DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southeast   Type    Fuel user/Non-retail
 
County Monroe   Status    OPEN
 
ID 8628214   Latitude    24° 34' 51.2502
 
Name LOWER KEYS MEDICAL CTR
5900 COLLEGE RD
Longitude    81° 44' 35.5403
  KEY WEST, FL 33040 LL Method    DPHO
 
Contact DAVID CLAY   LL Status    REVIEWED
 
Phone (305) 294-5531   Status Date    11/02/2022
 
Account Owner Information
 
Name LOWER KEYS MEDICAL CENTER
5900 COLLEGE RD
KEY WEST, FL 33040
Effective Date    05/20/1994
 
Contact DON HAKE
 
Phone (305) 294-5531
 
Email DON.HAKE@LKMC.COM
  Placard # / Date    700668 - 08/14/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
3 6000 Emerg Generator Diesel (G) 05/01/1999 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(2) Visual inspect pipe sumps
(F) Monitor dbl wall tank space
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Emerg Generator Diesel (G) 02/01/2003 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(M) Double wall - pipe jacket
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
5 3408 Emerg Generator Diesel (G) 06/01/2016 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (A) Abv, no soil contact (F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
(M) Manual tank gauging - USTs
(P) Vapor monitoring w/dilution
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
6 5100 Emerg Generator Diesel (G) 12/01/2023 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(P) Level gauges/alarms
  (B) Steel/galvanized metal (F) Monitor dbl wall tank space
(G) Electronic line leak detector
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Emerg Generator Diesel (G) 08/01/1982 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 5000 Fuel Oil - Onsite Heat (M) 10/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   10/01/2024 10/01/2025 ALLIED WORLD ASSURANCE COMPANY (US), INC.
INSURANCE   10/01/2023 10/01/2024 ALLIED WORLD ASSURANCE COMPANY (US), INC.
INSURANCE   10/01/2021 10/01/2022 ALLIED WORLD ASSURACE COMPANY (U.S.) INC
INSURANCE   10/01/2020 10/01/2021 ALLIED WORLD ASSURACE COMPANY (U.S.) INC
INSURANCE   10/01/2018 10/01/2019 ALLIED WORLD ASSURACE COMPANY (U.S.) INC
INSURANCE   10/01/2016 10/01/2017 AIG SPECIALTY INSURANCE COMPANY
INSURANCE   10/01/2014 10/01/2015 AIG
INSURANCE   10/01/2012 10/01/2013 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   10/01/2010 10/01/2011 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   10/01/2009 10/01/2010 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   10/01/2008 10/01/2009 ZURICH-AMERICAN
INSURANCE   09/07/1994 09/07/1998 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 07/20/2005 07/21/2005 IN-COMPLIANCE HAMMONTREE 1/1 COMPLIANCE ASSURANCE
 
TCI 11/12/2004 11/12/2004 IN-COMPLIANCE LOWE 1/1 COMPLIANCE ASSURANCE
 
CCD 07/21/2004 07/21/2004 CUMMINGS_B 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes CASE CLOSED NOTIFICATION LETTER SENT TO RESPONDENT
 
RRBD 07/20/2004 07/21/2004 CUMMINGS_B 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes ALL VIOLATIONS RESOLVED, ALL PENALTIES PAID.
 
PR 07/20/2004 07/21/2004 CUMMINGS_B 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes $3,250 RECEIVED. BALANCE = $0
 
SCOE 07/15/2004 07/21/2004 CUMMINGS_B 0/0 COMPLIANCE ASSURANCE
 
SCOI 06/28/2004 07/21/2004 CUMMINGS_B 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes PENALTIES: $1,000 [62-761.450(1)(A)3] + $2,000 [62-761.500(2)(A)3 & 62-761.400(4)(A)3] + $250 C&E = $3,250 TOTAL DUE 30 DAYS AFTER SIGNING.
 
WLI 04/26/2004 07/21/2004 UNKNOWN 0/0 COMPLIANCE ASSURANCE
 
SV 03/10/2004 03/12/2004 TREBESCH/RUSSELL 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes COORDINATED FDEP/FDOH INSPECTION FOR ENFORCMENT PROCEEDINGS RELATED TO INSTALL AND USE OF AN UNREGISTERED AST
 
CRDE 01/26/2004 01/26/2004 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
TCR 01/23/2004 01/26/2004 IN-COMPLIANCE TREBESCH 0/0 COMPLIANCE ASSURANCE
 
TIN 01/23/2004 01/26/2004 IN-COMPLIANCE TREBESCH 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes VIEWED INSTALLATION AND TESTING OF INTERSTITIAL PROBES FOR DW UNDERGROUND PIPING ASSOCIATED WITH THE CONVAULT AST. BOTH PROBES TESTED PER MANUFACTURERS RECOMMENDATIONS.
 
SV 01/21/2004 01/26/2004 TREBESCH 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes SITE VISIT TO VIEW ANTICIPATED RELEASE DETECTION DEVICE FOR THE UNDERGROUND DOUBLE WALL PIPING ASSOCIATED WITH THE CONVAULT AST. INSTALL WILL BE OF 2 OMNITEC LS-ASC [0.895"] INFARED LIQUID SENSING PROBES.
 
NCLI 10/29/2003 10/29/2003 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
NCLI 10/29/2003 10/29/2003 TREBESCH_CL 0/0 COMPLIANCE ASSURANCE
 
TIN 10/28/2003 10/29/2003 SIGNIFICANT OUT-OF-COMPLIANCE TREBESCH_CL 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALLED FEBRUARY 2003. 4000 GALLON CONVAULT
 
CALL 10/28/2003 10/29/2003 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SPOKE WITH RON MOORE OF HARRINGTON PLASTIC, PROVIDER OF AMERON DUALOY 3000/L EQ#378 FOR THE INSTALL AT LKMC
 
CALL 10/28/2003 10/29/2003 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SPOKE WITH ED STONE, PLUMBING CONTRACTOR FOR THE INSTALL OF CONVAULT AST AT LKMC
 
SV 10/27/2003 10/29/2003 TREBESCH_CL 0/0 COMPLIANCE ASSURANCE
 
CALL 10/27/2003 10/29/2003 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SPOKE WITH ED STONE, PROVIDED DIGITAL PICTURES OF INSTALL AT LKMC THAT OCCURED FEBRUARY 2003
 
TCI 10/24/2003 10/29/2003 SIGNIFICANT OUT-OF-COMPLIANCE TREBESCH_CL 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes 6000 GALLON FIBER-CLAD STEEL DW TANK/SUCTION/PIPING IS DW FG
 
CALL 10/24/2003 10/29/2003 TREBESCH 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes ED STONE CONTACTED ME AT LKMC-DEPOO CLINIC REGARDING SUBMISSION OF REGISTRATION AND INSPECTION OF PIPING PRIOR TO USE. KW CITY INSPECTED PIPING, NO DEPARTMENT PERSONNEL NOTIFIED. REGISTRATION THAT WAS SUBMITTED WAS INCOMPLETE.
 
SV 10/24/2003 10/29/2003 TREBESCH_CL 0/0 COMPLIANCE ASSURANCE
 
TCI 01/13/2003 02/11/2003 IN-COMPLIANCE DEIDRICK 0/1 COMPLIANCE ASSURANCE
 
SRCA 08/12/2002 10/18/2002 CUMMINGS_B 0/0 DISCHARGE PROJECT
 
 Completion Notes SRCO ISSUED FOR 05/05/1999 DRF. WELL ABANDONMENT REPORT DUE 10/18/2002
 
CALL 02/28/2002 03/07/2002 CUMMINGS_B 0/0 DISCHARGE PROJECT
 
 Completion Notes CALL (VMAIL) FROM RICHARD FARKAS. SAR WAS SENT TO JOHN CARTER WHICH SHOULD HAVE COMPLETED THE DRF. WILL CALL LATER AFTER 1130 AM.
 
CNLI 02/22/2002 02/28/2002 CUMMINGS_B 0/0 DISCHARGE PROJECT
 
 Completion Notes SAR, DUE 02/05/2000, NOT RECEIVED BY DEPARTMENT. NOTIFY DEP BY 03/11/2002 ON ACTIONS TO COMPLETE 62-770 REQUIREMENTS.
 
TCI 01/23/2002 01/24/2002 IN-COMPLIANCE SHULAW 0/1 COMPLIANCE ASSURANCE
 
TCI 01/26/2001 01/26/2001 IN-COMPLIANCE LAWRENCE_W 0/1 COMPLIANCE ASSURANCE
 
NCLI 02/25/2000 02/25/2000 CARTER_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes OPERATED PROVIDED DOCUMENTS TO CLEAR SNC-B.
 
TCI 02/16/2000 02/25/2000 SIGNIFICANT OUT-OF-COMPLIANCE CARTER_J 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes FIRST ROUTINE INSPECTION SINCE REPLACEMENT.
 
