Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/23/2025 Last Data Refresh: 02/22/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Fuel user/Non-retail | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 8629589 | Latitude | 30° 15' 15.1642 | ||||||||
Name |
ST VINCENTS MEDICAL CENTER-SOUTHSIDE 4201 BELFORT RD |
Longitude | 81° 34' 55.3672 | ||||||||
JACKSONVILLE, FL 32216-1431 | LL Method | DPHO | |||||||||
Contact | MATT JENKINS | LL Status | REVIEWED | ||||||||
Phone | (904) 296-3832 | Status Date | 10/14/2003 | ||||||||
Account Owner Information | |||||||||||
Name | ST LUKES-ST VINCENTS HEALTHCARE INC 4201 BELFORT RD JACKSONVILLE, FL 32216 |
Effective Date | 04/09/2008 | ||||||||
Contact | CAROL IPPOLITO | ||||||||||
Phone | (904) 296-3832 | ||||||||||
CRYSTAL.MAILLARD@JAXHEALTH.COM | |||||||||||
Placard # / Date | 681982 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | ST LUKES-ST VINCENTS HEALTHCARE INC 4201 BELFORT RD JACKSONVILLE, FL 32216 |
Effective Date | 02/20/2012 | ||||||||
Contact | CAROL IPPOLITO | ||||||||||
Phone | (904) 296-3832 | ||||||||||
CRYSTAL.MAILLARD@JAXHEALTH.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 20000 | Emerg Generator Diesel (G) | 08/01/1998 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(C) Fiberglass (F) Double wall (N) Approved synthetic material |
(2) Visual inspect pipe sumps (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs (V) Suction pump check valve |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 20000 | Emerg Generator Diesel (G) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel | (C) Fiberglass | (I) Not required | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 07/01/2024 | 07/01/2025 | BEAZLEY GROUP | ||||||||
INSURANCE | 07/01/2023 | 07/01/2024 | IRONSHORE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 07/01/2022 | 07/01/2023 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 07/01/2021 | 07/01/2022 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 07/01/2020 | 07/01/2021 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 07/01/2019 | 07/01/2020 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 07/02/2018 | 07/02/2019 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2017 | 09/30/2018 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2016 | 09/30/2017 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2015 | 09/30/2016 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2014 | 09/30/2015 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2013 | 09/30/2014 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2012 | 09/30/2013 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2011 | 09/30/2012 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/30/2011 | 09/30/2011 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/16/2010 | 09/16/2011 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/16/2009 | 09/16/2010 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 09/16/2008 | 09/16/2009 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/13/2005 | 04/14/2005 | IN-COMPLIANCE | TORSANKO | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 04/02/2004 | 04/10/2004 | IN-COMPLIANCE | BORISADE | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 05/14/2003 | 05/19/2003 | IN-COMPLIANCE | TOWNSEND_C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 02/11/2002 | 02/13/2002 | IN-COMPLIANCE | BORISADE_C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 11/02/2000 | 11/08/2000 | IN-COMPLIANCE | BORISADE_C | 0/1 | COMPLIANCE ASSURANCE | |||||
CWOE | 12/06/1999 | 12/09/1999 | HOFFMAN_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 11/22/1999 | 12/13/1999 | BORISADE_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes .400(3) .600(1)B | |||||||||||
TCI | 11/22/1999 | 12/13/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | BORISADE_C | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO INSURANCE/NO RDRL | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 02/21/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||||||
Letter | 01/23/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||||||
Site Inspection | 01/23/2025 | Major Out of Compliance | VILLEGASAVILA_OE_1 | 0/1 | Routine Compliance | ||||||
Enforcement Tracking | 07/20/2023 | Closed Without Enforcement | MILLS_MM | Enforcement | |||||||
Enforcement Referral | 06/06/2023 | Accepted | RICHARDS_JE_1 | Enforcement | |||||||
Letter | 03/20/2023 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Electronic Communication | 03/20/2023 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Letter | 12/12/2022 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Site Inspection | 12/12/2022 | Minor Out of Compliance | BRANCH_BL_1 | 0/1 | Routine Compliance | ||||||
Letter | 04/06/2022 | Satisfied | QUICK_V | Enforcement | |||||||
Enforcement Tracking | 04/06/2022 | Closed Without Enforcement | QUICK_V | Enforcement | |||||||
Document Management | 04/06/2022 | Satisfied | QUICK_V | Enforcement | |||||||
Enforcement Referral | 04/27/2021 | Accepted | RICHARDS_JE_1 | Enforcement | |||||||
Electronic Communication | 04/06/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Electronic Communication | 03/15/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Site Inspection | 02/01/2021 | Major Out of Compliance | BRANCH_BL_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 02/01/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Letter | 02/01/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Electronic Communication | 01/21/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||||||
