DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Northeast   Type    Fuel user/Non-retail
 
County Duval   Status    OPEN
 
ID 8736162   Latitude    30° 19' 8.6784
 
Name RIVERPLACE TOWER
1301 RIVERPLACE BLVD
Longitude    81° 39' 24.1827
  JACKSONVILLE, FL 32207-9047 LL Method    DPHO
 
Contact Shella Cardillo   LL Status    REVIEWED
 
Phone (904) 346-1600   Status Date    10/27/2003
 
Account Owner Information
 
Name LCP RIVERPLACE, LLC
1301 RIVERPLACE BOULEVARD
Jacksonville, FL 32207
Effective Date    06/27/2017
 
Contact Shella Cardillo
 
Phone (904) 346-1600
 
Email SHELLA.CARDILLO@CBRE.COM
  Placard # / Date    701300 - 09/06/2024
Property Owner Information
 
Name CBRE
1301 Riverplace Blvd
Jacksonville, FL 32207-9032
Effective Date    02/23/2023
 
Contact Shella Cardillo
 
Phone (904) 346-1600
 
Email shella.cardillo@cbre.com
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1R1 8000 Emerg Generator Diesel (G) 09/01/1987 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(I) Suction piping system
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Fuel Oil - Onsite Heat (M) 07/01/1966 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (D) External protective coating
(E) Cathodic protection
(Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/12/2021 06/12/2022 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2020 06/12/2021 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2019 06/12/2020 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2018 06/12/2019 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2017 06/12/2018 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2016 06/12/2017 NAUTILUS INSURANCE COMPANY
INSURANCE   06/12/2015 06/12/2016 NAUTILUS INSURANCE COMPANY
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   01/01/2013 12/31/2013
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2011 12/31/2011
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Tracking 01/07/2025 Closed Without Enforcement PAUL_JK Enforcement
 
Letter 11/08/2024 Satisfied STERLING_C Enforcement
 
Enforcement Referral 05/07/2024 Accepted GAINEY_H_1 Enforcement
 
Electronic Communication 03/15/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 03/08/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Document Management 02/22/2024 Satisfied CHRISTIAN_ED_1 Incident
 
Electronic Communication 02/09/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Letter 02/09/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Enforcement Referral 01/17/2024 Accepted RICHARDS_JE_1 Enforcement
 
Site Inspection 01/16/2024 Major Out of Compliance CHRISTIAN_ED_1 0/1 Routine Compliance
 
Letter 01/16/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Electronic Communication 01/02/2024 Satisfied CHRISTIAN_ED_1 Compliance Assistance
 
Letter 02/22/2022 Satisfied MCARTOR_H_1 Compliance Assistance
 
Site Inspection 02/18/2022 Minor Out of Compliance MCARTOR_H_1 0/1 Routine Compliance
 
Electronic Communication 11/05/2021 Satisfied MCARTOR_H_1 Compliance Assistance
 
Enforcement Tracking 02/19/2020 Closed Without Enforcement SOLTIS_C Enforcement
 
Letter 02/19/2020 Satisfied SOLTIS_C Enforcement
 
Enforcement Referral 10/29/2019 Accepted GAINEY_H_1 Enforcement
 
Electronic Communication 10/25/2019 Satisfied VERMILLION_KN_1 Compliance Assistance
 
Electronic Communication 09/18/2019 Satisfied VERMILLION_KN_1 Compliance Assistance
 
Electronic Communication 08/12/2019 Satisfied VERMILLION_KN_1 Compliance Assistance
 
Site Inspection 08/01/2019 Major Out of Compliance VERMILLION_KN_1 0/1 Routine Compliance
 
Letter 08/01/2019 Satisfied VERMILLION_KN_1 Compliance Assistance
 
Electronic Communication 07/22/2019 Satisfied VERMILLION_KN_1 Routine Compliance
 
Electronic Communication 03/03/2017 Satisfied CANTU_AB_1 Routine Compliance
 
Electronic Communication 02/27/2017 Satisfied CANTU_AB_1 Routine Compliance
 
Site Inspection 02/27/2017 In Compliance CANTU_AB_1 0/1 Non-Compliance
 
Letter 02/23/2017 Satisfied CANTU_AB_1 Non-Compliance
 
Site Inspection 02/22/2017 Minor Out of Compliance CANTU_AB_1 0/1 Routine Compliance
 
