Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Broward | Status | OPEN | ||||||||
ID | 8842086 | Latitude | 26° 7' 26.9175 | ||||||||
Name |
HCA FLORIDA WESTSIDE HOSPITAL 8201 W BROWARD BLVD |
Longitude | 80° 15' 31.8931 | ||||||||
PLANTATION, FL 33324-2701 | LL Method | DGPS | |||||||||
Contact | SCOTT BRACCI | LL Status | REVIEWED | ||||||||
Phone | (654) 476-3927 | Status Date | 03/09/2004 | ||||||||
Account Owner Information | |||||||||||
Name | COLUMBIA HOSPITAL CORPORATION OF SOUTH BROWARD 8201 W BROWARD BLVD FORT LAUDERDALE, FL 33324-2701 |
Effective Date | 11/03/1988 | ||||||||
Contact | SCOTT BRACCI | ||||||||||
Phone | (954) 473-6600 | ||||||||||
SCOTT.BRACCI@HCAHEALTHCARE.COM | |||||||||||
Placard # / Date | 686128 - 06/10/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | COLUMBIA HOSPITAL CORPORATION OF SOUTH BROWARD 8201 W BROWARD BLVD FORT LAUDERDALE, FL 33324-2701 |
Effective Date | 06/04/2019 | ||||||||
Contact | SCOTT BRACCI | ||||||||||
Phone | (954) 473-6600 | ||||||||||
SCOTT.BRACCI@HCAHEALTHCARE.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 6000 | Emerg Generator Diesel (G) | 04/01/2017 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (I) Suction piping system (M) Double wall - pipe jacket |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 6000 | Emerg Generator Diesel (G) | 04/01/2017 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (I) Suction piping system (M) Double wall - pipe jacket |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Emerg Generator Diesel (G) | 02/01/2018 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (J) Pressurized piping system (M) Double wall - pipe jacket |
(F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 5000 | Emerg Generator Diesel (G) | 04/01/1973 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 1000 | Emerg Generator Diesel (G) | 01/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system (M) Double wall - pipe jacket |
(2) Visual inspect pipe sumps (B) Site Suitabilitiy Plan exemption (F) Monitor dbl wall tank space (H) Mechanical line leak detector (N) Groundwater monitoring |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 1000 | Emerg Generator Diesel (G) | 01/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system (M) Double wall - pipe jacket |
(2) Visual inspect pipe sumps (B) Site Suitabilitiy Plan exemption (F) Monitor dbl wall tank space (H) Mechanical line leak detector (N) Groundwater monitoring |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 6000 | Emerg Generator Diesel (G) | 07/01/1993 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system (M) Double wall - pipe jacket |
(2) Visual inspect pipe sumps (B) Site Suitabilitiy Plan exemption (F) Monitor dbl wall tank space (H) Mechanical line leak detector (N) Groundwater monitoring |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
NONE | |||||||||||
INSURANCE | 09/01/2024 | 09/01/2025 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2023 | 09/01/2024 | ILLINOIS UNION INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2020 | 09/01/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2019 | 09/01/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
EXEMPT-NOT REQUIRED | 11/01/2018 | 03/31/2019 | |||||||||
INSURANCE | 09/01/2018 | 09/01/2019 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2016 | 09/01/2018 | ACE | ||||||||
INSURANCE | 09/01/2015 | 09/01/2016 | ACE | ||||||||
INSURANCE | 09/01/2013 | 09/01/2014 | STEADFAST | ||||||||
INSURANCE | 09/01/2011 | 09/01/2012 | STEADFAST | ||||||||
INSURANCE | 09/01/2010 | 09/01/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/01/2009 | 09/01/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 05/01/2008 | 05/01/2009 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 12/20/2005 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 04/27/2005 | 05/02/2005 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 03/30/2005 | 04/05/2005 | MINOR OUT-OF-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/04/2004 | 02/09/2004 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 08/16/2002 | 09/11/2002 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 04/04/2002 | 05/02/2002 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/18/2002 | 02/27/2002 | MINOR OUT-OF-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 01/29/2001 | 02/01/2001 | IN-COMPLIANCE | MARDIS_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 06/21/2000 | 06/28/2000 | IN-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 01/21/2000 | 02/07/2000 | MINOR OUT-OF-COMPLIANCE | HUMPHRIES_F | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 10/31/2024 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Site Inspection | 10/31/2024 | Major Out of Compliance | SCOTT_DC_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 10/21/2024 | Satisfied | SCOTT_DC_1 | Routine Compliance | |||||||
Enforcement Tracking | 06/10/2024 | Closed Without Enforcement | KOENIG_EJ_1 | Enforcement | |||||||
