DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Marine/Coastal Fuel Storage
 
County Pasco   Status    OPEN
 
ID 8626556   Latitude    28° 16' 17.5642
 
Name AMERICAN MARINA
4800 EBBTIDE LANE
Longitude    82° 44' 9.3759
  PORT RICHEY, FL 34668 LL Method    DPHO
 
Contact RONNIE FIGUEROA   LL Status    REVIEWED
 
Phone (727) 326-7694   Status Date    08/25/2003
 
Account Owner Information
 
Name AMERICAN MARINA
2015 ROSE ST
SARASOTA, FL 34239
Effective Date    06/13/2011
 
Contact RONNIE FIGUEROA
 
Phone (727) 326-7694
 
Email
  Placard # / Date    698718 - 07/02/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 12/01/1998 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) 12/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(M) Spill containment bucket   (Y) Unknown (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 1500 Unleaded Gas (B) 12/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(M) Spill containment bucket   (Y) Unknown (8) Manually sampled wells
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   04/03/2022 04/03/2023 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   04/03/2021 04/03/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/03/2020 04/03/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/03/2019 04/03/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/03/2018 04/03/2019 ACE
INSURANCE   04/03/2017 04/03/2018 ACE
INSURANCE   04/03/2016 04/03/2017 ACE
INSURANCE   04/03/2015 04/03/2016 ACE
INSURANCE   04/03/2014 04/03/2015 ACE
INSURANCE   04/03/2013 04/03/2014 ACE
INSURANCE   04/03/2011 04/03/2012 ACE
INSURANCE   04/03/2010 04/03/2011 ACE
INSURANCE   04/03/2009 04/03/2010 ACE
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
CWOE 10/17/2005 10/17/2005 CONDOLEON, GEORGE 0/0 COMPLIANCE ASSURANCE
 
RRBD 10/14/2005 CONDOLEON, GEORGE 0/0 COMPLIANCE ASSURANCE
 
TCI 09/22/2005 10/03/2005 MINOR OUT-OF-COMPLIANCE CONDOLEON, GEORGE 0/1 COMPLIANCE ASSURANCE
 
TCI 08/10/2004 08/27/2004 IN-COMPLIANCE RODRIGUEZ, IVAN 0/1 COMPLIANCE ASSURANCE
 
RRBD 09/25/2003 10/03/2003 IN-COMPLIANCE RODRIGUEZ, IVAN 0/1 COMPLIANCE ASSURANCE
 
TCI 09/04/2003 09/26/2003 MINOR OUT-OF-COMPLIANCE RODRIGUEZ, IVAN 0/1 COMPLIANCE ASSURANCE
 
TCI 10/08/2002 10/09/2002 IN-COMPLIANCE HANSEN, DAVID 0/1 COMPLIANCE ASSURANCE
 
TCI 11/13/2001 11/16/2001 IN-COMPLIANCE HANSEN 0/1 COMPLIANCE ASSURANCE
 
TCI 08/18/2000 08/24/2000 IN-COMPLIANCE HARRIS 0/1 COMPLIANCE ASSURANCE
 
NCLI 01/20/2000 03/06/2000 PETERSON 0/1 COMPLIANCE ASSURANCE
 
TCI 01/05/2000 01/21/2000 SIGNIFICANT OUT-OF-COMPLIANCE PETERSON 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 02/26/2025 Accepted TUCKER_SX_1 Enforcement
 
Enforcement Tracking 02/26/2025 Closed Without Enforcement GREEN_SM Enforcement
 
Site Inspection 01/15/2025 Major Out of Compliance TUCKER_SX_1 0/1 Routine Compliance
 
Letter 01/15/2025 Satisfied TUCKER_SX_1 Compliance Assistance
 
Record Document 01/13/2025 Satisfied TUCKER_SX_1 Compliance Assistance
 
Electronic Communication 01/08/2025 Satisfied TUCKER_SX_1 Routine Compliance
 
Electronic Communication 01/02/2025 Satisfied TUCKER_SX_1 Routine Compliance
 
Site Inspection 03/21/2023 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Letter 03/21/2023 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Document Management 03/14/2023 Satisfied JUARISTIC_GK_1 Closure
 
Letter 03/14/2023 Satisfied JUARISTIC_GK_1 Closure
 
TCAR 03/14/2023 Satisfied JUARISTIC_GK_1 Closure
 
Electronic Communication 03/01/2023 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Record Document 06/09/2021 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 11/16/2020 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Record Document 11/16/2020 Satisfied JUARISTIC_GK_1 Closure
 
Letter 11/16/2020 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 11/05/2020 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Record Document 02/13/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Enforcement Referral 02/07/2019 Accepted JUARISTIC_GK_1 Enforcement
 
