DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 8839781   Latitude    28° 1' .5694
 
Name STRIKE A DEAL
2141 CRYSTAL GROVE DR
Longitude    81° 54' 52.7649
  LAKELAND, FL 33801-6875 LL Method    DPHO
 
Contact TUYET THI VO   LL Status    REVIEWED
 
Phone (863) 606-5252   Status Date    06/09/2003
 
Account Owner Information
 
Name JOHNNY PO BOY
2141 CRYSTAL GROVE DR
LAKELAND, FL 33801
Effective Date    12/18/2017
 
Contact TUYET THI VO
 
Phone (601) 307-0809
 
Email TUYETV38@GMAIL.COM
  Placard # / Date    703689 - 12/03/2024
Property Owner Information
 
Name JOHNNY PO BOY
2141 CRYSTAL GROVE DR
LAKELAND, FL 33801
Effective Date    01/11/2018
 
Contact TUYET THI VO
 
Phone (601) 307-0809
 
Email TUYETV38@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
5 16000 Ethanol E10 (8) 07/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Unleaded Gas (B) 02/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 02/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 6000 Unleaded Gas (B) 02/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 6000 Vehicular Diesel (D) 02/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel   (C) Fiberglass (S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   ACE
INSURANCE   05/13/2020 05/13/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/13/2019 05/13/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   08/25/2017 08/25/2018 ACE AMERICAN INSURANCE COMPANY
INSURANCE   01/22/2016 01/22/2017 ADMIRAL INSURANCE COMPANY
INSURANCE   10/02/2013 10/02/2014 ACE
INSURANCE   10/02/2012 10/02/2013 ACE
INSURANCE   10/02/2011 10/02/2012 ACE
INSURANCE   10/02/2009 10/02/2010 ZURICH-AMERICAN
INSURANCE   10/02/2008 10/02/2009 ZURICH-AMERICAN
INSURANCE   01/18/2007 01/18/2008 ACE
INSURANCE   04/21/2002 04/21/2004 COMMERCE & INDUSTRY
INSURANCE   04/21/1999 04/22/2002 COLONY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
NCLI 05/04/2006 05/04/2006 CASSELS_C 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes REQUESTED: CLOSURE MATERIALS, STRF, TEST RESULTS, SIR REPORTS (12/03-04/06), VISUAL INSPECTIONS, WRITTEN RELEASE DETECTION RESPONSE LEVEL, MAY & JUNE INVENTORY CONTROL/SIR, LINE TIGHTNESS TEST RESULTS, LEAK DETECTOR RESULTS, SIR REPORTS (12/03-04/06).
 
TCI 04/25/2006 05/04/2006 SIGNIFICANT OUT-OF-COMPLIANCE CASSELS_C 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes FOUR PHOTOS. PIPING: SINGLE WALL FIBERGLASS PRESSURIZED. VIOLATIONS RESOLVED: 1004.
 
CRDE 06/27/2005 08/19/2005 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
NCLI 06/20/2005 06/20/2005 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
TCI 04/15/2005 06/20/2005 SIGNIFICANT OUT-OF-COMPLIANCE CROWELL_M 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND SINGLE-WALL FIBERGLASS
 
NCLI 04/04/2004 08/06/2004 RANDOLPH_L 0/0 COMPLIANCE ASSURANCE
 
RRBD 03/23/2004 04/06/2004 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED COPY OF PLACARD, TANK TIGHTNESS TEST AND CFR.
 
RRBD 01/28/2004 02/02/2004 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SIR REPORTS FOR 2003 RECEIVED. RESOLVES VIOLATION #86 & 170.
 
TCQA 01/23/2004 02/10/2004 SIGNIFICANT OUT-OF-COMPLIANCE RANDOLPH_L 0/0 COMPLIANCE ASSURANCE
 
NCLI 01/06/2004 01/08/2004 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes REQUESTED SIR REPORTS FOR ALL MONTHS IN 2003.
 
TCI 12/24/2003 01/08/2004 SIGNIFICANT OUT-OF-COMPLIANCE HUGHES_J 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND SINGLE-WALL FIBERGLASS. RESOLVES VIOLATION #142.
 
RRBD 05/21/2003 05/23/2003 HAUSCHILD_T 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #103.
 
