Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Fuel user/Non-retail | ||||||||
County | Escambia | Status | OPEN | ||||||||
ID | 8942860 | Latitude | 30° 51' 32.9414 | ||||||||
Name |
EICHER GREG 1931 N HWY 99 |
Longitude | 87° 27' 55.5195 | ||||||||
WALNUT HILL, FL 32568-9719 | LL Method | DPHO | |||||||||
Contact | EICHER GREG | LL Status | REVIEWED | ||||||||
Phone | Status Date | 06/30/2015 | |||||||||
Account Owner Information | |||||||||||
Name | EICHER, GREG 1931 N HWY 99 WALNUT HILL, FL 32568-9719 |
Effective Date | 01/20/1989 | ||||||||
Contact | GREG EICHER | ||||||||||
Phone | 0 | ||||||||||
Placard # / Date | |||||||||||
Property Owner Information | |||||||||||
Name | WESLEY A WIGGINS & GRETCHEN E WIGGINS 4251 CECILS RD CENTURY, FL 32535 |
Effective Date | 03/02/2020 | ||||||||
Contact | |||||||||||
Phone | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 250 | Unleaded Gas (B) | 07/01/1985 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (A) Abv, no soil contact | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 250 | Unleaded Gas (B) | 07/01/1985 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (A) Abv, no soil contact | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 550 | Vehicular Diesel (D) | 07/01/1966 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1R1 | 1000 | Vehicular Diesel (D) | 07/01/1985 | ABOVEGROUND | Closed In Place (A) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (A) Abv, no soil contact | (I) Not required | |||||||||
No Insurance Documents Found | |||||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 06/29/2021 | Accepted | WILSON_ML_1 | Enforcement | |||||||
Letter | 06/11/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 06/11/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 06/11/2021 | Major Out of Compliance | WILSON_ML_1 | 0/0 | Complaint | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
06/11/2021 | 5034 | SNC-B | 3.15 Storage tank system not installed according to reference guidelines for shop fabricated tank systems. | Have vent piping installed to meet the general requirements for storage tanks. Submit a copy of the invoice and pictures to the inspector for review. Email: Monica.Wilson@FLHealth.gov | |||||||
06/11/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Have an overfill device installed on the 12,000 gallon tank. If the smaller tank next to the 12,000 gallon tank (about 2,000 gallon) is in use, an overfill device would need to be installed, if not, the tank will need to be registered accordingly. The tank in the pole barn will need to have an operability test completed. Submit invoice, testing results for all currently and newly installed overfill device, registration form and pictures to the inspector for review. Email: Monica.Wilson@FLHealth.gov. | |||||||
06/11/2021 | 5093 | SNC-A | 3.6 Shop fabricated storage tank systems not provided with a release detection method to detect a new release from any portion of the system, including interstitial spaces. | It cannot be determined how the release detection is monitored for the 12,000 gallon tank and the Pole Barn Tank. Verify that the tanks do have an interstice and have a release detection device installed. Submit a copy of the invoice, pictures and operability test results of the release detection device. If the tank or tanks are single-walled, the product would need to be immediately emptied and the tank place out-of-service or properly closed. Single wall tanks that are regulated size are required to be in an FDEP approved containment dike. Email: Monica.Wilson@FLHealth.gov | |||||||
06/11/2021 | 4045 | SNC-B | 4.22 Storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. | Have a spill container installed at the fill connection/fill piping for all 3 ASTs . Submit invoice and pictures to the inspector for review. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Obtain Pollutant Liability Insurance Coverage and submit FDEP Financial Mechanisms Part C or D from the insurance company and Part P from the owner. Email FDEP Financial Mechanism Forms to the inspector for review to clear the violation. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5032 | Minor | 3.13 Exterior portions of tanks and integral piping not protected from external corrosion, deterioration or degradation for shop fabricated tank systems. | Remove surface rust from the tank and apply an FDEP approved rust preventative paint. Florida DEP Approved Equipment List can be found: https://floridadep.gov/waste/permitting-compliance-assistance/documents/storage-tank-equipment-approvalregistration-list. Contact the inspector once work on the containment has been completed and send pictures of the newly painted tank. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5003 | Minor | 1.3 Following owner change or discovery of unregistered facility, Registration Form not submitted. | Complete a Storage Tank Registration Form, updating the facility address and add the 3 regulated size aboveground storage tanks. Once completed, submit the Tank Registration Form to the inspector for review. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | Repair the piping and contact the inspector once work has been completed. Clean the concrete slab where the product has leaked. Submit any invoices and pictures to the inspector for review. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5005 | SNC-B | 1.5 Motor fuel being deposited into storage tank at facility where valid registration placard is not displayed. | Register the 3 Aboveground Storage Tanks at the facility and pay the registration fees in full to obtain an FDEP Storage Tank Placard. Once your placard is obtained, post the placard in a visible location inside the facility or within a record keeping book. Submit a copy of the placard to the inspector. Email: Monica.Wilson@FLHealth.gov | |||||||
06/09/2021 | 5027 | SNC-B | 3.8 Integrity test not conducted before placing into service for shop fabricated tank systems. | Have a certified technician test the integrity of the 3 regulated ASTs that were found at the facility. Once completed, send a copy of the test results to the inspector for review. Email: Monica.Wilson@FLHealth.gov | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/30/1988 | INACTIVE | 5 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||