DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Santa Rosa   Status    OPEN
 
ID 8734093   Latitude    30° 37' 58.6371
 
Name CIRCLE K #2704968
5462 STEWART ST
Longitude    87° 2' 33.6601
  MILTON, FL 32570-4279 LL Method    DGPS
 
Contact CHRIS BAVUSO   LL Status    REVIEWED
 
Phone (850) 316-6673   Status Date    10/27/2003
 
Account Owner Information
 
Name CIRCLE K STORES INC
25 W CEDAR ST STE M
Pensacola, FL 32502
Effective Date    01/13/2010
 
Contact IRA LEWIS/ SCOTT JANASHAK / DEBORAH BRATTON
 
Phone (850) 454-1070
 
Email ILEWIS@CIRCLEK.COM
  Placard # / Date    697408 - 06/28/2024
Property Owner Information
 
Name CIRCLE K STORES INC
25 W CEDAR ST STE M
Pensacola, FL 32502
Effective Date    01/13/2010
 
Contact IRA LEWIS/ SCOTT JANASHAK / DEBORAH BRATTON
 
Phone (850) 454-1070
 
Email ILEWIS@CIRCLEK.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
5 16000 Unleaded Gas (B) 08/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 05/01/1987 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 05/01/1987 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 05/01/1987 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Vehicular Diesel (D) 05/01/1987 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
6 12000 Vehicular Diesel (D) 08/01/2005 UNDERGROUND Out of Service (T)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
GUARANTEE   04/30/2023 08/28/2024
GUARANTEE   04/25/2021 08/27/2022
INSURANCE   12/01/2018 12/01/2019 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2017 12/01/2018 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2016 12/01/2017 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2013 12/01/2016 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2011 12/01/2013 CHUBB
INSURANCE   12/17/2009 12/01/2011 CHUBB
INSURANCE   12/16/2007 12/16/2009 AMERICAN INTERNATIONAL SPECIALTY LINES
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 12/15/2005 12/16/2005 IN-COMPLIANCE JOSEPH D. THAYER 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS FOUND THIS INSPECTION
 
TIN 08/23/2005 09/09/2005 IN-COMPLIANCE JOHN S.S TEVENSON 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALLATION OF TWO (2) NEWBERRY STI ACT-100 UST'S WITH AMERON DW RIGID FRP PIPE TO EXISTING ENVIRON MPD LINERS. LAURITZ SPANN PCC045053. CLOSURE ASSESSMENT DUE IN 60 DAYS. SYSTEM APPROVED.
 
TCI 11/09/2004 11/10/2004 IN-COMPLIANCE JOSEPH D. THAYER 0/4 COMPLIANCE ASSURANCE
 
TIN 11/03/2004 11/05/2004 IN-COMPLIANCE JOSEPH D. THAYER 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes MONTIE ROBERTS EXPLAINED A TREE FELL DIRECTLY ON DIESEL DISPENSER. GROOVIN NOOVIN REPLACED DISPENSER AND TESTED LINES. THE LINES WERE NOT DAMAGED.
 
TCI 12/18/2003 12/29/2003 IN-COMPLIANCE JOSEPH D. THAYER 0/4 COMPLIANCE ASSURANCE
 
TCI 02/11/2003 02/26/2003 IN-COMPLIANCE REGINALD W. BRADLEY 0/4 COMPLIANCE ASSURANCE
 
TCR 06/06/2002 06/13/2002 IN-COMPLIANCE REGINALD W. BRADLEY 0/4 COMPLIANCE ASSURANCE
 
TCI 12/07/2001 01/07/2002 SIGNIFICANT OUT-OF-COMPLIANCE REGINALD W. BRADLEY 0/4 COMPLIANCE ASSURANCE
 
RRBD 02/25/2001 04/12/2001 COMPLIANCE ASSURANCE
 
TCI 01/23/2001 01/29/2001 SIGNIFICANT OUT-OF-COMPLIANCE THAYER_JD 0/3 COMPLIANCE ASSURANCE
 
TCI 08/18/1999 09/01/1999 IN-COMPLIANCE THAYER_JD 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 06/26/2024 Accepted PAYNE_CL_1 Enforcement
 
Letter 06/25/2024 Satisfied PAYNE_CL_1 Compliance Assistance
 
Record Document 06/25/2024 Satisfied PAYNE_CL_1 Compliance Assistance
 
Record Document 06/24/2024 Satisfied PAYNE_CL_1 Compliance Assistance
 
Record Document 06/24/2024 Satisfied PAYNE_CL_1 Compliance Assistance
 
Letter 03/11/2024 Satisfied PAYNE_CL_1 Compliance Assistance
 
Site Inspection 03/11/2024 Major Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Electronic Communication 03/08/2024 Satisfied PAYNE_CL_1 Routine Compliance
 
Electronic Communication 03/05/2024 Satisfied PAYNE_CL_1 Routine Compliance
 
Electronic Communication 03/05/2024 Satisfied PAYNE_CL_1 Routine Compliance
 
Electronic Communication 03/05/2024 Satisfied PAYNE_CL_1 Routine Compliance
 
Document Management 10/20/2023 Satisfied PAYNE_CL_1 Incident
 
Letter 11/28/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
TCAR 11/28/2022 Satisfied PAYNE_CL_1 Component Closure
 
Letter 11/28/2022 Satisfied WILSON_ML_1 Component Closure
 
Document Management 11/28/2022 Satisfied WILSON_ML_1 Component Closure
 
Record Document 11/08/2022 Satisfied WILSON_ML_1 Component Closure
 
Letter 11/08/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Document Management 08/17/2022 Satisfied WILSON_ML_1 Component Closure
 
Letter 08/17/2022 Satisfied WILSON_ML_1 Component Closure
 
Letter 07/29/2022 Satisfied WILSON_ML_1 Component Installation
 
Site Inspection 07/22/2022 In Compliance PAYNE_CL_1 0/2 Component Installation
 
Letter 01/05/2022 Satisfied MERRITT_S Enforcement
 
Enforcement Tracking 01/05/2022 Closed Without Enforcement MERRITT_S Enforcement
 
Enforcement Referral 01/03/2022 Accepted WILSON_ML_1 Enforcement
 
Electronic Communication 12/28/2021 Satisfied MERRITT_S Compliance Assistance
 
Record Document 12/22/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 12/13/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 12/13/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 12/10/2021 Satisfied WILSON_ML_1 Component Closure
 
TCAR 12/10/2021 Satisfied PAYNE_CL_1 Component Closure
 
Letter 12/10/2021 Satisfied WILSON_ML_1 Component Closure
 
Document Management 12/10/2021 Satisfied WILSON_ML_1 Component Closure
 
Letter 10/28/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 10/28/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 10/28/2021 Major Out of Compliance WILSON_ML_1 0/2 Component Installation
 
Site Inspection 10/28/2021 Major Out of Compliance WILSON_ML_1 0/2 Component Closure
 
Letter 10/28/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 10/28/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 10/21/2021 Satisfied PAYNE_CL_1 Compliance Assistance
 
Letter 10/05/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 10/05/2021 Major Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Issue Document 10/05/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Electronic Communication 10/04/2021 Satisfied PAYNE_CL_1 Routine Compliance
 
Issue Document 10/16/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 10/16/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 10/14/2019 Satisfied PAYNE_CL_1 Compliance Assistance
 
Issue Document 09/09/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 09/09/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 09/09/2019 Minor Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Electronic Communication 09/04/2019 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 03/02/2017 In Compliance PAYNE_CL_1 0/2 Installation
 
Site Inspection 03/02/2017 In Compliance PAYNE_CL_1 0/2 Closure
 
Site Inspection 02/27/2017 In Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Emergency Preparedness Information 01/13/2015 Satisfied FOXWORTH_S_1 Routine Compliance
 
Site Inspection 01/13/2015 In Compliance FOXWORTH_S_1 0/2 Routine Compliance
 
Document Management 10/06/2014 Complete FOXWORTH_S_1 Incident
 
Incident 10/06/2014 Has not led to Discharge FOXWORTH_S_1 Incident
 
Emergency Preparedness Information 01/23/2013 Satisfied FOXWORTH_S_1 Routine Compliance
 