REX 05/02/2003 06/16/2003 HAUSCHILD_T 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes EXTENSION UNTIL 5/31/03
 
NCLI 01/31/2003 02/06/2003 HAUSCHILD_T 0/0 COMPLIANCE ASSURANCE
 
TCI 01/31/2003 02/06/2003 SIGNIFICANT OUT-OF-COMPLIANCE HAUSCHILD_T 0/4 COMPLIANCE ASSURANCE
 
CWOE 12/28/2001 01/07/2002 NEWBERG 0/0 COMPLIANCE ASSURANCE
 
RRBD 12/28/2001 01/07/2002 NEWBERG 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED PAPERWORK REQUESTED
 
NCLI 07/27/2001 08/06/2001 NEWBERG 0/0 COMPLIANCE ASSURANCE
 
TCI 07/26/2001 08/06/2001 MINOR OUT-OF-COMPLIANCE NEWBERG 0/4 COMPLIANCE ASSURANCE
 
CALL 07/11/2001 08/06/2001 NEWBERG 0/0 COMPLIANCE ASSURANCE
 
NCLI 02/21/2000 02/23/2000 RONEY_B 0/0 COMPLIANCE ASSURANCE
 
TCI 02/16/2000 02/23/2000 MINOR OUT-OF-COMPLIANCE RONEY_B 0/4 COMPLIANCE ASSURANCE
 
TCI 06/15/1999 07/14/1999 MINOR OUT-OF-COMPLIANCE HUGHES_J 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/18/2022 Accepted CASSELS_CR_2 Enforcement
 
Site Inspection 06/07/2022 Major Out of Compliance CASSELS_CR_2 0/1 Compliance Assistance
 
Letter 06/07/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Letter 06/01/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Site Inspection 05/31/2022 Major Out of Compliance CASSELS_CR_2 0/1 Routine Compliance
 
Electronic Communication 06/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Site Inspection 06/03/2019 Major Out of Compliance JARRETT_SE_1 0/1 Routine Compliance
 
Electronic Communication 06/03/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Letter 06/03/2019 Satisfied JARRETT_SE_1 Compliance Assistance
 
Phone Conversation 05/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Meeting 05/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 05/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Phone Conversation 05/03/2019 Satisfied JARRETT_SE_1 Routine Compliance
 
Electronic Communication 01/16/2018 Satisfied CASSELS_CR_2 Compliance Assistance
 
Letter 01/16/2018 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 12/29/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Meeting 12/15/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Meeting 12/15/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Phone Conversation 12/15/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 12/15/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 12/15/2017 Satisfied CASSELS_CR_2 Compliance Assistance
 
Letter 09/12/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Electronic Communication 09/12/2016 Satisfied CASSELS_CR_2 Non-Compliance
 
Site Inspection 09/12/2016 Minor Out of Compliance CASSELS_CR_2 0/1 Routine Compliance
 
Site Inspection 04/11/2014 Minor Out of Compliance NEWBERG_DR_1 0/1 Routine Compliance
 
Electronic Communication 04/11/2014 Satisfied NEWBERG_DR_1 Routine Compliance
 
Letter 04/11/2014 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 04/11/2012 In Compliance NEWBERG_DR_1 0/1 Non-Compliance
 
Site Inspection 04/05/2012 Minor Out of Compliance NEWBERG_DR_1 0/1 Routine Compliance
 
Letter 04/05/2012 Satisfied NEWBERG_DR_1 Non-Compliance
 
Electronic Communication 08/01/2011 Satisfied CASSELS_CR_1 Routine Compliance
 
Site Inspection 07/09/2010 In Compliance CASSELS_CR_1 0/1 Routine Compliance
 
Site Inspection 07/24/2009 In Compliance CASSELS_CR_1 0/1 Routine Compliance
 
Phone Conversation 07/08/2009 Satisfied CASSELS_CR_1 Routine Compliance
 
Issue Document 12/17/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 10/20/2008 In Compliance CASSELS_CR_1 0/1 Non-Compliance
 
Issue Document 09/10/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 08/29/2008 Minor Out of Compliance CASSELS_CR_1 0/1 Routine Compliance
 