Letter | 06/06/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Record Document | 06/06/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Record Document | 05/23/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Letter | 05/22/2024 | Satisfied | KOENIG_EJ_1 | Incident | |||||||
Record Document | 05/22/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Record Document | 05/03/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Phone Conversation | 05/02/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Phone Conversation | 05/02/2024 | Satisfied | WHITAKER_AJ_1 | Routine Compliance | |||||||
Record Document | 04/18/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Record Document | 04/12/2024 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Record Document | 10/23/2023 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Enforcement Referral | 06/02/2023 | Accepted | KOENIG_EJ_1 | Enforcement | |||||||
Site Inspection | 04/28/2023 | Minor Out of Compliance | WHITAKER_AJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 04/28/2023 | Satisfied | WHITAKER_AJ_1 | Compliance Assistance | |||||||
Electronic Communication | 04/17/2023 | Satisfied | WHITAKER_AJ_1 | Routine Compliance | |||||||
Phone Conversation | 04/17/2023 | Satisfied | WHITAKER_AJ_1 | Routine Compliance | |||||||
Letter | 03/09/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Record Document | 03/09/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Site Inspection | 02/28/2021 | Minor Out of Compliance | SCOTT_DC_1 | 0/3 | Routine Compliance | ||||||
Letter | 02/28/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Site Inspection | 11/01/2019 | In Compliance | WICKE_CJ_1 | 0/3 | Installation | ||||||
Letter | 04/02/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Document Management | 04/02/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
TCAR | 04/02/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Site Inspection | 03/18/2019 | In Compliance | WHITAKER_AJ_1 | 0/1 | Closure | ||||||
Document Management | 03/14/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Letter | 02/19/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Document Management | 02/06/2019 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Document Management | 10/26/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Electronic Communication | 08/07/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Document Management | 08/07/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
TCAR | 08/07/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Letter | 08/07/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Electronic Communication | 06/11/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Site Inspection | 05/07/2018 | In Compliance | SCOTT_DC_1 | 0/4 | Routine Compliance | ||||||
Letter | 05/07/2018 | Satisfied | SCOTT_DC_1 | Routine Compliance | |||||||
Phone Conversation | 05/02/2018 | Satisfied | SCOTT_DC_1 | Routine Compliance | |||||||
Document Management | 04/13/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Site Inspection | 02/07/2018 | In Compliance | WICKE_CJ_1 | 0/1 | Closure | ||||||
Site Inspection | 01/23/2018 | In Compliance | MARDIS_FH_1 | 0/3 | Closure | ||||||
Electronic Communication | 01/12/2018 | Satisfied | JEANBAPTISTE_C_1 | Installation | |||||||
Letter | 01/03/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Document Management | 01/03/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
TCAR | 01/03/2018 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Site Inspection | 02/19/2016 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
Phone Conversation | 02/12/2016 | Satisfied | SCOTT_DC_1 | Routine Compliance | |||||||
Site Inspection | 09/06/2013 | In Compliance | COOPER_RA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 03/29/2012 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 05/23/2011 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 04/27/2010 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 08/07/2008 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/07/2008 | In Compliance | MARDIS_FH_1 | 0/4 | Routine Compliance | ||||||
Site Inspection | 05/09/2007 | In Compliance | MARDIS_FH_1 | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/31/2024 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Make repairs to 6k western tank Pneumercator system to ensure that alarm conditions are activated on console, re-test and provide results to inspector upon completion. | |||||||
10/31/2024 | 6051 | SNC-B | 4.5 Overfill prevention not provided or properly functioning. | Make necessary repairs to system and re-test to ensure that overfill device is operational, provide testing report to inspector when completed. | |||||||
10/30/2024 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Make necessary repairs to console, provide confirmation to inspector when completed. | |||||||
10/30/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Have liquid inside of spill containment components properly removed and disposed of by a licensed hauler. Provide confirmation to inspector upon completion. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
08/01/1997 | COMPLETED | 61 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||