057 | SNC-B | 3.5 Pressurized small diameter piping not installed with line leak detectors and meeting requirements. | All pressurized small diameter integral piping installed prior to January 11, 2017, that is in contact with the soil must be installed with line leak detectors meeting the requirements of paragraph 62-762.601(4)(b), F.A.C., by January 11, 2018. The line leak detectors must be tested annually at intervals not exceeding 12 months in accordance with paragraph 62-762.601(1)(b), F.A.C. Install line leak detectors on any lines that contain underground piping and perform operability testing at time of installation. Submit repair documentation and test results to Citrus County Environmental Health. | |||||||
12/17/2020 | 5044 | Minor | 3.24 Fillbox covers not marked according to requirements for shop fabricated tank systems. | Fillbox covers shall be marked or the fill connection tagged and facility signage shall be prominently displayed in accordance with Using the API Color-Symbol System. Either add product labeling or API Color-Symbol labeling to the new 10,000 gallon non-eth tank and submit pictures or a work order to Citrus County Environmental Health. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
07/24/1997 | COMPLETED | 7 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||