DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Citrus   Status    OPEN
 
ID 8731642   Latitude    28° 53' 34.1799
 
Name CIRCLE K #2705995
2025 N LECANTO HWY
Longitude    82° 29' 1.3654
  LECANTO, FL 34461-9675 LL Method    DPHO
 
Contact GRAHAM BIGGS   LL Status    REVIEWED
 
Phone (919) 774-6700   Status Date    02/07/2003
 
Account Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    05/12/2008
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
  Placard # / Date    697792 - 06/28/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
4 30000 Unleaded Gas (B) 12/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 6000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   04/30/2023 08/28/2024
GUARANTEE   04/24/2022 08/21/2023
INSURANCE   12/01/2020 12/01/2021 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2019 12/01/2020 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2018 12/01/2019 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2017 12/01/2018 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2016 12/01/2017 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2015 12/01/2016 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2014 12/01/2015 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2013 12/01/2014 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2011 12/01/2013 CHUBB
INSURANCE   12/17/2010 12/16/2011 CHUBB
INSURANCE   12/17/2009 12/17/2010 CHUBB
INSURANCE   12/17/2007 12/17/2008 AMERICAN INTERNATIONAL SPECIALTY LINES
INSURANCE   02/15/1990 09/23/1991 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 05/01/2006 05/03/2006 IN-COMPLIANCE HARMAN_GR 0/3 COMPLIANCE ASSURANCE
 
TCI 06/07/2005 06/07/2005 IN-COMPLIANCE MOLLI_SA 0/3 COMPLIANCE ASSURANCE
 
TCI 05/11/2004 05/18/2004 IN-COMPLIANCE MOLLI_SA 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING IS SW FIBERGLASS YELLOW
 
TCI 01/28/2003 01/28/2003 IN-COMPLIANCE SUMNER_C 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes SINGLE WALLED FIBERGLASS PIPING (YELLOW)
 
RRBD 02/11/2002 02/11/2002 SUMNER_C 0/0 COMPLIANCE ASSURANCE
 
CWOE 02/11/2002 02/11/2002 SUMNER_C 0/0 COMPLIANCE ASSURANCE
 
NCLI 12/18/2001 12/26/2001 SUMNER_C 0/0 COMPLIANCE ASSURANCE
 
TCI 12/18/2001 12/26/2001 SIGNIFICANT OUT-OF-COMPLIANCE SUMNER_C 0/3 COMPLIANCE ASSURANCE
 
TCI 03/07/2001 03/08/2001 IN-COMPLIANCE SUMNER_C 0/3 COMPLIANCE ASSURANCE
 
TCI 05/24/2000 05/25/2000 IN-COMPLIANCE SUMNER_C 0/3 COMPLIANCE ASSURANCE
 
RRBD 02/08/1999 03/05/1999 CHRONISTER_D 0/3 COMPLIANCE ASSURANCE
 
TCI 01/14/1999 03/05/1999 MINOR OUT-OF-COMPLIANCE CHRONISTER_D 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 11/13/2024 Satisfied LEE_MC_1 Compliance Assistance
 
Site Inspection 09/25/2024 Major Out of Compliance LEE_MC_1 0/1 Routine Compliance
 
Letter 09/25/2024 Satisfied LEE_MC_1 Compliance Assistance
 
Enforcement Referral 07/21/2023 Accepted MULLIGAN_PC_1 Enforcement
 
Letter 03/16/2023 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Site Inspection 03/16/2023 Major Out of Compliance MULLIGAN_PC_1 0/1 Routine Compliance
 
Record Document 10/22/2020 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Letter 10/22/2020 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Incident 09/22/2020 Has not led to Discharge MULLIGAN_PC_1 Incident
 
Site Inspection 08/03/2020 Major Out of Compliance MULLIGAN_PC_1 0/1 Routine Compliance
 
Letter 08/03/2020 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Document Management 07/07/2020 Satisfied MULLIGAN_PC_1 Incident
 
Letter 01/29/2019 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 01/29/2019 Satisfied BROWNLEE_S Enforcement
 
Enforcement Tracking 01/29/2019 Closed Without Enforcement BROWNLEE_S Enforcement
 
Letter 01/28/2019 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Site Inspection 01/28/2019 In Compliance MULLIGAN_PC_1 0/1 Compliance Assistance
 
Enforcement Referral 01/07/2019 Accepted MULLIGAN_PC_1 Enforcement
 
Electronic Communication 12/21/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Electronic Communication 12/21/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Electronic Communication 12/20/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Electronic Communication 12/20/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Site Inspection 12/10/2018 Minor Out of Compliance MULLIGAN_PC_1 0/1 Compliance Assistance
 
Letter 12/10/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Document Management 09/18/2018 Satisfied MULLIGAN_PC_1 Incident
 
Incident 09/18/2018 Has not led to Discharge MULLIGAN_PC_1 Incident
 
Record Document 09/17/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Site Inspection 08/02/2018 Minor Out of Compliance MULLIGAN_PC_1 0/1 Routine Compliance
 
Letter 08/02/2018 Satisfied MULLIGAN_PC_1 Compliance Assistance
 
Electronic Communication 07/31/2018 Satisfied MULLIGAN_PC_1 Routine Compliance
 
Electronic Communication 12/14/2017 Satisfied ANTON_TM_1 Compliance Assistance
 
Electronic Communication 12/11/2017 Satisfied ANTON_TM_1 Compliance Assistance
 
Electronic Communication 12/04/2017 Satisfied ANTON_TM_1 Routine Compliance
 
Record Document 07/07/2017 Satisfied ANTON_TM_1 Compliance Assistance
 
Letter 06/29/2017 Satisfied ANTON_TM_1 Compliance Assistance
 
Site Inspection 04/25/2017 Minor Out of Compliance ANTON_TM_1 0/1 Routine Compliance
 
Letter 04/25/2017 Satisfied ANTON_TM_1 Non-Compliance
 
Record Document 12/18/2014 Satisfied HECKMAN_DA_1 Non-Compliance
 
Letter 12/16/2014 Satisfied HECKMAN_DA_1 Non-Compliance
 
Site Inspection 12/16/2014 Minor Out of Compliance HECKMAN_DA_1 0/1 Routine Compliance
 
Record Document 08/29/2011 Satisfied COLSON_NJ_1 Non-Compliance
 
Letter 07/18/2011 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 07/18/2011 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Site Inspection 08/13/2010 In Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Site Inspection 04/29/2010 Minor Out of Compliance JUARISTIC_GK_1 0/1 Non-Compliance
 
Letter 04/29/2010 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 04/20/2010 Minor Out of Compliance JUARISTIC_GK_1 0/1 Routine Compliance
 
Emergency Preparedness Information 04/20/2010 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Letter 04/20/2010 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Record Document 05/11/2009 Satisfied OSTENSEN_SA_1 Non-Compliance
 
Record Document 09/30/2008 Satisfied COLSON_NJ_1 Non-Compliance
 
Letter 09/30/2008 Satisfied COLSON_NJ_1 Closure
 
TCAR 09/30/2008 Satisfied COLSON_NJ_1 Closure
 
Letter 09/03/2008 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 09/03/2008 Minor Out of Compliance COLSON_NJ_1 0/1 Non-Compliance
 
TCAR 07/14/2008 Incomplete COLSON_NJ_1 Closure
 
Phone Conversation 07/09/2008 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 07/02/2008 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 07/02/2008 Satisfied COLSON_NJ_1 Non-Compliance
 
Emergency Preparedness Information 06/30/2008 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 06/20/2008 Major Out of Compliance BAUER_DR_1 0/1 Installation
 
Letter 06/20/2008 Satisfied BAUER_DR_1 Non-Compliance
 
Letter 12/26/2007 Satisfied OSTENSEN_SA_1 Non-Compliance
 
Site Inspection 12/26/2007 Major Out of Compliance OSTENSEN_SA_1 0/3 Closure
 
Site Inspection 06/19/2007 In Compliance OSTENSEN_SA_1 0/3 Routine Compliance
 
Emergency Preparedness Information 02/07/2007 Satisfied OSTENSEN_SA_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied HARMAN_GR Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/16/2023 6051 SNC-B 4.5 Overfill prevention not provided or properly functioning. Flow shutoff valves should be set at 95% or lower. Repair/replace and retest the diesel flow shutoff valve and submit repair/testing documentation to Citrus County Environmental Health.
 
03/16/2023 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Scrape/sand/recoat all corroded areas of the PUL STP head and associated piping and submit pictures or a work order to Citrus County Environmental Health.
 
 
 
No Discharges Found