Phone Conversation 02/06/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 02/04/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 02/04/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 01/18/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 11/08/2018 Major Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Letter 11/08/2018 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 10/26/2018 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Site Inspection 03/08/2016 In Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Electronic Communication 03/08/2016 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 02/26/2016 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 02/24/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 02/24/2014 In Compliance JUARISTIC_GK_1 0/1 Non-Compliance
 
Site Inspection 12/31/2013 Minor Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Letter 12/31/2013 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Record Document 03/20/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Site Inspection 03/07/2013 Major Out of Compliance ROGGELIN_EM_1 0/1 Routine Compliance
 
Letter 03/07/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Electronic Communication 03/07/2013 Satisfied ROGGELIN_EM_1 Routine Compliance
 
Record Document 08/26/2011 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Emergency Preparedness Information 08/22/2011 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Letter 08/22/2011 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 08/22/2011 Major Out of Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Letter 10/27/2010 Satisfied CONDOLEON_GJ_1 Closure
 
TCAR 10/27/2010 Satisfied CONDOLEON_GJ_1 Closure
 
Site Inspection 10/26/2010 In Compliance CONDOLEON_GJ_1 0/1 Installation
 
Site Inspection 10/07/2010 In Compliance CONDOLEON_GJ_1 0/1 Closure
 
Site Inspection 09/27/2010 In Compliance CONDOLEON_GJ_1 0/1 Closure
 
Site Inspection 09/27/2010 In Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Record Document 09/30/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Letter 09/10/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 09/10/2009 Minor Out of Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Site Inspection 08/28/2008 In Compliance CONDOLEON_GJ_1 0/1 Routine Compliance
 
Record Document 06/09/2008 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 07/25/2007 In Compliance CONDOLEON_GJ_1 0/1 Non-Compliance
 
Site Inspection 06/12/2006 In Compliance CONDOLEON_GJ_1 0/3 Discharge
 
Letter 06/12/2006 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 06/12/2006 Major Out of Compliance CONDOLEON_GJ_1 0/3 Non-Compliance
 
Document Management 06/12/2006 Satisfied CONDOLEON_GJ_1 Discharge
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
01/15/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of water from E0 STP sump and submit proof of compliance documentation (photo documentation and/or waste manifest).
 
01/15/2025 6006 Minor 2.5 Placard not displayed (or available upon request). Display valid registration placard and email copy to this program office.
 
01/15/2025 6002 Minor 2.1 Operator Training records not available. Provide certificates for Class A/ B and C operators for the facility. Owners or operators shall identify and designate for each in-service underground storage tank system facility, including unmanned facilities, at least one named individual for each class of operator – Class A, Class B, and Class.
 
01/15/2025 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Provide required financial responsibility forms 4/3/23 through present and email documentation to this program office.
 
01/15/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove PCW and conduct operability test on secondary gauge to ensure it is functioning properly. Submit test results to this program office.
 
01/15/2025 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Visual inspections shall be conducted at least once a month, but not exceeding 35 days, every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances and document its true condition. Piping and dispenser sumps that use an electronic release detection method must also be visually inspected every six months and records kept of the visual inspection. If records are unavailable, Provide documentation of monthly visual inspections for the next two consecutive months then every month thereafter.
 
01/15/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of PCW from E0 UDC and submit proof of compliance documentation (photo documentation and/or waste manifest).
 
01/15/2025 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Investigation SHALL INCLUDE integrity testing of the tank to determine tightness. When an incident occurs at a facility, actions shall be taken within 24 hours of discovery to investigate the incident to determine if a discharge has occurred.
 
01/15/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Treat for corrosion and repair/replace UDC in disrepair, conduct integrity test on UDC, and submit photos and test documentation to this program office.
 
01/15/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of PCW from E0 spill bucket primary and submit proof of compliance documentation (photo documentation and/or waste manifest).
 
01/15/2025 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Provide testing for overfill protection devices due 6/2/23, 6/2/24 and forward test results to this program office.
 
01/15/2025 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Piping and dispenser sumps, double wall spill buckets shall be tested every 3 years not to exceed 36 months. Provide DW spill bucket, UDC and STP sump integrity tests due 9/30/24 and submit test records to this program office.
 
01/15/2025 6062 Minor 2.5 Release detection devices not tested annually. Provide testing for spill bucket secondary gauge due 9/30/23, 9/30/24 and forward test results to this program office.
 
03/21/2023 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair/replace the electrical conduit in the STP sump.
 
03/21/2023 6008 Minor 2.7 For installation, closure, or change in service status, notification not received in a timely manner. Applied Science & Engineering conducted a Closure Assessment. Violation will be resolved with the issue of the non-compliance letter.
 
11/16/2020 4012 Minor 2.3 For an incident, notification not received in a timely manner. Ensure all future incidents are reported within 72-hours of discovery. Resolved with 7/17/2020 incident investigation/Closure Assessment.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
09/29/1994   COMPLETED 26 PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE
 
08/04/1992   COMPLETED 26 PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE