Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 8631217 | Latitude | 28° 7' 59.5078 | ||||||||
Name |
MARATHON 39720 US HWY 19 N |
Longitude | 82° 44' 26.4599 | ||||||||
TARPON SPRINGS, FL 34689-9406 | LL Method | DPHO | |||||||||
Contact | SEERAM, RALPH | LL Status | REVIEWED | ||||||||
Phone | (727) 934-9408 | Status Date | 05/30/2024 | ||||||||
Account Owner Information | |||||||||||
Name | BANGAL PROPERTY MANAGEMENT LLC 39720 US HWY 19 N TARPON SPRINGS, FL 34689 |
Effective Date | 09/29/2008 | ||||||||
Contact | GAZI RAHMAN | ||||||||||
Phone | (813) 986-6180 | ||||||||||
NICKMAJLISH@YAHOO.COM | |||||||||||
Placard # / Date | 684479 - 06/06/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | BANGAL PROPERTY MANAGEMENT LLC 39720 US HWY 19 N TARPON SPRINGS, FL 34689 |
Effective Date | 04/19/2012 | ||||||||
Contact | GAZI RAHMAN | ||||||||||
Phone | (813) 986-6180 | ||||||||||
NICKMAJLISH@YAHOO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 15000 | Unleaded Gas (B) | 09/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (I) Suction piping system (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (M) Manual tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10000 | Vehicular Diesel (D) | 09/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (I) Suction piping system (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (M) Manual tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Unleaded Gas (B) | 02/01/1985 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 6000 | Unleaded Gas (B) | 02/01/1985 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 6000 | Unleaded Gas (B) | 02/01/1985 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/15/2023 | 10/15/2024 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/15/2021 | 10/15/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2020 | 10/15/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2018 | 10/15/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2016 | 10/15/2017 | ACE | ||||||||
INSURANCE | 10/15/2014 | 10/15/2015 | ACE | ||||||||
INSURANCE | 10/15/2013 | 10/15/2014 | ACE | ||||||||
INSURANCE | 10/15/2011 | 10/15/2012 | ACE | ||||||||
INSURANCE | 10/15/2010 | 10/15/2011 | ACE | ||||||||
INSURANCE | 10/15/2009 | 10/15/2010 | ILLINOIS UNION | ||||||||
INSURANCE | 10/15/2008 | 10/15/2009 | ACE | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
CRDE | 02/06/2006 | 02/10/2006 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 10/17/2005 | 10/18/2005 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/12/2005 | 10/18/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |||||
SCOE | 10/06/2005 | 10/09/2005 | RANDOLPH_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 07/13/2004 | 07/15/2004 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/12/2004 | 07/15/2004 | MINOR OUT-OF-COMPLIANCE | PINK | 0/3 | COMPLIANCE ASSURANCE | |||||
LTR | 02/13/2004 | 02/17/2004 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED COMPLIANCE SERVICES INC - RESOLVE TANK OWNERSHIP ISSUES IN STCM DATABASE. | |||||||||||
LTR | 02/13/2004 | 02/17/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes INF OF 1/18/04 FOR SIR REPORT - RCVD FACILITY TIGHTNESS TEST REPORT & LLD FUNCTION TESTS OF JAN 26, 2004. - RESOLVED | |||||||||||
RRBD | 01/20/2004 | 02/05/2004 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
CRDE | 05/08/2003 | 05/16/2003 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/07/2003 | 02/10/2003 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
LTR | 02/07/2003 | 02/10/2003 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 01/15/2003 | 01/21/2003 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 01/14/2003 | 01/21/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | TAM | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DW AMERON FLEX PIPE (RED) | |||||||||||
RRBD | 10/02/2001 | 10/04/2001 | COMPLIANCE ASSURANCE | ||||||||
TCI | 09/24/2001 | 10/01/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | HALSCOTT | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 02/05/2001 | 02/05/2001 | COMPLIANCE ASSURANCE | ||||||||
TCI | 10/23/2000 | 10/30/2000 | MINOR OUT-OF-COMPLIANCE | HALSCOTT | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 09/27/2000 | 10/02/2000 | HALSCOTT | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 06/20/2000 | 06/30/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | HALSCOTT | 0/3 | COMPLIANCE ASSURANCE | |||||
UTII | 12/09/1998 | 12/20/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Record Document | 07/03/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Site Inspection | 05/16/2024 | Major Out of Compliance | MUSLIC_A_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/16/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Electronic Communication | 05/06/2024 | Satisfied | MUSLIC_A_1 | Routine Compliance | |||||||
Letter | 06/16/2022 | Satisfied | GREEN_SM | Enforcement | |||||||
Enforcement Referral | 05/16/2022 | Accepted | SHOCK_E_1 | Enforcement | |||||||
Letter | 05/04/2022 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||||||
Site Inspection | 05/02/2022 | Major Out of Compliance | SHOCK_E_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 04/04/2022 | Satisfied | SHOCK_E_1 | Routine Compliance | |||||||
Letter | 11/15/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 11/15/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 10/28/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 10/21/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 10/21/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Record Document | 06/04/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 05/24/2019 | Major Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/24/2019 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Electronic Communication | 05/07/2019 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 02/28/2018 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 02/28/2018 | In Compliance | STRAUSS_RH_1 | 0/2 | Compliance Assistance | ||||||