Electronic Communication 02/22/2017 Satisfied CANTU_AB_1 Routine Compliance
 
Electronic Communication 07/08/2015 Satisfied RICHARDS_JE_1 Non-Compliance
 
Letter 06/16/2015 Satisfied RICHARDS_JE_1 Non-Compliance
 
Record Document 06/15/2015 Satisfied RICHARDS_JE_1 Non-Compliance
 
Record Document 06/15/2015 Satisfied RICHARDS_JE_1 Non-Compliance
 
Letter 03/19/2015 Satisfied HILL_KL_1 Non-Compliance
 
Letter 02/17/2015 Satisfied MAYOR_AK_1 Non-Compliance
 
Electronic Communication 02/13/2015 Satisfied MAYOR_AK_1 Routine Compliance
 
Electronic Communication 02/13/2015 Satisfied MAYOR_AK_1 Routine Compliance
 
Electronic Communication 02/12/2015 Satisfied MAYOR_AK_1 Routine Compliance
 
Site Inspection 02/12/2015 Major Out of Compliance MAYOR_AK_1 0/1 Routine Compliance
 
Site Inspection 01/23/2013 In Compliance KOROUS_E_1 0/1 Routine Compliance
 
Electronic Communication 01/23/2013 Satisfied KOROUS_E_1 Routine Compliance
 
TCAR 11/04/2011 Satisfied RICHARDS_JE_1 Closure
 
Discharge Reporting 10/25/2011 Satisfied RICHARDS_JE_1 Discharge
 
Issue Document 10/07/2011 Satisfied TOWLE_M Enforcement
 
Record Document 10/07/2011 Satisfied TOWLE_M Enforcement
 
Enforcement Tracking 10/07/2011 Closed Without Enforcement TOWLE_M Enforcement
 
Site Inspection 10/04/2011 In Compliance LUNN_RJ_1 0/1 Closure
 
Site Inspection 10/04/2011 In Compliance LUNN_RJ_1 0/1 Installation
 
Letter 09/23/2011 Satisfied RICHARDS_JE_1 Discharge
 
Document Management 09/22/2011 Complete RICHARDS_JE_1 Discharge
 
Issue Document 08/29/2011 Satisfied TOWLE_M Enforcement
 
Letter 08/24/2011 Satisfied LUNN_RJ_1 Non-Compliance
 
Enforcement Referral 08/24/2011 Accepted TOWLE_M Enforcement
 
Electronic Communication 08/24/2011 Satisfied LUNN_RJ_1 Complaint
 
Site Inspection 08/22/2011 Major Out of Compliance LUNN_RJ_1 0/1 Complaint
 
Electronic Communication 07/18/2011 Satisfied LUNN_RJ_1 Closure
 
Electronic Communication 07/18/2011 Satisfied LUNN_RJ_1 Installation
 
Electronic Communication 05/26/2011 Satisfied LUNN_RJ_1 Complaint
 
Issue Document 02/02/2011 Satisfied TOWLE_M Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/09/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Facility must repair and replace the entry boot inside the sump. Responsible party must determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. Post repair integrity testing required. Sampling may be required.
 
01/16/2024 6001 Minor 2.1 No reasonable access provided. Provide access to the double walled spill bucket interstitial to confirm if the interstitial space is clean and dry.
 
01/12/2024 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. Submit an incident notification form.
 
01/12/2024 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Investigate the issue.
 
01/12/2024 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. Investigate the issue to determine if a discharge has occurred.
 
01/12/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Facility must remove liquid from the piping sump and dispose of liquid properly. Responsible party must determine the source of the liquid and determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. Post liquid removal integrity testing may be required. Sampling may be required.
 
01/12/2024 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Please provide an updated and current Storage Tank financial responsibility, including Parts P, and C/D.
 
01/12/2024 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. Please send updated Parts P and D to the inspector.
 
01/12/2024 6002 Minor 2.1 Operator Training records not available. Please present an operator C certificate to the inspector via email.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
09/15/2011   COMPLETED 29