Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Retail Station | ||||||||
County | Leon | Status | OPEN | ||||||||
ID | 8733136 | Latitude | 30° 27' 41.86 | ||||||||
Name |
CIRCLE K #2705170 3211 MAHAN DR |
Longitude | 84° 13' 21.52 | ||||||||
TALLAHASSEE, FL 32308-5509 | LL Method | WGPS | |||||||||
Contact | GRAHAM BIGGS | LL Status | REVIEWED | ||||||||
Phone | (919) 774-6700 | Status Date | 08/21/2003 | ||||||||
Account Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 07/08/1999 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Placard # / Date | 697815 - 06/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 07/07/1999 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Unleaded Gas (B) | 07/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (H) Impressed current CP (M) Spill containment bucket (S) DEP approved containment |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 07/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (H) Impressed current CP (M) Spill containment bucket (S) DEP approved containment |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 8000 | Unleaded Gas (B) | 07/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (H) Impressed current CP (M) Spill containment bucket (S) DEP approved containment |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 04/28/2024 | 08/26/2025 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 04/30/2023 | 08/28/2024 | |||||||||
FULLY FUNDED TRUST | 04/24/2022 | 08/01/2023 | |||||||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2017 | 12/01/2018 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2014 | 12/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2013 | 12/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2013 | 12/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2012 | 12/01/2013 | CHUBB | ||||||||
INSURANCE | 12/01/2011 | 12/01/2012 | CHUBB | ||||||||
INSURANCE | 12/17/2010 | 12/17/2011 | CHUBB | ||||||||
INSURANCE | 12/18/2009 | 12/17/2010 | CHUBB | ||||||||
INSURANCE | 12/17/2008 | 12/17/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 08/24/2005 | 09/01/2005 | IN-COMPLIANCE | HATCHER | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 01/25/2005 | 02/02/2005 | IN-COMPLIANCE | FRENCH | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes INSTALLING DOUBLE WALLED FIBERGLASS PIPING, NEW SUMPS, AND TANK TECH IS INSTALLING PARABEAM LINERS IN TANKS AND ADDING SACRAFICIAL ANODES | |||||||||||
TXI | 01/19/2005 | 02/02/2005 | IN-COMPLIANCE | FRENCH | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes CLOSURE OF PIPING AND SUMPS | |||||||||||
TCR | 12/29/2004 | 01/14/2005 | IN-COMPLIANCE | FRENCH | 0/3 | COMPLIANCE ASSURANCE | |||||
CWOE | 12/29/2004 | 01/14/2005 | FRENHC | 0/3 | COMPLIANCE ASSURANCE | ||||||
WLI | 12/14/2004 | 01/14/2005 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 11/04/2004 | 12/14/2004 | IN-COMPLIANCE | FRENCH | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 10/27/2004 | 12/14/2004 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
NCLI | 10/01/2004 | 10/05/2004 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/28/2004 | 10/05/2004 | MINOR OUT-OF-COMPLIANCE | HATCHER | 0/3 | COMPLIANCE ASSURANCE | |||||
CNLI | 07/07/2004 | 07/12/2004 | FRENCH | 0/3 | DISCHARGE PROJECT | ||||||
DCCR | 07/07/2004 | 07/12/2004 | FRENCH | 0/3 | DISCHARGE PROJECT | ||||||
DRFR | 07/07/2004 | 07/12/2004 | FRENCH | 0/3 | DISCHARGE PROJECT | ||||||
CWOE | 10/10/2003 | 10/10/2003 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 10/03/2003 | 10/10/2003 | IN-COMPLIANCE | HATCHER | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ALL ISSUES ADDRESSED | |||||||||||
RRBD | 09/24/2003 | 10/10/2003 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/21/2003 | 08/29/2003 | MINOR OUT-OF-COMPLIANCE | HATCHER | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOVE WATER FROM PREMIUM SUMP | |||||||||||
CWOE | 11/02/2002 | 12/03/2002 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 10/31/2002 | 12/03/2002 | IN-COMPLIANCE | FRENCH | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 08/26/2002 | 08/26/2002 | FRENCH | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/22/2002 | 08/26/2002 | MINOR OUT-OF-COMPLIANCE | HATCHER | 0/3 | COMPLIANCE ASSURANCE | |||||
TDI | 06/05/2002 | 06/24/2002 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
DSNR | 06/04/2002 | 06/25/2002 | TOOTHMAN | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes DISCOVERY TANK TESTING PERFORMED HYDROSTATIC LINE TEST WHICH PASSED | |||||||||||
IRFR | 05/31/2002 | 06/25/2002 | FRENCH | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes PERFORMING ANNUAL LINE TEST WHEN BUBBLE IN INNER PIPE BURST | |||||||||||
NCLI | 12/07/2001 | 12/07/2001 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCR | 12/06/2001 | 12/07/2001 | MINOR OUT-OF-COMPLIANCE | ROSS | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 11/30/2001 | 12/07/2001 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECORDS FOR DISPENSER LK. REPAIR AND PCW REMOVAL | |||||||||||
NCLI | 10/31/2001 | 10/31/2001 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCR | 10/24/2001 | 10/31/2001 | MINOR OUT-OF-COMPLIANCE | ROSS | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 10/10/2001 | 10/31/2001 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REPAIR RECORDS | |||||||||||
