District | Southwest | Type | Retail Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 8839781 | Latitude | 28° 1' .5694 | ||||||||
Name |
ALADDIN MARKET 2141 CRYSTAL GROVE DR |
Longitude | 81° 54' 52.7649 | ||||||||
LAKELAND, FL 33801-6875 | LL Method | DPHO | |||||||||
Contact | SAM RABI | LL Status | REVIEWED | ||||||||
Phone | (863) 899-5526 | Status Date | 06/09/2003 | ||||||||
Account Owner Information | |||||||||||
Name | AMIR ZAIN LLC 2141 CRYSTAL GROVE DR LAKELAND, FL 33801 |
Effective Date | 10/05/2023 | ||||||||
Contact | SAM RABI | ||||||||||
Phone | (863) 899-5526 | ||||||||||
SAMRABI0423@GMAIL.COM | |||||||||||
Placard # / Date | 705197 - 02/18/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | AMIR ZAIN LLC 207 RUBY LAKE LN WINTER HAVEN, FL 33884 |
Effective Date | 10/05/2023 | ||||||||
Contact | MOHAMMED RABI | ||||||||||
Phone | (863) 899-5526 | ||||||||||
SAMRABIO423@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 16000 | Ethanol E10 (8) | 07/01/2007 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 6000 | Unleaded Gas (B) | 02/01/1988 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 6000 | Unleaded Gas (B) | 02/01/1988 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 6000 | Unleaded Gas (B) | 02/01/1988 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 6000 | Vehicular Diesel (D) | 02/01/1988 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel | (C) Fiberglass | (S) Statistical Inventory Reconcile | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | ACE | ||||||||||
INSURANCE | 12/18/2024 | 12/18/2025 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/21/2023 | 03/21/2024 | CRUM & FORSTER SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2020 | 05/13/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2019 | 05/13/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 08/25/2017 | 08/25/2018 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 01/22/2016 | 01/22/2017 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 10/02/2013 | 10/02/2014 | ACE | ||||||||
INSURANCE | 10/02/2012 | 10/02/2013 | ACE | ||||||||
INSURANCE | 10/02/2011 | 10/02/2012 | ACE | ||||||||
INSURANCE | 10/02/2009 | 10/02/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 10/02/2008 | 10/02/2009 | ZURICH-AMERICAN | ||||||||
INSURANCE | 01/18/2007 | 01/18/2008 | ACE | ||||||||
INSURANCE | 04/21/2002 | 04/21/2004 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/21/1999 | 04/22/2002 | COLONY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
NCLI | 05/04/2006 | 05/04/2006 | CASSELS_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: CLOSURE MATERIALS, STRF, TEST RESULTS, SIR REPORTS (12/03-04/06), VISUAL INSPECTIONS, WRITTEN RELEASE DETECTION RESPONSE LEVEL, MAY & JUNE INVENTORY CONTROL/SIR, LINE TIGHTNESS TEST RESULTS, LEAK DETECTOR RESULTS, SIR REPORTS (12/03-04/06). | |||||||||||
TCI | 04/25/2006 | 05/04/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | CASSELS_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes FOUR PHOTOS. PIPING: SINGLE WALL FIBERGLASS PRESSURIZED. VIOLATIONS RESOLVED: 1004. | |||||||||||
CRDE | 06/27/2005 | 08/19/2005 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 06/20/2005 | 06/20/2005 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/15/2005 | 06/20/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND SINGLE-WALL FIBERGLASS | |||||||||||
NCLI | 04/04/2004 | 08/06/2004 | RANDOLPH_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 03/23/2004 | 04/06/2004 | COMPLIANCE ASSURANCE | ||||||||
Completion Notes RECEIVED COPY OF PLACARD, TANK TIGHTNESS TEST AND CFR. | |||||||||||
RRBD | 01/28/2004 | 02/02/2004 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes SIR REPORTS FOR 2003 RECEIVED. RESOLVES VIOLATION #86 & 170. | |||||||||||
TCQA | 01/23/2004 | 02/10/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | RANDOLPH_L | 0/0 | COMPLIANCE ASSURANCE | |||||
NCLI | 01/06/2004 | 01/08/2004 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED SIR REPORTS FOR ALL MONTHS IN 2003. | |||||||||||
TCI | 12/24/2003 | 01/08/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | HUGHES_J | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND SINGLE-WALL FIBERGLASS. RESOLVES VIOLATION #142. | |||||||||||
RRBD | 05/21/2003 | 05/23/2003 | HAUSCHILD_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #103. | |||||||||||
REX | 05/02/2003 | 06/16/2003 | HAUSCHILD_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes EXTENSION UNTIL 5/31/03 | |||||||||||
TCI | 01/31/2003 | 02/06/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | HAUSCHILD_T | 0/4 | COMPLIANCE ASSURANCE | |||||
NCLI | 01/31/2003 | 02/06/2003 | HAUSCHILD_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
CWOE | 12/28/2001 | 01/07/2002 | NEWBERG | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 12/28/2001 | 01/07/2002 | NEWBERG | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED PAPERWORK REQUESTED | |||||||||||
NCLI | 07/27/2001 | 08/06/2001 | NEWBERG | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 07/26/2001 | 08/06/2001 | MINOR OUT-OF-COMPLIANCE | NEWBERG | 0/4 | COMPLIANCE ASSURANCE | |||||
CALL | 07/11/2001 | 08/06/2001 | NEWBERG | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/21/2000 | 02/23/2000 | RONEY_B | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/16/2000 | 02/23/2000 | MINOR OUT-OF-COMPLIANCE | RONEY_B | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 06/15/1999 | 07/14/1999 | MINOR OUT-OF-COMPLIANCE | HUGHES_J | 0/4 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Tracking | 05/07/2025 | Closed Without Enforcement | PEDIGO_L | Enforcement | |||||||
Issue Document | 05/07/2025 | Satisfied | PEDIGO_L | Enforcement | |||||||
Letter | 04/02/2025 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 04/02/2025 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 04/02/2025 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 04/02/2025 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Site Inspection | 04/01/2025 | Major Out of Compliance | CASSELS_CR_2 | 0/1 | Routine Compliance | ||||||
Enforcement Referral | 11/18/2022 | Accepted | CASSELS_CR_2 | Enforcement | |||||||
Site Inspection | 06/07/2022 | Major Out of Compliance | CASSELS_CR_2 | 0/1 | Compliance Assistance | ||||||
Letter | 06/07/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Letter | 06/01/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Site Inspection | 05/31/2022 | Major Out of Compliance | CASSELS_CR_2 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 06/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Letter | 06/03/2019 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Site Inspection | 06/03/2019 | Major Out of Compliance | JARRETT_SE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 06/03/2019 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Phone Conversation | 05/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Phone Conversation | 05/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 05/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Meeting | 05/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Phone Conversation | 05/03/2019 | Satisfied | JARRETT_SE_1 | Routine Compliance | |||||||
Electronic Communication | 01/16/2018 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Letter | 01/16/2018 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 12/29/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Phone Conversation | 12/15/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Meeting | 12/15/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 12/15/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 12/15/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Meeting | 12/15/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 09/12/2016 | Satisfied | CASSELS_CR_2 | Non-Compliance | |||||||
Site Inspection | 09/12/2016 | Minor Out of Compliance | CASSELS_CR_2 | 0/1 | Routine Compliance | ||||||
Letter | 09/12/2016 | Satisfied | CASSELS_CR_2 | Non-Compliance | |||||||
Site Inspection | 04/11/2014 | Minor Out of Compliance | NEWBERG_DR_1 | 0/1 | Routine Compliance | ||||||
Letter | 04/11/2014 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Electronic Communication | 04/11/2014 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Site Inspection | 04/11/2012 | In Compliance | NEWBERG_DR_1 | 0/1 | Non-Compliance | ||||||
Letter | 04/05/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Site Inspection | 04/05/2012 | Minor Out of Compliance | NEWBERG_DR_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 08/01/2011 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Site Inspection | 07/09/2010 | In Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 07/24/2009 | In Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 07/08/2009 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Issue Document | 12/17/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 10/20/2008 | In Compliance | CASSELS_CR_1 | 0/1 | Non-Compliance | ||||||
Issue Document | 09/10/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 08/29/2008 | Minor Out of Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Letter | 08/29/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 08/11/2008 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Issue Document | 05/19/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 03/21/2008 | Minor Out of Compliance | CASSELS_CR_1 | 0/1 | Installation | ||||||
Letter | 03/21/2008 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 07/13/2007 | In Compliance | CASSELS_CR_1 | 0/4 | Closure | ||||||
Emergency Preparedness Information | 02/12/2007 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Issue Document | 12/11/2006 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Record Document | 12/08/2006 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/01/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | All conduit ports must be properly closed and sealed in the STP sumps and the department notified. | |||||||
04/01/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | The corrosion must be removed from the steel components in the premium and diesel STP sumps and treated to maintain corrosion protection, with the department notified. | |||||||
04/01/2025 | 6060 | SNC-B | 4.11 Release detection methods do not meet monitoring requirements. | The double-walled pipe secondary boots must be opened in dispenser liners #1/2 & 3/4 for interstitial monitoring or jumper tubes installed to connect the secondary boots, and the department notified. | |||||||
04/01/2025 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Copies of the complete proof of Financial Responsibility documentation, including all DEP Forms, for the 2023-2024 policy period must be submitted to the Department. | |||||||
04/01/2025 | 6006 | Minor | 2.5 Placard not displayed (or available upon request). | The Placard was printed and posted at the facility at the time of the inspection; therefore, the violation will be closed with issuance of the Compliance Assistance Offer Letter. | |||||||
04/01/2025 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Copies of the completed 2023-2024 and 2024-2025 Certification of Financial Responsibility Forms Part P must be submitted to the Department. | |||||||
04/01/2025 | 6002 | Minor | 2.1 Operator Training records not available. | The store clerk on duty was trained for a Class C Operator Certificate by Class A/B Certificate holder, Sam Alvarez, Fuel Repairs. However, an Owner/Operator's Class A/B Operator Certificate was not available and must be submitted to the department. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
10/07/1998 | COMPLETED | 10 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||