Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Volusia | Status | OPEN | ||||||||
ID | 8731593 | Latitude | 28° 54' 43.5708 | ||||||||
Name |
CHEVRON SAXON BLVD & I-4 2123 SAXON BLVD |
Longitude | 81° 16' 1.534 | ||||||||
DELTONA, FL 32725-3224 | LL Method | DPHO | |||||||||
Contact | Donna Sada | LL Status | REVIEWED | ||||||||
Phone | (407) 886-3338 | Status Date | 07/15/2005 | ||||||||
Account Owner Information | |||||||||||
Name | EXPERT CAR CARE 3 LLC 2123 SAXON BLVD Deltona, FL 32725 |
Effective Date | 09/22/2011 | ||||||||
Contact | Donna Sada | ||||||||||
Phone | (407) 655-9958 | ||||||||||
DONNASADAEXPERT@GMAIL.COM | |||||||||||
Placard # / Date | 700321 - 07/30/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | EXPERT CAR CARE 3 LLC 2123 SAXON BLVD Deltona, FL 32725 |
Effective Date | 01/13/2010 | ||||||||
Contact | Donna Sada | ||||||||||
Phone | (407) 655-9958 | ||||||||||
DONNASADAEXPERT@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 15000 | Unleaded Gas (B) | 02/01/1999 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (L) Compartmented (M) Spill containment bucket (R) Double wall - tank jacket |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Unleaded Gas (B) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system |
(8) Manually sampled wells (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8000 | Unleaded Gas (B) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system |
(8) Manually sampled wells (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 5000 | Unleaded Gas (B) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system |
(8) Manually sampled wells (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 5000 | Vehicular Diesel (D) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system |
(8) Manually sampled wells (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 500 | Waste Oil (L) | 04/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells (M) Manual tank gauging - USTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/28/2017 | 02/28/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/28/2016 | 02/28/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/28/2015 | 02/28/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/28/2013 | 02/28/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/28/2012 | 02/28/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 12/31/2010 | 12/31/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 01/02/2010 | 01/02/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 12/31/2008 | 12/31/2009 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 03/14/2006 | 03/15/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | MOSER_T | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes NUMEROUS VIOLATIONS NOTED. | |||||||||||
TCI | 04/18/2005 | 05/03/2005 | IN-COMPLIANCE | MOSER_T | 0/2 | COMPLIANCE ASSURANCE | |||||
TCR | 10/13/2004 | 10/14/2004 | IN-COMPLIANCE | EJ | 2/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes SPILL BUCKET HAS BEEN INSTALLED FOR USED OIL TANK. | |||||||||||
RRBD | 08/26/2004 | 08/26/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED COPY OF RDRL AND STATEMENT OF SPILL CONTAINMENT INSTALLATION ON USED OIL TANK. | |||||||||||
CALL | 08/24/2004 | 08/25/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes SPOKE W/ MR. BROWNING AND HE IS TO ADDRESS THE REMANING ISSUES AND CONTACT THIS DEPARTMENT. | |||||||||||
LTR | 08/12/2004 | 08/13/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NO RESPONSE FROM FACILITY SINCE 6/28/04. MAILED ELRA LETTER. WILL REFER IF NO FURTHER CONTACT FROM FACILITY. | |||||||||||
RRBD | 06/28/2004 | 06/28/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED DOCS. INDICATING THE LLD'S AND RD EQUIPMENT WERE TESTED AND PASSED 4/29/04. | |||||||||||
RRBD | 06/24/2004 | 06/24/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED LETTER FROM FACILITY INDICATING LLD'S AND EQUIP. WAS TESTED. RESULTS FORTHCOMING FROM PETRO TECH. | |||||||||||
CALL | 06/22/2004 | 06/23/2004 | EJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes PER BONNIE, EVERYTHING HAS BEEN DONE. SHE IS SENDING A LETTER TO US TODAY. | |||||||||||
WLI | 06/10/2004 | 06/15/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NO RESPONSE TO NCLI. | |||||||||||
NCLI | 04/19/2004 | 04/21/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NCLI MAILED. | |||||||||||
TCI | 04/05/2004 | 04/06/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | DJ | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes RDRL NOT POSTED. VACUUM GAUGE NOT WORKING/TESTED. RD MONITOR AND LLD'S REQUIRE ANNUAL TESTING. USED OIL DROP REQUIRES SPILL BUCKET. | |||||||||||
TCI | 04/02/2003 | 04/02/2003 | IN-COMPLIANCE | DJ | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 05/06/2002 | 05/06/2002 | IN-COMPLIANCE | DJ | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 05/09/2001 | 05/09/2001 | IN-COMPLIANCE | LLW | 0/2 | COMPLIANCE ASSURANCE | |||||
RRBD | 07/13/2000 | 07/17/2000 | LLW | 1/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 06/05/2000 | 06/27/2000 | MINOR OUT-OF-COMPLIANCE | LLW | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 06/14/1999 | 07/01/1999 | IN-COMPLIANCE | MOSER_T | 0/1 | COMPLIANCE ASSURANCE | |||||
TIN | 02/25/1999 | 05/04/1999 | IN-COMPLIANCE | MOSER_T | 0/1 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 11/12/2024 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 05/20/2024 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Site Inspection | 05/10/2024 | Major Out of Compliance | PIERCE_BN_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 02/01/2024 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Enforcement Referral | 03/09/2023 | Accepted | GREGORY_JW_1 | Enforcement | |||||||
Electronic Communication | 12/29/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 12/22/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 11/16/2022 | Satisfied | GREGORY_JW_1 | Compliance Assistance | |||||||
Enforcement Referral | 11/04/2022 | Rejected | GREGORY_JW_1 | Enforcement | |||||||
Letter | 09/22/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Site Inspection | 05/04/2022 | Major Out of Compliance | PIERCE_BN_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 05/04/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 05/04/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 04/01/2022 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||||||
