Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Marine/Coastal Fuel Storage
 
County Pinellas   Status    OPEN
 
ID 8630856   Latitude    27° 41' 30.5542
 
Name TIERRA VERDE MARINA
100 PINELLAS BAYWAY S
Longitude    82° 43' 9.6012
  TIERRA VERDE, FL 33715-1700 LL Method    DPHO
 
Contact KEVIN BARTKOVSKY   LL Status    REVIEWED
 
Phone (727) 710-0869   Status Date    08/29/2003
 
Account Owner Information
 
Name CYPRESS PROPERTY MGMT SRVCS
5300 W CYPRESS ST
TAMPA, FL 33607
Effective Date    07/20/2011
 
Contact JEREMY HECKLER
 
Phone (202) 355-3578
 
Email JHECKLER@TVMARINA.COM
  Placard # / Date    687079 - 06/12/2024
Property Owner Information
 
Name CYPRESS PROPERTY MGMT SRVCS
5300 W CYPRESS ST
TAMPA, FL 33607
Effective Date    10/05/2012
 
Contact JEREMY HECKLER
 
Phone (202) 355-3578
 
Email JHECKLER@TVMARINA.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
3 16000 Unleaded Gas (B) 10/01/1993 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (B) Steel/galvanized metal
(G) Pipe trench liner
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
4 12000 Unleaded Gas (B) 10/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/10/2024 05/10/2025 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2023 05/10/2024 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2022 05/10/2023 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2021 05/10/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2020 05/10/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2019 05/10/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2018 05/10/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2017 05/10/2018 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2016 05/10/2017 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2015 05/10/2016 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2014 05/10/2015 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/10/2013 05/10/2014 ACE
INSURANCE   05/10/2012 05/10/2013 ACE
INSURANCE   05/10/2011 05/10/2012 ACE
INSURANCE   05/10/2010 05/10/2011 ACE
INSURANCE   05/02/2008 05/02/2009 ACE
INSURANCE   12/23/1993 12/23/1998 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
DPRI 08/03/2005 08/04/2005 IN-COMPLIANCE FRAZIER 0/0 TERMINAL FACILITY PROJECT
 
TCI 08/03/2005 08/04/2005 IN-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
LTR 08/03/2005 08/04/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/09/2005 06/13/2005 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCR 06/01/2005 06/07/2005 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT 0/3 COMPLIANCE ASSURANCE
 
NCLI 06/01/2005 06/07/2005 BARNETT 0/0 COMPLIANCE ASSURANCE
 
NCLI 05/19/2005 05/23/2005 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCI 05/18/2005 05/23/2005 MINOR OUT-OF-COMPLIANCE BARNETT 0/3 COMPLIANCE ASSURANCE
 
LTR 12/20/2004 12/29/2004 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TIN 12/17/2004 12/29/2004 IN-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
LTR 04/23/2004 04/29/2004 PINK 0/0 COMPLIANCE ASSURANCE
 
TCI 04/23/2004 04/29/2004 IN-COMPLIANCE PINK 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes MARINA TANKS PIPE-GREEN TAPE IN EARTHEN SUMPS; PRIMARY TYPE NOT VISIBLE
 
DPRI 04/23/2004 04/29/2004 PINK 0/0 TERMINAL FACILITY PROJECT
 
RRBD 07/11/2003 07/15/2003 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO CORRECTION - SENSORS TESTED BUT DO NOT HAVE POSITIVE SHUT-DOWN OF PUMPS WHEN TRIPPED
 
RRBD 05/08/2003 06/04/2003 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
NCLI 04/30/2003 05/01/2003 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
DPRI 04/25/2003 05/15/2003 IN-COMPLIANCE STRAUSS 0/0 TERMINAL FACILITY PROJECT
 
TCI 04/25/2003 05/01/2003 MINOR OUT-OF-COMPLIANCE STRAUSS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes PIPE NOT VISIBLE
 
LTR 04/22/2002 05/06/2002 TAM 0/0 COMPLIANCE ASSURANCE
 
DPRI 04/18/2002 06/14/2002 IN-COMPLIANCE TAM 0/0 TERMINAL FACILITY PROJECT
 
TCI 04/17/2002 05/05/2002 IN-COMPLIANCE TAM 0/3 COMPLIANCE ASSURANCE
 
DPRI 03/16/2001 03/27/2001 IN-COMPLIANCE EASTMAN_T 0/0 TERMINAL FACILITY PROJECT
 
TCI 07/17/2000 08/01/2000 IN-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
TCI 08/27/1999 08/31/1999 IN-COMPLIANCE CASTOR 0/0 COMPLIANCE ASSURANCE
 
RRBD 07/07/1999 07/12/1999 SOWERS 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/11/1999 06/15/1999 SOWERS 0/0 COMPLIANCE ASSURANCE
 
TCI 05/26/1999 05/27/1999 MINOR OUT-OF-COMPLIANCE SOWERS 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 03/27/2024 Major Out of Compliance PUHR_NM_1 0/2 Routine Compliance
 
Letter 03/27/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Letter 02/18/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 02/18/2022 Major Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Electronic Communication 12/09/2021 Satisfied COLSON_NJ_1 Routine Compliance
 
Enforcement Referral 09/27/2019 Accepted COLSON_NJ_1 Enforcement
 
Electronic Communication 09/10/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 09/10/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 09/10/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 09/10/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 05/10/2019 Major Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Letter 05/10/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 04/26/2019 Satisfied COLSON_NJ_1 Routine Compliance
 