NCLI | 08/17/2001 | 08/17/2001 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/14/2001 | 08/17/2001 | MINOR OUT-OF-COMPLIANCE | ROSS | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 10/25/2000 | 11/03/2000 | IN-COMPLIANCE | SHEFFIELD | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ADDITIONAL DISPENSER LOCATIONS ADDED TO SYSTEM. | |||||||||||
TCI | 08/24/2000 | 08/31/2000 | IN-COMPLIANCE | MIKE SHEFFIELD | 0/3 | COMPLIANCE ASSURANCE | |||||
DSNR | 08/21/2000 | 08/22/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes TWO TANKS WITH FAILED AND INCONCLUSIVE SIRS PASSED T-TEST. | |||||||||||
RRBD | 08/21/2000 | 08/22/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes TANK TIGHTNESS TEST RESULTS | |||||||||||
IRFR | 06/21/2000 | 06/22/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes FAILED SIR TANK 1, TWO CONSECUTIVE INCONCLUSIVES ON PLUS TANK | |||||||||||
RRBD | 06/06/2000 | 06/07/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes TANK TIGHTNESS TEST RESULTS. | |||||||||||
DSNR | 06/06/2000 | 06/07/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes PASSING T-TEST DO NOT CONFIRM FAILED SIR FOR TANK 1 (REG UNL). | |||||||||||
IRFR | 04/19/2000 | 04/27/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes REG. UNL TANK FAILED SIR, PREV. MONTH WAS INCONCLUSIVE. | |||||||||||
DSNR | 03/09/2000 | 03/13/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes PASSING T-TET DO NOT CNFIRM FAILED SIR. | |||||||||||
RRBD | 03/09/2000 | 03/13/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes FOLLOW UP T-TEST RESULTS PROVIDED. | |||||||||||
IRFR | 01/21/2000 | 02/18/2000 | ROSS | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes FAILED SIR | |||||||||||
CWOE | 12/29/1999 | 01/03/2000 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes MONITORING WELLS NO LONGER USED FOR LD PROPERLY CLOSED. | |||||||||||
TCR | 12/28/1999 | 01/03/2000 | IN-COMPLIANCE | SHEFFIELD | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes MONITORING WELLS NO LONGER USED FOR LD HAVE BEEN ABANDONED. | |||||||||||
NCLI | 10/13/1999 | 10/13/1999 | ROSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/23/1999 | 10/08/1999 | MINOR OUT-OF-COMPLIANCE | SHEFFIELD | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 10/15/2024 | Major Out of Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Letter | 10/15/2024 | Satisfied | FRENCH_EC_1 | Compliance Assistance | |||||||
Letter | 01/23/2023 | Satisfied | FRENCH_EC_1 | Compliance Assistance | |||||||
Electronic Communication | 01/23/2023 | Satisfied | FRENCH_EC_1 | Compliance Assistance | |||||||
Letter | 10/21/2022 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 10/21/2022 | Minor Out of Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Enforcement Tracking | 03/25/2022 | Closed With Enforcement | BRISTOL_S | Enforcement | |||||||
Incident | 11/18/2021 | Has not led to Discharge | BRISTOL_S | Incident | |||||||
Incident | 11/18/2021 | Has not led to Discharge | FRENCH_EC_1 | Incident | |||||||
Enforcement Referral | 06/29/2021 | Accepted | FRENCH_EC_1 | Enforcement | |||||||
Site Inspection | 10/30/2020 | Major Out of Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Letter | 10/30/2020 | Satisfied | HATCHER_JD_1 | Compliance Assistance | |||||||
Site Inspection | 08/16/2018 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 09/29/2016 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 09/09/2015 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 08/25/2014 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 09/23/2013 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 09/26/2012 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/26/2012 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 08/24/2011 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Site Inspection | 08/19/2011 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 08/30/2010 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/30/2010 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Record Document | 01/13/2010 | Satisfied | HATCHER_JD_1 | Non-Compliance | |||||||
Record Document | 10/07/2009 | Satisfied | HATCHER_JD_1 | Non-Compliance | |||||||
Letter | 09/16/2009 | Satisfied | HATCHER_JD_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 09/16/2009 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Site Inspection | 09/16/2009 | Minor Out of Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/30/2008 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Site Inspection | 09/30/2008 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 07/31/2007 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/14/2007 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | HATCHER_JD_1 | Routine Compliance | |||||||
Site Inspection | 08/29/2006 | In Compliance | HATCHER_JD_1 | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/08/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Perform required testing of the STP/piping sumps and dispenser liners and provide test results to this department. | |||||||
10/03/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove rust | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
05/18/2004 | COMPLETED | ||||||||||
05/26/1988 | COMPLETED | 35 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||