District Northwest   Type    Retail Station
 
County Escambia   Status    OPEN
 
ID 8943512   Latitude    30° 24' 10.4334
 
Name MR - Pensacola
2 S BLUE ANGEL PKWY
Longitude    87° 20' 31.8408
  PENSACOLA, FL 32506-6045 LL Method    DPHO
 
Contact Rich Sillery   LL Status    REVIEWED
 
Phone (202) 777-2005   Status Date    07/01/2015
 
Account Owner Information
 
Name MR SQRL Retail LLC
750 17th Street NW
Washington, DC 20006
Effective Date    09/12/2023
 
Contact Rich Sillery
 
Phone (202) 777-2005
 
Email rsillery@monumentretail.com
  Placard # / Date   
Property Owner Information
 
Name MR SQRL Retail LLC
750 17th Street NW
Washington, DC 20006
Effective Date    09/12/2023
 
Contact Rich Sillery
 
Phone (202) 777-2005
 
Email rsillery@monumentretail.com
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 15000 Unleaded Gas (B) 12/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 20000 Leaded Gas (A) 12/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 03/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 03/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 03/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-NON REGULATED  
INSURANCE   12/14/2023 07/14/2024 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   03/08/2023 03/08/2024 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   03/08/2022 03/08/2023 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   02/24/2016 02/23/2017 WESTFIELD INSURANCE COMPANY
INSURANCE   02/24/2015 02/24/2016 WESTCHESTER SURPLUS LINES INS CO
INSURANCE   02/20/2013 02/20/2014 FEDERATED MUTUAL
INSURANCE   12/17/2009 12/01/2011 CHUBB
INSURANCE   11/01/2009 11/01/2010 ZURICH-AMERICAN
INSURANCE   11/01/2007 11/01/2008 ZURICH-AMERICAN
INSURANCE   04/23/1994 04/23/1995 PLUS
INSURANCE   04/23/1993 04/23/1994 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 02/14/2006 02/15/2006 MINOR OUT-OF-COMPLIANCE ARTHUR B. TISSINGTON 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes REGISTRATION FORM SENT TO OWNER TO UPDATE FACILITY NAME AND OWNER INFORMATION.
 
RRBD 12/17/2004 12/20/2004 COMPLIANCE ASSURANCE
 
RRBD 11/18/2004 11/19/2004 COMPLIANCE ASSURANCE
 
TCI 11/12/2004 11/16/2004 MINOR OUT-OF-COMPLIANCE ARTHUR B. TISSINGTON 0/3 COMPLIANCE ASSURANCE
 
RRBD 12/31/2003 01/02/2004 COMPLIANCE ASSURANCE
 
TIN 12/19/2003 12/24/2003 SIGNIFICANT OUT-OF-COMPLIANCE JOHN B. HOLLINGSHEAD 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes THIS INSTALLATION INSPECTION FOR UPGRADE OF EXISTING SYSTEM.
 
TCI 07/22/2003 07/31/2003 SIGNIFICANT OUT-OF-COMPLIANCE JOHN S. STEVENSON 0/3 COMPLIANCE ASSURANCE
 
TCI 10/10/2002 10/30/2002 IN-COMPLIANCE JOHN S. STEVENSON 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes STORE CLOSED, DISPENSERS REMOVED, TANKS LOCKED
 
RRBD 05/29/2002 05/30/2002 COMPLIANCE ASSURANCE
 
TCI 10/30/2001 12/05/2001 MINOR OUT-OF-COMPLIANCE STEVENSON_JS 0/3 COMPLIANCE ASSURANCE
 
TCI 09/20/2000 09/26/2000 IN-COMPLIANCE STEVENSON_JS 0/3 COMPLIANCE ASSURANCE
 
RRBD 10/25/1999 12/08/1999 STEVENSON_JS 0/0 COMPLIANCE ASSURANCE
 
TCI 09/07/1999 09/20/1999 SIGNIFICANT OUT-OF-COMPLIANCE STEVENSON_JS 0/3 COMPLIANCE ASSURANCE
 
RRBD 12/22/1998 11/15/1999 STEVENSON_JS 0/0 COMPLIANCE ASSURANCE
 
UTII 11/06/1998 12/14/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Document Management 04/21/2025 Satisfied GILLMAN_M Enforcement
 