Record Document 03/04/2016 Satisfied COLSON_NJ_1 Non-Compliance
 
Phone Conversation 01/28/2016 Satisfied COLSON_NJ_1 Non-Compliance
 
Letter 01/26/2016 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 01/26/2016 Major Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Electronic Communication 01/13/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
TCAR 03/19/2014 Satisfied ROGGELIN_EM_1 Closure
 
Letter 03/19/2014 Satisfied ROGGELIN_EM_1 Closure
 
Document Management 03/19/2014 Complete ROGGELIN_EM_1 Closure
 
Record Document 12/30/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Issue Document 11/26/2013 Satisfied ROGGELIN_EM_1 Closure
 
Site Inspection 11/25/2013 Minor Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Letter 11/25/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 06/17/2013 Satisfied ROGGELIN_EM_1 Closure
 
Record Document 09/11/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 09/04/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 09/04/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 09/04/2012 Minor Out of Compliance STRAUSS_RH_1 0/2 Installation
 
Site Inspection 08/29/2012 Minor Out of Compliance LONGEN_JL_1 0/1 Closure
 
Letter 08/29/2012 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 06/14/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 06/14/2012 Minor Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Issue Document 06/12/2012 Satisfied STRAUSS_RH_1 Routine Compliance
 
Letter 05/23/2012 Satisfied STRAUSS_RH_1 Closure
 
Issue Document 02/20/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
TCAR 12/27/2011 Satisfied STRAUSS_RH_1 Closure
 
Enforcement Tracking 06/15/2011 Closed Without Enforcement PEDIGO_L Enforcement
 
Site Inspection 06/02/2011 Major Out of Compliance STRAUSS_RH_1 0/2 Non-Compliance
 
Letter 06/02/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Emergency Preparedness Information 05/11/2011 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 05/06/2011 Major Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Letter 05/06/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Incident 03/22/2011 Has not led to Discharge STRAUSS_RH_1 Incident
 
Issue Document 01/21/2011 Satisfied STRAUSS_RH_1 Routine Compliance
 
Discharge Reporting 06/18/2010 Satisfied SOWERS_JA_1 Discharge
 
Document Management 06/18/2010 Complete SOWERS_JA_1 Discharge
 
Letter 06/15/2010 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Letter 06/14/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 06/14/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 06/14/2010 Major Out of Compliance STRAUSS_RH_1 0/1 Non-Compliance
 
Site Inspection 06/03/2010 Major Out of Compliance ROGGELIN_EM_1 0/1 Installation
 
Letter 05/21/2010 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Site Inspection 05/17/2010 Major Out of Compliance ROGGELIN_EM_1 0/1 Installation
 
Electronic Communication 04/30/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Emergency Preparedness Information 04/23/2010 Satisfied STRAUSS_RH_1 Routine Compliance
 
Letter 04/12/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 04/12/2010 Major Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Record Document 03/11/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 03/03/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 11/05/2009 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 11/05/2009 Major Out of Compliance STRAUSS_RH_1 0/2 Closure
 
Letter 04/14/2009 Satisfied BARNETT_JX Non-Compliance
 
Site Inspection 04/14/2009 Major Out of Compliance BARNETT_JX 0/3 Routine Compliance
 
Letter 02/16/2009 Satisfied BARNETT_JX Non-Compliance
 
Site Inspection 02/16/2009 Major Out of Compliance BARNETT_JX 0/3 Closure
 
Record Document 09/11/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 04/30/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 04/29/2008 Major Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Site Inspection 02/29/2008 Major Out of Compliance LONGEN_JL_1 0/2 Non-Compliance
 
Letter 02/29/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Record Document 01/04/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Enforcement Referral 10/09/2007 Accepted MARSH_L Enforcement
 
Site Inspection 10/05/2007 Major Out of Compliance LONGEN_JL_1 0/3 Non-Compliance
 
Letter 10/05/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 07/18/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 07/09/2007 Major Out of Compliance LONGEN_JL_1 0/3 Non-Compliance
 
Letter 06/19/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 05/16/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 05/15/2007 Major Out of Compliance LONGEN_JL_1 0/3 Non-Compliance
 
Site Inspection 03/27/2007 Major Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/27/2024 6066 Minor 4.4 Not repaired per applicable standards. Treat/repair the corrosion in the STP sump as necessary and submit documentation to this office for review once completed.
 
02/18/2022 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair the Premium spill bucket as necessary. Notify this office if more than the Primary insert must be replaced. Submit post-installation integrity test results once repairs are complete.
 
05/10/2019 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Fill out & submit an Incident Notification Form. Investigate the Incident (vacuum test the bucket) & then submit investigation results to this office.
 
05/10/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Submit current integrity test results for the (4) double walled spill buckets.
 
05/10/2019 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Repair/replace the faulty sensor. Submit work receipts to this office for review, once corrected.
 
05/10/2019 4067 Minor 4.2 Release detection devices not tested annually. Submit current test results for the (4) spill bucket VisiGauges.
 
05/10/2019 4067 Minor 4.2 Release detection devices not tested annually. Submit current test results for the EBW monitoring panel & (2) liquid sensors.
 
05/10/2019 4079 Minor 2.7 Records requiring 3 years documentation period not kept by facility. Submit the missing test results, if found. Provide current test results for the (2) mechanical line leak detectors on the convenience store UST system.
 
05/10/2019 4067 Minor 4.2 Release detection devices not tested annually. Submit current test results for the tank interstice vacuum gauge.
 
05/10/2019 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Submit current test results for the (2) ball float valves in the Marina side UST and for the (2) flow shutoff valves in the C-Store side UST.
 
05/10/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Submit current integrity test results for the (2) C-Store side STP sumps.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
11/09/2009   COMPLETED 7
 
07/21/1993   COMPLETED
 
07/13/1990   COMPLETED