Meeting | 02/19/2018 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Meeting | 07/06/2017 | Satisfied | STRAUSS_RH_1 | Compliance Assistance | |||||||
Site Inspection | 02/13/2017 | Major Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Letter | 02/13/2017 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Electronic Communication | 02/02/2017 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Site Inspection | 12/18/2014 | In Compliance | STRAUSS_RH_1 | 0/2 | Non-Compliance | ||||||
Electronic Communication | 12/18/2014 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 09/29/2014 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Letter | 09/04/2014 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 09/04/2014 | Minor Out of Compliance | STRAUSS_RH_1 | 0/2 | Routine Compliance | ||||||
Record Document | 04/13/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 02/08/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 02/08/2012 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Discharge Reporting | 04/05/2011 | Satisfied | STRAUSS_RH_1 | Discharge | |||||||
Letter | 04/05/2011 | Satisfied | STRAUSS_RH_1 | Discharge | |||||||
Record Document | 03/17/2011 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 11/05/2010 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 11/05/2010 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 02/26/2010 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Non-Compliance | ||||||
Letter | 02/26/2010 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Record Document | 11/09/2009 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 10/16/2009 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 10/16/2009 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
Site Inspection | 10/16/2009 | Major Out of Compliance | LONGEN_JL_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 10/30/2008 | In Compliance | LONGEN_JL_1 | 0/2 | Installation | ||||||
TCAR | 10/14/2008 | Satisfied | STRAUSS_RH_1 | Closure | |||||||
Record Document | 09/15/2008 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Record Document | 09/03/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 08/29/2008 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Site Inspection | 08/29/2008 | Major Out of Compliance | BARNETT_JX | 0/3 | Closure | ||||||
Enforcement Referral | 08/07/2008 | Accepted | RANDOLPH_L | Enforcement | |||||||
Enforcement Tracking | 08/07/2008 | Closed With Enforcement | RANDOLPH_L | Enforcement | |||||||
Emergency Preparedness Information | 01/03/2008 | Satisfied | BARNETT_JX | Routine Compliance | |||||||
Site Inspection | 07/19/2007 | Major Out of Compliance | BARNETT_JX | 0/3 | Routine Compliance | ||||||
Letter | 07/19/2007 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Emergency Preparedness Information | 02/09/2007 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/19/2006 | Satisfied | BARNETT_JX | Routine Compliance | |||||||
Enforcement Referral Activity - OLD | 09/14/2006 | Terminated | CULBRETH_L | Enforcement | |||||||
Record Document | 09/08/2006 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Site Inspection | 07/18/2006 | Major Out of Compliance | BARNETT_JX | 0/3 | Routine Compliance | ||||||
Letter | 07/18/2006 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/16/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Complete operability test of line leak detectors and submit test results to this office. | |||||||
05/16/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove corrosion and ensure all components are in working order. | |||||||
05/16/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove and properly dispose of PCW from STP sumps and perform STP sump integrity test on all three STP sumps. Submit waste manifest and STP sump integrity test results to this office. | |||||||
05/16/2024 | 6002 | Minor | 2.1 Operator Training records not available. | Submit Class A, B, and C certificates for the facility. | |||||||
05/16/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Submit monthly visual inspection records for period from April 2022 to present. | |||||||
05/16/2024 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Submit financial responsibility records, including relevant State Forms, to this office. | |||||||
05/16/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Complete integrity tests of all 3 double-walled spill buckets, 4 dispenser sumps, and 3 STP sumps and submit test results to this office. | |||||||
05/14/2024 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Repair or replace inoperable EZ-gauges, perform operability test, and submit test results to this office. | |||||||
05/02/2022 | 6055 | SNC-A | 4.6 Cannot detect a release from any portion of the system. (Including Emergency power generator storage tank systems installed prior to rule do not meet release detection requirements by October 13, 2018.) | Provide documentation (photographs) that the interstitial openings on the tanks can be opened and manually/visually inspected. | |||||||
05/02/2022 | 6021 | SNC-B | 4.1 Failure of secondary containment to meet standards including: impervious spill containment, liners, allowing for release detection, allow for monitoring point, and hydrant pit secondary containment. | Provide documentation (photographs) that the interstitial openings on the tanks can be opened and manually/visually inspected. | |||||||
04/29/2022 | 6061 | SNC-B | 4.12 Release detection devices for integral piping do not meet general standards. | Complete testing of 3 mechanical line leak detectors and provide results. | |||||||
04/29/2022 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Complete annual operability testing for 3 overfill flow shut-off valves and provide testing results. | |||||||
04/28/2022 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Perform necessary maintenance so that ports to tank interstices are readily accessible for stick check / release detection. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
09/04/2008 | COMPLETED | ||||||||||