CNLI 06/30/1999 10/04/1999 CARTER_J 0/0 DISCHARGE PROJECT
 
 Completion Notes DOSAR LETTER FROM MONROE CO DEPT OF HEALTH
 
TIN 05/08/1999 06/08/1999 MINOR OUT-OF-COMPLIANCE CARTER_J 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes NEW TANK INSTALLED BEFORE, DURING AND AFTER OLD TANK CLOSURE.
 
TXI 05/06/1999 06/07/1999 IN-COMPLIANCE CARTER_J 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes OLD UNDERGROUND GENERATOR TANK REMOVED. CONTAMINATION FOUND.
 
DDCI 05/05/1999 06/30/1999 CARTER_J 0/0 DISCHARGE PROJECT
 
 Completion Notes CLOSURE INSPECTION
 
DRFR 05/05/1999 02/28/2002 CARTER_J 0/0 DISCHARGE PROJECT
 
 Completion Notes DISCOVERED DURING A CLOSURE INSPECTION
 
UTCI 04/15/1998 04/27/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 11/26/2024 Major Out of Compliance FORREST_C 3/1 Routine Compliance
 
Enforcement Referral 09/18/2024 Accepted DOLAN_J Enforcement
 
Letter 09/16/2024 Satisfied SMITH_SAM Compliance Assistance
 
Site Inspection 09/12/2024 Major Out of Compliance SMITH_SAM 2/1 Installation
 
Letter 06/01/2022 Satisfied CUMBIE_B Non-Compliance
 
Site Inspection 05/24/2022 Major Out of Compliance CUMBIE_B 2/1 Routine Compliance
 
Record Document 08/14/2019 Satisfied WINKLER_MG_1 Compliance Assistance
 
Letter 07/11/2019 Satisfied WINKLER_MG_1 Compliance Assistance
 
Site Inspection 07/11/2019 Major Out of Compliance WINKLER_MG_1 2/1 Routine Compliance
 
Site Inspection 06/21/2017 In Compliance WINKLER_MG_1 2/1 Installation
 
Record Document 06/05/2017 Satisfied WINKLER_MG_1 Non-Compliance
 
Meeting 04/08/2017 Satisfied WINKLER_MG_1 Non-Compliance
 
Letter 04/08/2017 Satisfied WINKLER_MG_1 Non-Compliance
 
Site Inspection 04/07/2017 Major Out of Compliance WINKLER_MG_1 1/1 Routine Compliance
 
Site Inspection 04/03/2015 In Compliance WINKLER_MG_1 1/1 Routine Compliance
 
Letter 01/17/2013 Satisfied WINKLER_MG_1 Non-Compliance
 
Site Inspection 01/15/2013 Minor Out of Compliance WINKLER_MG_1 1/1 Routine Compliance
 
Site Inspection 06/17/2011 Major Out of Compliance BEVARD_TK_1 1/1 Routine Compliance
 
Site Inspection 04/22/2010 In Compliance LICHTLER_GB_1 1/1 Routine Compliance
 
Meeting 04/08/2010 Satisfied LICHTLER_GB_1 Non-Compliance
 
Site Inspection 05/11/2009 In Compliance SMITH_RR 1/1 Routine Compliance
 
Site Inspection 08/28/2008 In Compliance SMITH_RR 1/1 Routine Compliance
 
Site Inspection 07/23/2007 In Compliance HAMMONTREE_TD 1/1 Routine Compliance
 
Site Inspection 07/19/2006 In Compliance HAMMONTREE_TD 1/1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/20/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide the spill bucket AOT for tanks 3 and 4 for years 2022 and 2023.
 
11/20/2024 6062 Minor 2.5 Release detection devices not tested annually. Provide AOT of release detection and LLD for the UST for years 2021-2023. If the facility is sticking the interstice monthly in lieu of the annual operability testing, begin documenting this test on the monthly visual inspection and submit records to the Department.
 
11/13/2024 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Provide the missing monthly visual inspections for all three tanks for 2022 and 2023.
 
11/13/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide the three-year integrity testing documentation to the Department.
 
11/05/2024 7002 Minor 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Update the contact information and registration for tank 5 and send to tankregistration@dep.state.fl.us.
 
05/19/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Facility should not receive fuel until Spill Bucket passes integrity test. Submit INF and repair documentation for the Spill Bucket.
 
05/19/2022 6062 Minor 2.5 Release detection devices not tested annually. Complete and submit the Annual Operability for Release Detection to the Department
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
05/05/1999   COMPLETED 8