Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 03/19/2025 Last Data Refresh: 03/18/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Fuel user/Non-retail | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 8736957 | Latitude | 30° 16' 25.3114 | ||||||||
Name |
FIRST COAST TOWER GROUP 9830 ANDERS BLVD |
Longitude | 81° 33' 12.673 | ||||||||
JACKSONVILLE, FL 32246-6427 | LL Method | DPHO | |||||||||
Contact | Joe McKenzie | LL Status | REVIEWED | ||||||||
Phone | (904) 393-9863 | Status Date | 10/20/2003 | ||||||||
Account Owner Information | |||||||||||
Name | FIRST COAST TOWER GROUP 4 Broadcast Pl Jacksonville, FL 32207 |
Effective Date | 05/20/1994 | ||||||||
Contact | JOE MCKENZIE | ||||||||||
Phone | (904) 393-9863 | ||||||||||
JMCKENZIE@WJXT.COM | |||||||||||
Placard # / Date | 679325 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | FIRST COAST TOWER GROUP 4 Broadcast Pl Jacksonville, FL 32207 |
Effective Date | 09/23/2010 | ||||||||
Contact | JOE MCKENZIE | ||||||||||
Phone | (904) 393-9863 | ||||||||||
JMCKENZIE@WJXT.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 2000 | Emerg Generator Diesel (G) | 06/01/1998 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 2000 | Emerg Generator Diesel (G) | 06/01/1998 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 2000 | Emerg Generator Diesel (G) | 03/01/2002 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2000 | Emerg Generator Diesel (G) | 07/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(B) Steel/galvanized metal | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 2000 | Emerg Generator Diesel (G) | 01/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel | (B) Steel/galvanized metal | (I) Not required | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/24/2019 | 02/24/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 02/24/2018 | 02/24/2019 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 02/24/2017 | 02/24/2018 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 02/24/2016 | 02/24/2017 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 10/18/2014 | 10/18/2015 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 10/18/2013 | 10/18/2014 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/16/2013 | 03/15/2014 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/16/2012 | 03/15/2013 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/16/2011 | 03/16/2012 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/16/2010 | 03/15/2011 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/16/2010 | 03/16/2011 | |||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 03/15/2008 | 03/15/2009 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 02/27/2006 | 02/28/2006 | IN-COMPLIANCE | TORSANKO | 3/0 | COMPLIANCE ASSURANCE | |||||
TCI | 12/14/2004 | 12/16/2004 | IN-COMPLIANCE | TORSANKO | 2/0 | COMPLIANCE ASSURANCE | |||||
TCI | 11/05/2003 | 11/16/2003 | IN-COMPLIANCE | TOWNSEND_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TCR | 04/28/2003 | 04/30/2003 | IN-COMPLIANCE | TOWNSEND_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TCI | 03/14/2003 | 03/15/2003 | MINOR OUT-OF-COMPLIANCE | TOWNSEND_C | 3/0 | COMPLIANCE ASSURANCE | |||||
TIN | 01/23/2002 | 02/04/2002 | IN-COMPLIANCE | BORISADE_C | 1/0 | COMPLIANCE ASSURANCE | |||||
TCI | 09/05/2001 | 09/06/2001 | IN-COMPLIANCE | BORISADE_C | 2/0 | COMPLIANCE ASSURANCE | |||||
TCI | 03/14/2001 | 03/21/2001 | IN-COMPLIANCE | BORISADE_C | 2/0 | COMPLIANCE ASSURANCE | |||||
TCI | 02/16/2000 | 02/28/2000 | IN-COMPLIANCE | TORSANKO_G | 1/0 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 04/01/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Electronic Communication | 02/26/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Enforcement Referral | 02/06/2024 | Accepted | GAINEY_H_1 | Enforcement | |||||||
Electronic Communication | 01/26/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Site Inspection | 01/25/2024 | Major Out of Compliance | CHRISTIAN_ED_1 | 3/0 | Routine Compliance | ||||||
Letter | 01/25/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Electronic Communication | 01/11/2024 | Satisfied | CHRISTIAN_ED_1 | Compliance Assistance | |||||||
Letter | 03/04/2020 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||||||
Letter | 01/27/2020 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||||||
Site Inspection | 01/24/2020 | Minor Out of Compliance | MONDO_PW_1 | 3/0 | Routine Compliance | ||||||
Letter | 12/13/2017 | Satisfied | GREGORY_HM_1 | Compliance Assistance | |||||||
Site Inspection | 12/13/2017 | Major Out of Compliance | GREGORY_HM_1 | 3/0 | Routine Compliance | ||||||
Letter | 12/13/2017 | Satisfied | GREGORY_HM_1 | Compliance Assistance | |||||||
Electronic Communication | 11/29/2017 | Satisfied | GREGORY_HM_1 | Routine Compliance | |||||||
Site Inspection | 03/16/2015 | In Compliance | MAYOR_AK_1 | 3/0 | Routine Compliance | ||||||
Electronic Communication | 03/16/2015 | Satisfied | MAYOR_AK_1 | Routine Compliance | |||||||
Electronic Communication | 02/01/2013 | Satisfied | KOROUS_E_1 | Routine Compliance | |||||||
Site Inspection | 01/28/2013 | In Compliance | KOROUS_E_1 | 3/0 | Routine Compliance | ||||||
Electronic Communication | 03/12/2012 | Satisfied | CAIN_M_1 | Non-Compliance | |||||||
Letter | 02/27/2012 | Satisfied | RICHARDS_JE_1 | Non-Compliance | |||||||
Letter | 01/27/2012 | Satisfied | CAIN_M_1 | Non-Compliance | |||||||
Electronic Communication | 01/27/2012 | Satisfied | CAIN_M_1 | Non-Compliance | |||||||
Electronic Communication | 01/27/2012 | Satisfied | CAIN_M_1 | Non-Compliance | |||||||
Electronic Communication | 01/24/2012 | Satisfied | CAIN_M_1 | Routine Compliance | |||||||
Site Inspection | 01/24/2012 | Major Out of Compliance | CAIN_M_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 10/31/2010 | In Compliance | BORISADE_KA_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 06/08/2010 | In Compliance | GRIFFIN_TW_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 08/04/2008 | In Compliance | BORISADE_KA_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 03/31/2008 | In Compliance | BORISADE_KA_1 | 3/0 | Routine Compliance | ||||||
Site Inspection | 06/29/2007 | In Compliance | GRIFFIN_TW_1 | 3/0 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/26/2024 | 7001 | Minor | 1.1 No reasonable access provided. | Provide access to the pneumercator and send a photograph showing that the tanks are not in alarm to the inspector. | |||||||
01/22/2024 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide current electronic release detection equipment monthly inspection documentation from the past three months. | |||||||
01/22/2024 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide up-to-date financial responsibility documentation. | |||||||
01/22/2024 | 7011 | Minor | 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. | Provide a Part P for 2022, 2023, and 2024. | |||||||
01/22/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Facility must send updated release detection testing of tanks 3, 4 and 5 with a passing result for the interstitial sensors. | |||||||
01/22/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Facility must provide current and passing testing for the primary overfill protection devices for Tanks 3, 4, and 5. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/09/1998 | COMPLETED | 9 | |||||||||