Record Document 01/23/2013 Satisfied FOXWORTH_S_1 Routine Compliance
 
Site Inspection 01/23/2013 In Compliance FOXWORTH_S_1 0/2 Routine Compliance
 
Record Document 02/15/2012 Satisfied PORTER_AJ_1 Non-Compliance
 
Record Document 10/31/2011 Satisfied PORTER_AJ_1 Non-Compliance
 
Letter 09/20/2011 Satisfied PURDY_EM_1 Non-Compliance
 
Emergency Preparedness Information 09/14/2011 Satisfied PORTER_AJ_1 Routine Compliance
 
Site Inspection 09/14/2011 Major Out of Compliance PORTER_AJ_1 0/2 Routine Compliance
 
Incident 11/16/2010 Has not led to Discharge THAYER_JD_1 Incident
 
Site Inspection 11/02/2010 In Compliance THAYER_JD_1 0/2 Non-Compliance
 
Document Management 09/30/2010 Complete THAYER_JD_1 Incident
 
Letter 09/22/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Emergency Preparedness Information 09/21/2010 Satisfied THAYER_JD_1 Routine Compliance
 
Site Inspection 09/21/2010 Minor Out of Compliance THAYER_JD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 09/20/2010 Satisfied THAYER_JD_1 Routine Compliance
 
Discharge Reporting 03/16/2010 Satisfied THAYER_JD_1 Discharge
 
Document Management 02/08/2010 Complete THAYER_JD_1 Discharge
 
Meeting 01/26/2010 Satisfied THAYER_JD_1 Non-Compliance
 
Site Inspection 07/20/2009 Minor Out of Compliance THAYER_JD_1 0/2 Routine Compliance
 
Record Document 07/02/2009 Satisfied THAYER_JD_1 Routine Compliance
 
Record Document 10/10/2008 Satisfied THAYER_JD_1 Non-Compliance
 
Site Inspection 10/09/2008 Minor Out of Compliance THAYER_JD_1 0/2 Routine Compliance
 
Site Inspection 06/30/2008 In Compliance STEVENSON_JS 0/2 Non-Compliance
 
Site Inspection 05/16/2008 In Compliance STEVENSON_JS 0/2 Routine Compliance
 
Record Document 05/08/2008 Satisfied STEVENSON_JS Non-Compliance
 
Letter 04/11/2008 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 03/21/2008 Minor Out of Compliance STEVENSON_JS 0/2 Routine Compliance
 
Site Inspection 06/07/2007 In Compliance THAYER_JD_1 0/6 Routine Compliance
 
Record Document 04/25/2007 Satisfied THAYER_JD_1 Closure
 
TCAR 04/25/2007 Complete THAYER_JD_1 Closure
 
TCAR 04/09/2007 Rejected THAYER_JD_1 Closure
 
Record Document 02/22/2007 Satisfied THAYER_JD_1 Discharge
 
Site Inspection 02/22/2007 In Compliance THAYER_JD_1 0/6 Discharge
 
Emergency Preparedness Information 02/13/2007 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Phone Conversation 02/05/2007 Satisfied THAYER_JD_1 Routine Compliance
 
Record Document 10/12/2006 Satisfied THAYER_JD_1 Routine Compliance
 
Emergency Preparedness Information 09/25/2006 Satisfied THAYER_JD_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
06/25/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Provide Superior Service's post repair report, pictures post repair, primary and secondary tank testing results post repair. Email: Charles.Payne@flhealth.gov
 
06/25/2024 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. Conduct an incident investigation to determine if a discharge has occurred. Provide the primary and secondary tank testing no more than 30 days prior to repair. If primary and secondary tank testing for the premium tank was not performed no more than 30 days prior to tank repair, sampling will be required to determine if a discharge occurred. Email: Charles.Payne@flhealth.gov
 
03/11/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have a technician replace or adjust the overfill device to the correct height. Email a copy of the invoice and passing test results to the inspector. Email: Charles.Payne@flhealth.gov
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
02/21/2007   COMPLETED
 
06/27/1989   COMPLETED 72 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE