DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Manatee   Status    OPEN
 
ID 8732457   Latitude    27° 25' 7.3097
 
Name GAS EXPRESS
6829 15TH ST E
Longitude    82° 32' 47.0273
  SARASOTA, FL 34243 LL Method    DGPS
 
Contact AKBAR BARMANWALLA   LL Status    REVIEWED
 
Phone (727) 642-4847   Status Date    11/05/2003
 
Account Owner Information
 
Name AABAAD & AABAAD CORP
580 LAKE CYPRESS CIR
OLDSMAR, FL 34677
Effective Date    07/22/2011
 
Contact AKBAR BARMANWALLA
 
Phone (727) 642-4847
 
Email AKBARBARMANWALLA@YAHOO.COM
  Placard # / Date    698240 - 07/01/2024
Property Owner Information
 
Name AABAAD & AABAAD CORP
580 LAKE CYPRESS CIR
OLDSMAR, FL 34677
Effective Date    07/22/2011
 
Contact AKBAR BARMANWALLA
 
Phone (727) 642-4847
 
Email AKBARBARMANWALLA@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 20000 Unleaded Gas (B) 05/01/2011 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 12000 Unleaded Gas (B) 05/01/2011 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 07/01/1984 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel   (D) External protective coating (7) Automatically sampled wells
 
 
Tank Tank Size Content Installed Placement Status
1R1 10000 Vehicular Diesel (D) 05/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 07/01/1984 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel   (D) External protective coating (7) Automatically sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2R1 10000 Unleaded Gas (B) 05/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Leaded Gas (A) 07/01/1984 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel   (D) External protective coating (7) Automatically sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3R1 10000 Unleaded Gas (B) 05/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   07/22/2023 07/22/2024 ACE AMERICAN INSURANCE COMPANY
INSURANCE   07/22/2021 07/22/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   07/22/2019 07/22/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   07/20/2017 07/22/2018 ACE
INSURANCE   07/22/2016 07/22/2017 ACE
INSURANCE   07/22/2014 07/22/2015 ACE
INSURANCE   07/22/2012 07/22/2013 ACE
INSURANCE   07/21/2011 07/21/2012 ACE
INSURANCE   10/08/2008 10/08/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 12/05/2005 12/05/2005 COMPLIANCE ASSURANCE
 
NCLI 11/28/2005 11/28/2005 COMPLIANCE ASSURANCE
 
TCI 11/22/2005 11/28/2005 SIGNIFICANT OUT-OF-COMPLIANCE MARK TRETHEWEY /3 COMPLIANCE ASSURANCE
 
TCI 12/21/2004 12/22/2004 IN-COMPLIANCE SEGO 0/3 COMPLIANCE ASSURANCE
 
TCR 07/21/2004 08/03/2004 MINOR OUT-OF-COMPLIANCE SEGO 0/3 COMPLIANCE ASSURANCE
 
TCI 04/22/2004 04/22/2004 SIGNIFICANT OUT-OF-COMPLIANCE SEGO 0/3 COMPLIANCE ASSURANCE
 
RRBD 06/04/2003 07/11/2003 COMPLIANCE ASSURANCE
 
TCI 12/19/2002 01/08/2003 MINOR OUT-OF-COMPLIANCE SEGO 0/3 COMPLIANCE ASSURANCE
 
TCI 03/19/2002 12/22/2004 IN-COMPLIANCE FIELDS 0/3 COMPLIANCE ASSURANCE
 
NCLI 03/21/2001 03/29/2001 COMPLIANCE ASSURANCE
 
TCI 03/07/2001 03/21/2001 MINOR OUT-OF-COMPLIANCE FIELDS 0/3 COMPLIANCE ASSURANCE
 
TCI 08/10/1999 04/26/2004 IN-COMPLIANCE BROWNING 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Phone Conversation 05/30/2024 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Issue Document 05/30/2024 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Phone Conversation 05/30/2024 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 05/30/2024 Major Out of Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Phone Conversation 05/30/2024 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Phone Conversation 05/30/2024 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Letter 05/30/2024 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Letter 11/30/2022 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 11/30/2022 Minor Out of Compliance TRETHEWEY_MB_1 0/2 Complaint
 
Phone Conversation 03/08/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 03/08/2022 Minor Out of Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Issue Document 03/08/2022 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Letter 03/08/2022 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Enforcement Referral 09/08/2020 Accepted TRETHEWEY_MB_1 Enforcement
 
Letter 02/10/2020 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Issue Document 02/10/2020 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Phone Conversation 02/10/2020 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 02/10/2020 Major Out of Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Electronic Communication 04/26/2018 Satisfied BROWNLEE_S Enforcement
 
Enforcement Tracking 04/26/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Issue Document 04/25/2018 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 04/25/2018 In Compliance TRETHEWEY_MB_1 0/2 Compliance Assistance
 
Electronic Communication 12/20/2017 Satisfied BROWNLEE_S Enforcement
 
Phone Conversation 12/19/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Phone Conversation 12/19/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Phone Conversation 12/19/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Enforcement Referral 12/18/2017 Accepted TRETHEWEY_MB_1 Enforcement
 
Letter 12/12/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Site Inspection 12/12/2017 Minor Out of Compliance TRETHEWEY_MB_1 0/2 Compliance Assistance
 
Record Document 07/18/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Record Document 07/18/2017 Satisfied TRETHEWEY_MB_1 Compliance Assistance
 
Letter 03/29/2017 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Phone Conversation 03/29/2017 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 03/29/2017 Major Out of Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Issue Document 03/29/2017 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Issue Document 01/22/2015 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 01/22/2015 In Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Issue Document 04/30/2013 Satisfied TRETHEWEY_MB_1 Routine Compliance
 
Site Inspection 04/30/2013 In Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Site Inspection 05/17/2012 In Compliance TRETHEWEY_MB_1 0/2 Routine Compliance
 
Site Inspection 07/29/2011 In Compliance TRETHEWEY_MB_1 0/2 Installation
 
Site Inspection 04/27/2011 Minor Out of Compliance TRETHEWEY_MB_1 0/3 Closure
 
Letter 04/27/2011 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 12/14/2010 Minor Out of Compliance TRETHEWEY_MB_1 0/3 Routine Compliance
 
Letter 12/14/2010 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Enforcement Tracking 03/17/2010 Closed With Enforcement MEETZE_A Enforcement
 
Electronic Communication 01/26/2010 Major Out of Compliance MEETZE_A Enforcement
 
Record Document 01/26/2010 Major Out of Compliance MEETZE_A Enforcement
 
Electronic Communication 01/26/2010 Major Out of Compliance MEETZE_A Enforcement
 
Phone Conversation 01/22/2010 Major Out of Compliance MEETZE_A Enforcement
 
Phone Conversation 01/15/2010 Major Out of Compliance MEETZE_A Enforcement
 
Meeting 01/04/2010 Satisfied REEDER_JH_1 Non-Compliance
 
Enforcement Referral 11/20/2009 Accepted MEETZE_A Enforcement
 
Site Inspection 09/09/2009 Major Out of Compliance TRETHEWEY_MB_1 0/3 Routine Compliance
 
Letter 09/09/2009 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 11/17/2008 Minor Out of Compliance TRETHEWEY_MB_1 0/3 Routine Compliance
 
Letter 11/17/2008 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Enforcement Tracking 01/09/2008 Closed With Enforcement MEETZE_A Enforcement
 
Site Inspection 11/26/2007 In Compliance TRETHEWEY_MB_1 0/3 Routine Compliance
 
Record Document 08/22/2007 Satisfied MEETZE_A Enforcement
 
Record Document 08/22/2007 Satisfied REEDER_JH_1 Non-Compliance
 
Enforcement Referral 08/02/2007 Accepted MEETZE_A Enforcement
 
Enforcement Referral Activity - OLD 04/06/2007 Terminated CULBRETH_L Enforcement
 
Record Document 03/01/2007 Satisfied REEDER_JH_1 Non-Compliance
 
Letter 02/22/2007 Satisfied REEDER_JH_1 Non-Compliance
 
Emergency Preparedness Information 02/09/2007 Satisfied REEDER_JH_1 Routine Compliance
 
Letter 12/15/2006 Satisfied TRETHEWEY_MB_1 Non-Compliance
 
Site Inspection 12/15/2006 Major Out of Compliance TRETHEWEY_MB_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied REEDER_JH_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/30/2024 6075 Minor 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. No certificates have been provided.
 
05/30/2024 6002 Minor 2.1 Operator Training records not available. Provide proof of operator training and designated class.
 
05/30/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Invoice provided for work performed on 5/23/2024, tests not available. provide Manatee County NRD with copies of the results.
 
05/30/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Within 90 days, have the required tests performed and provide Manatee County NRD with copies of the results.
 
05/30/2024 6045 Minor 4.3 Double-walled spill containment system does not allow for interstitial monitoring. Repair all spill bucket gauges.
 
05/30/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Within 90 days secure the piping and dispenser.
 
05/30/2024 6062 Minor 2.5 Release detection devices not tested annually. Invoice provided for work performed on 5/23/2024, tests not available. Provide Manatee County NRD with copies of test results.
 
05/30/2024 6043 Minor 4.13 Fillbox covers not marked according to requirements. Repaint covers in proper code.
 
05/30/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Invoice provided for work performed on 5/23/2024, tests not available. Provide Manatee County NRD with copies of the results. NOTE: spill buckets were tested as single-wall, hydrostatic. Should be vacuum tested.
 
05/30/2024 6061 SNC-B 4.12 Release detection devices for integral piping do not meet general standards. Invoice provided for work performed on 5/23/2024, tests not available. Provide Manatee County NRD with copies of the test results.
 
03/08/2022 6002 Minor 2.1 Operator Training records not available. Provide Manatee County PNRD with copies of required certificates.
 
03/08/2022 6062 Minor 2.5 Release detection devices not tested annually. Ensure that all release detection devices are tested each year and retain results for review.
 
02/10/2020 4001 Minor 2.2 Operator certification requirements not met. Provide Manatee County PNRD with copies of the required certificates.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
09/17/1997   INACTIVE 30 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE
 
04/17/1990   INACTIVE 30 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE
 
12/30/1987   INACTIVE 30 EARLY DETECTION INCENTIVE-ELIGIBLE