Electronic Communication 03/27/2025 Satisfied GILLMAN_M Enforcement
 
Electronic Communication 03/27/2025 Satisfied GILLMAN_M Enforcement
 
Electronic Communication 03/04/2025 Satisfied GILLMAN_M Enforcement
 
Phone Conversation 03/04/2025 Satisfied GILLMAN_M Enforcement
 
Phone Conversation 02/21/2025 Satisfied GILLMAN_M Enforcement
 
Document Management 02/05/2025 Satisfied GILLMAN_M Enforcement
 
Letter 08/27/2024 Satisfied GILLMAN_M Enforcement
 
Electronic Communication 08/06/2024 Satisfied GILLMAN_M Enforcement
 
Enforcement Referral 06/26/2024 Accepted ELLIOTT_EV_1 Enforcement
 
Record Document 06/12/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Letter 03/22/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Site Inspection 03/22/2024 Major Out of Compliance ELLIOTT_EV_1 0/2 Routine Compliance
 
Enforcement Tracking 07/25/2022 Closed Without Enforcement MATHERLY_H Enforcement
 
Letter 06/21/2022 Satisfied MATHERLY_H Enforcement
 
Enforcement Referral 06/08/2022 Accepted GARTIN_D Enforcement
 
Electronic Communication 05/19/2022 Satisfied GARTIN_D Compliance Assistance
 
Issue Document 03/23/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 03/23/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 03/23/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 03/21/2022 Major Out of Compliance GARTIN_D 0/2 Routine Compliance
 
Electronic Communication 03/21/2022 Satisfied GARTIN_D Routine Compliance
 
Enforcement Tracking 07/16/2021 Closed With Enforcement GILLMAN_M Enforcement
 
Enforcement Tracking 07/16/2021 Closed Without Enforcement GILLMAN_M Enforcement
 
Document Management 06/30/2021 Satisfied MERRITT_S Enforcement
 
Document Management 05/25/2021 Satisfied MERRITT_S Enforcement
 
Document Management 05/10/2021 Satisfied MERRITT_S Enforcement
 
Document Management 01/20/2021 Satisfied MERRITT_S Enforcement
 
Enforcement Referral 02/11/2020 Accepted BRAGG_SD_2 Enforcement
 
Electronic Communication 12/13/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Electronic Communication 12/09/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Electronic Communication 12/06/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Issue Document 11/27/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 11/27/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 11/26/2019 Major Out of Compliance BRAGG_SD_2 0/2 Routine Compliance
 
Enforcement Referral 07/19/2018 Accepted BRAGG_SD_2 Enforcement
 
Record Document 10/27/2017 Satisfied BRAGG_SD_2 Compliance Assistance
 
Site Inspection 08/03/2017 Major Out of Compliance BRAGG_SD_2 0/2 Routine Compliance
 
Letter 08/03/2017 Satisfied WILSON_ML_1 Compliance Assistance
 
Phone Conversation 07/20/2017 Satisfied BRAGG_SD_2 Routine Compliance
 
Site Inspection 10/16/2015 In Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Emergency Preparedness Information 10/13/2015 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 12/09/2013 In Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Emergency Preparedness Information 12/04/2013 Satisfied PAYNE_CL_1 Routine Compliance
 
Letter 04/12/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 04/10/2013 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 04/10/2013 Minor Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Incident 06/27/2011 Has not led to Discharge PORTER_AJ_1 Incident
 
Record Document 05/23/2011 Satisfied PORTER_AJ_1 Non-Compliance
 
Letter 04/18/2011 Satisfied RHOADS_KM_1 Non-Compliance
 
Site Inspection 04/14/2011 Minor Out of Compliance PORTER_AJ_1 0/2 Routine Compliance
 
Emergency Preparedness Information 04/14/2011 Satisfied PORTER_AJ_1 Routine Compliance
 