Letter 08/29/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Phone Conversation 08/11/2008 Satisfied CASSELS_CR_1 Routine Compliance
 
Issue Document 05/19/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 03/21/2008 Minor Out of Compliance CASSELS_CR_1 0/1 Installation
 
Letter 03/21/2008 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 07/13/2007 In Compliance CASSELS_CR_1 0/4 Closure
 
Emergency Preparedness Information 02/12/2007 Satisfied NEWBERG_DR_1 Routine Compliance
 
Issue Document 12/11/2006 Satisfied CASSELS_CR_1 Non-Compliance
 
Record Document 12/08/2006 Satisfied CASSELS_CR_1 Non-Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied CASSELS_CR_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
06/01/2022 6082 Minor 4.13 Closure Integrity Report and Evaluation not completed and submitted in a timely fashion. Closure assessment sampling must be performed at time of component closure. As there is no Corrective Action possible, the violation will be closed with issuance of the Compliance Assistance Offer Letter.
 
05/31/2022 6076 Minor 4.7 Requirements not met for out-of-service systems. The tank must be registered as In-service, after all required testing is completed immediately, or the fuel must be removed from the tank. Copies of all required test reports must be submitted to the Department, or a copy of the pump out manifest must be submitted and the Department contacted for re-inspection.
 
05/31/2022 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. The DEP CFR Form Part P for the 2020-2021 policy must be completed and a copy submitted to the Department.
 
05/31/2022 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. A completed Storage Tank Registration Form must be submitted to the Department will all corrections and updates made, or the information can be updated using the DEP's self-service application portal (ESSA) at: https://floridadep.gov/waste/permitting-compliance-assistance/content/storage-tank-facility-registration.
 
05/31/2022 6024 Minor 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. A 48 to 72 hour notification must be provided to the Department for when a technician will return to the site with the proper apparatus to perform the proper test, for an inspection to observe the required post-construction installation testing.
 
05/31/2022 6077 Minor 4.8 Out of service storage tank systems not tested annually for operability or interstice and liquid level not monitored annually. All required testing must be performed immediately and the tank registered In-service, or the fuel must be removed from the tank immediately, and the Department notified.
 
05/31/2022 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Financial Responsibility must be demonstrated until the tank is permanently closed, including when it is out-of-service. Financial Responsibility must be demonstrated by getting the insurance re-instated with a retroactive date back to 05/13/2021, or by acquiring gap insurance for the period between 05/13/2021 and date of any new insurance policy, or the tank must be closed per 62-761.800(2)(a)3., Florida Administrative Code (FAC).
 
05/31/2022 6076 Minor 4.7 Requirements not met for out-of-service systems. An out-of-service tank cannot contain more than one inch of liquid. The PCW must be removed so that no more than one inch is present and the Department notified.
 
05/31/2022 6051 SNC-B 4.5 Overfill prevention not provided or properly functioning. The overfill protection equipment (drop tube overfill prevention valves) must be repaired or replaced and re-tested immediately, with a copy of the work order and test reports submitted to the Department. No fuel should be added to the tank without proper functioning overfill protection.
 
05/31/2022 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. As the INF has now been submitted, the violation will be closed with issuance of the Compliance Assistance Offer Letter.
 
05/31/2022 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Access must be provided to the tank interstitial port and the Department notified.
 
05/31/2022 6008 Minor 2.7 For installation, closure, or change in service status, notification not received in a timely manner. As there is no Corrective Action possible, the violation will be closed with issuance of the Compliance Assistance Offer Letter.
 
05/31/2022 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. All requested Financial Responsibility documentation must be submitted to the Department. The 05/13/2020 - 05/13/2021 ACE policy was sent after the inspection; however, the current 2021-2022 policy has not been submitted.
 
06/03/2019 4059 SNC-B 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. A release detection inspection must be performed immediately with a copy of the inspection record submitted to the Department. - Inspection records must include visual inspection of the UST and piping interstices, including visual inspection of the STP sumps, dispensing systems (liners, nozzles, hoses, and breakaway devices) and double-walled, spill containment buckets (including interstices).
 
06/03/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Access must be provided to the spill bucket interstices (bolts opened) and the Department contacted for inspection.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
10/07/1998   COMPLETED 10 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE