Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Fuel user/Non-retail | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 8736162 | Latitude | 30° 19' 8.6784 | ||||||||
Name |
RIVERPLACE TOWER 1301 RIVERPLACE BLVD |
Longitude | 81° 39' 24.1827 | ||||||||
JACKSONVILLE, FL 32207-9047 | LL Method | DPHO | |||||||||
Contact | Shella Cardillo | LL Status | REVIEWED | ||||||||
Phone | (904) 346-1600 | Status Date | 10/27/2003 | ||||||||
Account Owner Information | |||||||||||
Name | LCP RIVERPLACE, LLC 1301 RIVERPLACE BOULEVARD Jacksonville, FL 32207 |
Effective Date | 06/27/2017 | ||||||||
Contact | Shella Cardillo | ||||||||||
Phone | (904) 346-1600 | ||||||||||
SHELLA.CARDILLO@CBRE.COM | |||||||||||
Placard # / Date | 701300 - 09/06/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CBRE 1301 Riverplace Blvd Jacksonville, FL 32207-9032 |
Effective Date | 02/23/2023 | ||||||||
Contact | Shella Cardillo | ||||||||||
Phone | (904) 346-1600 | ||||||||||
shella.cardillo@cbre.com | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1R1 | 8000 | Emerg Generator Diesel (G) | 09/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (I) Suction piping system |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Fuel Oil - Onsite Heat (M) | 07/01/1966 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating (E) Cathodic protection |
(Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 06/12/2021 | 06/12/2022 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2020 | 06/12/2021 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2019 | 06/12/2020 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2018 | 06/12/2019 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2017 | 06/12/2018 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2016 | 06/12/2017 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 06/12/2015 | 06/12/2016 | NAUTILUS INSURANCE COMPANY | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 01/01/2013 | 12/31/2013 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2011 | 12/31/2011 | |||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Tracking | 01/07/2025 | Closed Without Enforcement | PAUL_JK | Enforcement | |||||||
Letter | 11/08/2024 | Satisfied | STERLING_C | Enforcement | |||||||
Enforcement Referral | 05/07/2024 | Accepted | GAINEY_H_1 | Enforcement | |||||||
Electronic Communication | 03/15/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Electronic Communication | 03/08/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Document Management | 02/22/2024 | Satisfied | CHRISTIAN_ED_1 | Incident | |||||||
Electronic Communication | 02/09/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Letter | 02/09/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Enforcement Referral | 01/17/2024 | Accepted | RICHARDS_JE_1 | Enforcement | |||||||
Site Inspection | 01/16/2024 | Major Out of Compliance | CHRISTIAN_ED_1 | 0/1 | Routine Compliance | ||||||
Letter | 01/16/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Electronic Communication | 01/02/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Letter | 02/22/2022 | Satisfied | MCARTOR_H_1 | Compliance Assistance | |||||||
Site Inspection | 02/18/2022 | Minor Out of Compliance | MCARTOR_H_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 11/05/2021 | Satisfied | MCARTOR_H_1 | Compliance Assistance | |||||||
Enforcement Tracking | 02/19/2020 | Closed Without Enforcement | SOLTIS_C | Enforcement | |||||||
Letter | 02/19/2020 | Satisfied | SOLTIS_C | Enforcement | |||||||
Enforcement Referral | 10/29/2019 | Accepted | GAINEY_H_1 | Enforcement | |||||||
Electronic Communication | 10/25/2019 | Satisfied | VERMILLION_KN_1 | Compliance Assistance | |||||||
Electronic Communication | 09/18/2019 | Satisfied | VERMILLION_KN_1 | Compliance Assistance | |||||||
Electronic Communication | 08/12/2019 | Satisfied | VERMILLION_KN_1 | Compliance Assistance | |||||||
Site Inspection | 08/01/2019 | Major Out of Compliance | VERMILLION_KN_1 | 0/1 | Routine Compliance | ||||||
Letter | 08/01/2019 | Satisfied | VERMILLION_KN_1 | Compliance Assistance | |||||||
Electronic Communication | 07/22/2019 | Satisfied | VERMILLION_KN_1 | Routine Compliance | |||||||
Electronic Communication | 03/03/2017 | Satisfied | CANTU_AB_1 | Routine Compliance | |||||||
Electronic Communication | 02/27/2017 | Satisfied | CANTU_AB_1 | Routine Compliance | |||||||
Site Inspection | 02/27/2017 | In Compliance | CANTU_AB_1 | 0/1 | Non-Compliance | ||||||