Electronic Communication | 09/22/2021 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Electronic Communication | 02/12/2021 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Phone Conversation | 08/03/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 07/10/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 04/03/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Site Inspection | 03/31/2020 | Major Out of Compliance | PIERCE_BN_1 | 0/1 | Routine Compliance | ||||||
Meeting | 03/24/2020 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||||||
Electronic Communication | 03/24/2020 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||||||
Site Inspection | 03/09/2017 | In Compliance | PERRY_JF_2 | 0/1 | Routine Compliance | ||||||
Site Inspection | 05/13/2015 | In Compliance | PERRY_JF_2 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 05/08/2015 | Satisfied | PERRY_JF_2 | Routine Compliance | |||||||
Site Inspection | 03/28/2013 | In Compliance | COX_CD_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/22/2012 | In Compliance | CRAFT_TT_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/22/2011 | In Compliance | CRAFT_TT_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 12/06/2010 | Satisfied | STAFFORD_P_1 | Non-Compliance | |||||||
Phone Conversation | 12/03/2010 | Satisfied | STAFFORD_P_1 | Non-Compliance | |||||||
Letter | 11/16/2010 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Letter | 06/11/2010 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 06/01/2010 | Minor Out of Compliance | CRAFT_TT_1 | 0/2 | Routine Compliance | ||||||
Record Document | 03/22/2010 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Issue Document | 03/05/2010 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Meeting | 01/07/2010 | Satisfied | COIL_JM_1 | Routine Compliance | |||||||
Site Inspection | 03/25/2009 | In Compliance | CRAFT_TT_1 | 0/2 | Routine Compliance | ||||||
Record Document | 09/03/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Record Document | 09/03/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Record Document | 08/19/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Letter | 08/05/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Record Document | 05/21/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Record Document | 05/20/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Letter | 05/14/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 04/11/2008 | Minor Out of Compliance | MOSER_T | 0/1 | Routine Compliance | ||||||
Site Inspection | 07/19/2007 | In Compliance | LEIGH_MM_1 | 0/6 | Non-Compliance | ||||||
Site Inspection | 04/04/2007 | In Compliance | MOSER_T | 0/2 | Routine Compliance | ||||||
Record Document | 02/15/2007 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/14/2007 | Satisfied | LEIGH_MM_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/19/2006 | Satisfied | MOSER_T | Routine Compliance | |||||||
Letter | 08/09/2006 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/10/2024 | 6079 | SNC-B | 4.10 USTs not closed with 90 days of discovery, or not meeting requirements, unable to be repaired or no FR. | Please work with a certified Pollutant Storage System Contractor (PSSC) to perform a proper closure in place. A full closure assessment with soil sampling should be performed. All corrective action should be supplied to FDEP Central District staff. | |||||||
05/04/2022 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Please arrange for access to be provided to the tank interstitial monitoring. Please contact Brittany.Finney@ocfl.net to arrange access. | |||||||
05/04/2022 | 6001 | Minor | 2.1 No reasonable access provided. | Please arrange for access to be provided to all system components. Please contact Brittany.Finney@ocfl.net to arrange access. | |||||||
03/31/2020 | 4014 | SNC-B | 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. | Please provide storage tank insurance documentation from February 2018 through present. Please supply to Brittany.Finney@ocfl.net. | |||||||
03/31/2020 | 4001 | Minor | 2.2 Operator certification requirements not met. | If tanks will be left in service: Please have applicable representatives complete operator A, B, C training. Please use the following link to access approved operator training for Florida: https://floridadep.gov/waste/permitting-compliance-assistance/content/underground-storage-tank-operator-training. If tanks will be taken out of service: please complete all applicable out of service requirements to close this violation. | |||||||
03/31/2020 | 4059 | SNC-B | 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. | If tanks will be left in service: Please immediately begin completing monthly visual inspections. Please submit the next two months of inspection records as they are completed. Please submit to Brittany.Finney@ocfl.net. If tanks will be taken out of service: please complete all applicable out of service requirements to close this violation. | |||||||
03/31/2020 | 4018 | SNC-B | 2.7 Removal of regulated substance from a release not initiated within three days and completed within 30 days of discovery. | Please have petroleum contact water removed and properly disposed of. Please supply manifest for review to close violation. Please contact Brittany.Finney@ocfl.net for a re-inspection once PCW is removed and access can be provided to all system components. Alternatively, please supply manifest for review and take tanks properly out of service. | |||||||
03/31/2020 | 4067 | Minor | 4.2 Release detection devices not tested annually. | If tanks will be left in service: Please arrange for testing of the system components. Please forward testing to Brittany.Finney@ocfl.net. If tanks will be taken out of service: please complete all applicable out of service requirements to close this violation. | |||||||
03/31/2020 | 4057 | Minor | 4.31 Overfill protection devices not registered or tested annually. | If tanks will be left in service: Please arrange for testing of the system components. Please forward testing to Brittany.Finney@ocfl.net. If tanks will be taken out of service: please complete all applicable out of service requirements to close this violation. | |||||||
03/31/2020 | 4076 | Minor | 4.11 Failure to conduct required periodic containment and interstitial integrity testing. | If tanks will be left in service: Please arrange for integrity testing of the system components. Please forward testing to Brittany.Finney@ocfl.net. If tanks will be taken out of service: please complete all applicable out of service requirements to close this violation. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/19/1998 | COMPLETED | 29 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||