Enforcement Tracking | 12/03/2018 | Closed Without Enforcement | OLIVA_L | Enforcement | |||||||
Letter | 12/03/2018 | Satisfied | OLIVA_L | Enforcement | |||||||
Enforcement Referral | 11/20/2018 | Accepted | RICHARDS_JE_1 | Enforcement | |||||||
Electronic Communication | 11/08/2018 | Satisfied | LUNN_RJ_1 | Compliance Assistance | |||||||
Electronic Communication | 10/29/2018 | Satisfied | LUNN_RJ_1 | Routine Compliance | |||||||
Letter | 08/16/2018 | Satisfied | LUNN_RJ_1 | Compliance Assistance | |||||||
Site Inspection | 08/16/2018 | Major Out of Compliance | LUNN_RJ_1 | 0/1 | Routine Compliance | ||||||
Letter | 02/09/2016 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Electronic Communication | 02/04/2016 | Satisfied | MONDO_PW_1 | Routine Compliance | |||||||
Site Inspection | 02/04/2016 | In Compliance | MONDO_PW_1 | 0/1 | Routine Compliance | ||||||
Document Management | 02/04/2016 | Complete | MONDO_PW_1 | Routine Compliance | |||||||
Electronic Communication | 01/06/2016 | Satisfied | MONDO_PW_1 | Routine Compliance | |||||||
Site Inspection | 02/24/2014 | In Compliance | WILLIAMS_AK_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 02/24/2014 | Satisfied | WILLIAMS_AK_1 | Routine Compliance | |||||||
Site Inspection | 02/14/2012 | In Compliance | CAIN_M_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 02/14/2012 | Satisfied | CAIN_M_1 | Routine Compliance | |||||||
Site Inspection | 10/24/2010 | In Compliance | BORISADE_KA_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 05/26/2010 | In Compliance | SPEARS_CV_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 02/10/2010 | Satisfied | WILLIAMS_EM_1 | Routine Compliance | |||||||
Site Inspection | 05/06/2009 | In Compliance | WILLIAMS_AK_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 11/18/2008 | Satisfied | TOWLE_M | Non-Compliance | |||||||
Enforcement Tracking | 11/14/2008 | Closed Without Enforcement | TOWLE_M | Enforcement | |||||||
Phone Conversation | 11/14/2008 | Satisfied | TOWLE_M | Enforcement | |||||||
Enforcement Referral | 10/06/2008 | Accepted | TOWLE_M | Enforcement | |||||||
Letter | 09/09/2008 | Satisfied | WILLIAMS_AK_1 | Non-Compliance | |||||||
Record Document | 08/06/2008 | Satisfied | WILLIAMS_EM_1 | Non-Compliance | |||||||
Letter | 07/29/2008 | Satisfied | WILLIAMS_AK_1 | Non-Compliance | |||||||
Record Document | 07/24/2008 | Satisfied | LUNN_RJ_1 | Closure | |||||||
Record Document | 06/24/2008 | Satisfied | WILLIAMS_EM_1 | Non-Compliance | |||||||
Letter | 06/06/2008 | Satisfied | WILLIAMS_AK_1 | Non-Compliance | |||||||
Site Inspection | 06/06/2008 | Major Out of Compliance | WILLIAMS_AK_1 | 0/1 | Routine Compliance | ||||||
Enforcement Tracking | 07/25/2007 | Closed With Enforcement | DOHANEY_T | Enforcement | |||||||
Enforcement Referral | 07/25/2007 | Rejected | DOHANEY_T | Enforcement | |||||||
Enforcement Referral | 07/25/2007 | Accepted | DEFALCO_L | Enforcement | |||||||
Site Inspection | 06/19/2007 | In Compliance | WILLIAMS_AK_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 05/11/2007 | Satisfied | DEFALCO_L | Enforcement | |||||||
Issue Document | 04/26/2007 | Satisfied | DEFALCO_L | Enforcement | |||||||
Site Inspection | 04/19/2007 | In Compliance | LUNN_RJ_1 | 0/1 | Installation | ||||||
Site Inspection | 04/19/2007 | In Compliance | LUNN_RJ_1 | 0/1 | Closure | ||||||
TCAR | 04/17/2007 | Satisfied | HOLLOWAY_RW_1 | Closure | |||||||
Enforcement Referral Activity - OLD | 10/25/2006 | Terminated | DOHANEY_T | Enforcement | |||||||
Letter | 10/19/2006 | Satisfied | GRIFFIN_TW_1 | Non-Compliance | |||||||
Enforcement Referral Activity - OLD | 09/12/2006 | Terminated | DOHANEY_T | Enforcement | |||||||
Letter | 09/12/2006 | Satisfied | GRIFFIN_TW_1 | Non-Compliance | |||||||
Site Inspection | 09/12/2006 | Major Out of Compliance | GRIFFIN_TW_1 | 0/2 | Routine Compliance | ||||||
Letter | 09/08/2006 | Satisfied | GRIFFIN_TW_1 | Non-Compliance | |||||||
Letter | 09/07/2006 | Satisfied | GRIFFIN_TW_1 | Non-Compliance | |||||||
Record Document | 09/07/2006 | Satisfied | TORSANKO_G | Non-Compliance | |||||||
Site Inspection | 06/21/2006 | Major Out of Compliance | TORSANKO_G | 0/2 | Non-Compliance | ||||||
Site Inspection | 04/29/2006 | Major Out of Compliance | TORSANKO_G | 0/1 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/23/2025 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Provide current training certificates for designated Class A, B, and C to the EQD Inspector. | |||||||
01/21/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Manage the repair/replacement of the defective components of the ATG. Retest and provide results. | |||||||
01/21/2025 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | The facility must remove the water/sludge from the spill bucket, the piping sump in the tank, and the transition sump. The facility must ensure the piping sump sensor status is returned to normal. Provide photos to the EQD Inspector. | |||||||
01/21/2025 | 6061 | SNC-B | 4.12 Release detection devices for integral piping do not meet general standards. | Pressurized integral piping in contact with the soil shall be equipped with a release detection system that can detect a leak within one hour. Manage the installation of an automatic line leak detector that meets regulatory standards. Perform operability test and provide documentation to EQD Inspector. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
07/31/1991 | COMPLETED | 25 | |||||||||