Letter | 02/23/2017 | Satisfied | CANTU_AB_1 | Non-Compliance | |||||||
Site Inspection | 02/22/2017 | Minor Out of Compliance | CANTU_AB_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 02/22/2017 | Satisfied | CANTU_AB_1 | Routine Compliance | |||||||
Electronic Communication | 07/08/2015 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Letter | 06/16/2015 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Record Document | 06/15/2015 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Record Document | 06/15/2015 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Letter | 03/19/2015 | Satisfied | HILL_KL_1 | Non-Compliance | |||||||
Letter | 02/17/2015 | Satisfied | MAYOR_AK_1 | Non-Compliance | |||||||
Electronic Communication | 02/13/2015 | Satisfied | MAYOR_AK_1 | Routine Compliance | |||||||
Electronic Communication | 02/13/2015 | Satisfied | MAYOR_AK_1 | Routine Compliance | |||||||
Electronic Communication | 02/12/2015 | Satisfied | MAYOR_AK_1 | Routine Compliance | |||||||
Site Inspection | 02/12/2015 | Major Out of Compliance | MAYOR_AK_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 01/23/2013 | In Compliance | KOROUS_E_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 01/23/2013 | Satisfied | KOROUS_E_1 | Routine Compliance | |||||||
TCAR | 11/04/2011 | Satisfied | RICHARDS_JE_1 | Closure | |||||||
Discharge Reporting | 10/25/2011 | Satisfied | RICHARDS_JE_1 | Discharge | |||||||
Issue Document | 10/07/2011 | Satisfied | TOWLE_M | Enforcement | |||||||
Record Document | 10/07/2011 | Satisfied | TOWLE_M | Enforcement | |||||||
Enforcement Tracking | 10/07/2011 | Closed Without Enforcement | TOWLE_M | Enforcement | |||||||
Site Inspection | 10/04/2011 | In Compliance | LUNN_RJ_1 | 0/1 | Closure | ||||||
Site Inspection | 10/04/2011 | In Compliance | LUNN_RJ_1 | 0/1 | Installation | ||||||
Letter | 09/23/2011 | Satisfied | RICHARDS_JE_1 | Discharge | |||||||
Document Management | 09/22/2011 | Complete | RICHARDS_JE_1 | Discharge | |||||||
Issue Document | 08/29/2011 | Satisfied | TOWLE_M | Enforcement | |||||||
Letter | 08/24/2011 | Satisfied | LUNN_RJ_1 | Non-Compliance | |||||||
Enforcement Referral | 08/24/2011 | Accepted | TOWLE_M | Enforcement | |||||||
Electronic Communication | 08/24/2011 | Satisfied | LUNN_RJ_1 | Complaint | |||||||
Site Inspection | 08/22/2011 | Major Out of Compliance | LUNN_RJ_1 | 0/1 | Complaint | ||||||
Electronic Communication | 07/18/2011 | Satisfied | LUNN_RJ_1 | Closure | |||||||
Electronic Communication | 07/18/2011 | Satisfied | LUNN_RJ_1 | Installation | |||||||
Electronic Communication | 05/26/2011 | Satisfied | LUNN_RJ_1 | Complaint | |||||||
Issue Document | 02/02/2011 | Satisfied | TOWLE_M | Installation | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/09/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Facility must repair and replace the entry boot inside the sump. Responsible party must determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. Post repair integrity testing required. Sampling may be required. | |||||||
01/16/2024 | 6001 | Minor | 2.1 No reasonable access provided. | Provide access to the double walled spill bucket interstitial to confirm if the interstitial space is clean and dry. | |||||||
01/12/2024 | 6009 | Minor | 4.1 Incident Notification Form (INF) not received in a timely manner. | Submit an incident notification form. | |||||||
01/12/2024 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | Investigate the issue. | |||||||
01/12/2024 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | Investigate the issue to determine if a discharge has occurred. | |||||||
01/12/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Facility must remove liquid from the piping sump and dispose of liquid properly. Responsible party must determine the source of the liquid and determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. Post liquid removal integrity testing may be required. Sampling may be required. | |||||||
01/12/2024 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Please provide an updated and current Storage Tank financial responsibility, including Parts P, and C/D. | |||||||
01/12/2024 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Please send updated Parts P and D to the inspector. | |||||||
01/12/2024 | 6002 | Minor | 2.1 Operator Training records not available. | Please present an operator C certificate to the inspector via email. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
09/15/2011 | COMPLETED | 29 | |||||||||