Incident 01/24/2011 Has not led to Discharge PORTER_AJ_1 Incident
 
Document Management 01/13/2011 Complete PORTER_AJ_1 Incident
 
Document Management 11/30/2010 Complete PORTER_AJ_1 Incident
 
Document Management 10/04/2010 Complete PORTER_AJ_1 Incident
 
Incident 10/04/2010 Has not led to Discharge PORTER_AJ_1 Incident
 
Record Document 10/01/2010 Satisfied PORTER_AJ_1 Routine Compliance
 
Site Inspection 06/22/2010 In Compliance PORTER_AJ_1 0/2 Non-Compliance
 
Letter 04/19/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 04/07/2010 Major Out of Compliance PORTER_AJ_1 0/2 Routine Compliance
 
Record Document 12/07/2009 Satisfied PORTER_AJ_1 Non-Compliance
 
Record Document 09/28/2009 Satisfied PORTER_AJ_1 Non-Compliance
 
Record Document 09/24/2009 Satisfied PORTER_AJ_1 Non-Compliance
 
Letter 09/08/2009 Satisfied PORTER_AJ_1 Non-Compliance
 
Site Inspection 09/02/2009 Minor Out of Compliance PORTER_AJ_1 0/2 Non-Compliance
 
Letter 04/06/2009 Satisfied STEVENSON_JS Non-Compliance
 
Emergency Preparedness Information 04/02/2009 Satisfied STEVENSON_JS Routine Compliance
 
Record Document 04/02/2009 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 04/01/2009 Major Out of Compliance STEVENSON_JS 0/2 Routine Compliance
 
TCAR 03/26/2009 Complete STEVENSON_JS Closure
 
Letter 03/26/2009 Satisfied STEVENSON_JS Closure
 
Letter 03/26/2009 Satisfied STEVENSON_JS Closure
 
Site Inspection 12/20/2007 In Compliance STEVENSON_JS 0/2 Installation
 
Site Inspection 12/20/2007 In Compliance STEVENSON_JS 0/3 Closure
 
Emergency Preparedness Information 12/19/2007 Satisfied STEVENSON_JS Routine Compliance
 
Phone Conversation 10/15/2007 Satisfied STEVENSON_JS Non-Compliance
 
Letter 09/19/2007 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 09/12/2007 Major Out of Compliance STEVENSON_JS 0/3 Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Emergency Preparedness Information 10/02/2006 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Site Inspection 09/06/2006 In Compliance TISSINGTON_AB_1 0/3 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/22/2024 6043 Minor 4.13 Fillbox covers not marked according to requirements. Have the Regular spill bucket lid repainted according to API standards. Email to the inspector a detailed work invoice indicating that the Regular spill bucket lid has been painted and/or a picture of the painted Regular spill bucket lid. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have all the liquid removed from the premium and non-ethanol spill containments. Email a copy of the work invoice to the inspector for review and pictures of the cleared spill containments. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6002 Minor 2.1 Operator Training records not available. Have each employee of the facility take Class C Operator Training. Email to the inspector Class C Operator Training Certificates for review. Email: Emily.Elliott@FLHealth.gov.
 
03/22/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Test the Ball Valves for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Submit a registration form to indicate that Tank #5 contains Unleaded Gas to the inspector for review and to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the Double Wall Spill Containments. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Start conducting and continue conducting monthly visual inspections. Provide the inspector at least three months of monthly visual inspections that do not exceed 35 days. The monthly inspections can’t be prefilled out for the year. Email the inspector the paperwork to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Have a certified contractor remove the valves beneath dispenser 1/2. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the valves have been removed. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. Complete the FDEP Financial Mechanism Part P Form to match the Insurance Part C From. Once completed, send the Part P Form to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6062 Minor 2.5 Release detection devices not tested annually. Test the Line Leak Detectors for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from Dispenser 3/4. Email a copy of the work invoice to the inspector for review and pictures of Dispenser 3/4 to show the liquid has been removed. Email: Emily.Elliott@FLHealth.gov
 
03/22/2024 6001 Minor 2.1 No reasonable access provided. Coordinate with the inspector to schedule a re-inspection and ensure that a facility representative will be at the facility on the date of scheduled inspection and the STP Sumps are able to be accessible. Email: Emily.Elliott@FLHealth.gov
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/16/2003   COMPLETED
 