DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Taylor   Status    OPEN
 
ID 8943659   Latitude    30° 5' 51.8164
 
Name SPEED STOP- FARZANA 23 INC
2269 HWY 27 E
Longitude    83° 32' 59.2339
  PERRY, FL 32347-9554 LL Method    DPHO
 
Contact Rabeya Rahim   LL Status    REVIEWED
 
Phone (850) 584-8885   Status Date    04/04/2003
 
Account Owner Information
 
Name FARZANA 23 INC
2269 HWY 27 E
PERRY, FL 32347
Effective Date    11/07/2023
 
Contact RABEYA RAHIM
 
Phone (352) 356-1882
 
Email RABEYA.RAHIM@YAHOO.COM
  Placard # / Date    703236 - 10/29/2024
Property Owner Information
 
Name FARZANA 23 INC
2269 HWY 27 E
PERRY, FL 32347
Effective Date    11/07/2023
 
Contact RABEYA RAHIM
 
Phone (352) 356-1882
 
Email RABEYA.RAHIM@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
215200 15000 Unleaded Gas (B) 02/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 6000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   10/09/2023 10/09/2024 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/01/2021 04/01/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/01/2020 04/01/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   06/22/2019 06/22/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/22/2018 06/22/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/22/2017 06/22/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/22/2016 06/22/2017 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/19/2015 06/19/2016 COMMERCE & INDUSTRY
INSURANCE   06/18/2014 06/18/2015 COMMERCE & INDUSTRY
INSURANCE   06/18/2013 06/18/2014 COMMERCE & INDUSTRY
INSURANCE   06/18/2012 06/18/2013 ZURICH-AMERICAN
INSURANCE   06/18/2011 06/18/2012 ZURICH-AMERICAN
INSURANCE   06/18/2010 06/18/2011 ZURICH-AMERICAN
INSURANCE   06/18/2009 06/18/2010 ZURICH-AMERICAN
INSURANCE   08/01/2008 08/01/2009 ZURICH-AMERICAN
INSURANCE   08/01/1999 08/01/2004 UNITED CAPITOL
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 12/05/2005 12/30/2005 IN-COMPLIANCE PAUL HUTCHERSON 0/3 COMPLIANCE ASSURANCE
 
TCI 09/30/2004 10/10/2004 IN-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes TCI
 
TCI 10/27/2003 11/07/2003 IN-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes TCI
 
CWOE 02/03/2003 02/13/2003 GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
TCR 02/03/2003 02/13/2003 IN-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
NCLI 01/24/2003 01/27/2003 GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
TCI 11/06/2002 01/27/2003 SIGNIFICANT OUT-OF-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
NCLI 01/25/2002 03/15/2002 GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes SHEAR VALVES AND SMALL LEAK
 
TCR 01/08/2002 03/15/2002 IN-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes COMPLIED
 
CWOE 01/08/2002 03/15/2002 GARRY ALLSHOUSE 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes COMPLIED
 
TCI 12/13/2001 03/15/2002 SIGNIFICANT OUT-OF-COMPLIANCE GARRY ALLSHOUSE 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 76, 144
 
RRBD 05/07/2001 05/25/2001 MEISSNER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes CLEARED VIOLATION
 
TCI 03/20/2001 04/17/2001 MINOR OUT-OF-COMPLIANCE MEISSNER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes LINE LEAK DETECTOR TEST NEEDED
 
TCR 02/28/2000 03/06/2000 IN-COMPLIANCE MEISSNER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes CLEARED ALL VIOLATIONS
 
TCI 12/28/1999 01/05/2000 MINOR OUT-OF-COMPLIANCE MEISSNER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes MONITORING WELLS AND LEAK TESTING IN JANUARY
 
TCI 03/31/1999 04/12/1999 IN-COMPLIANCE MEISSNER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes INVENTORY ON SIRS. MONITORING WELLS NEED TO BE CLOSED
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 08/08/2024 Satisfied STERLING_C Enforcement
 
Enforcement Referral 01/31/2024 Accepted ZIMMERMAN_RA_2 Enforcement
 
Electronic Communication 01/23/2024 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 01/12/2024 Satisfied ZIMMERMAN_RA_2 Component Installation
 
Electronic Communication 10/27/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 10/27/2023 Minor Out of Compliance ZIMMERMAN_RA_2 0/1 Routine Compliance
 
Letter 10/27/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 10/09/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 10/09/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 08/29/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 01/27/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 01/27/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Record Document 01/27/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 01/26/2023 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 09/27/2021 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 09/27/2021 Minor Out of Compliance ZIMMERMAN_RA_2 0/1 Routine Compliance
 
Phone Conversation 09/09/2021 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 07/22/2020 Satisfied COLLINS_MR Enforcement
 
Enforcement Tracking 07/22/2020 Closed Without Enforcement COLLINS_MR Enforcement
 
Electronic Communication 06/08/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Enforcement Referral 06/08/2020 Accepted ZIMMERMAN_RA_2 Enforcement
 
Record Document 09/05/2019 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 08/12/2019 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 08/12/2019 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 08/12/2019 Minor Out of Compliance ZIMMERMAN_RA_2 0/1 Routine Compliance
 
Phone Conversation 07/25/2019 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Record Document 12/26/2017 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Record Document 12/26/2017 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 12/26/2017 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 12/18/2017 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 11/17/2017 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 11/17/2017 Minor Out of Compliance ZIMMERMAN_RA_2 0/1 Routine Compliance
 
Electronic Communication 11/15/2017 Satisfied ZIMMERMAN_RA_2 Routine Compliance
 
Phone Conversation 11/13/2017 Satisfied ZIMMERMAN_RA_2 Routine Compliance
 
Site Inspection 10/08/2015 In Compliance GRAHAM_DL_1 0/1 Routine Compliance
 
Phone Conversation 09/18/2015 Satisfied GRAHAM_DL_1 Routine Compliance
 
Issue Document 05/14/2015 Satisfied GRAHAM_DL_1 Non-Compliance
 
Site Inspection 05/14/2015 In Compliance GRAHAM_DL_1 0/1 Non-Compliance
 
Phone Conversation 04/30/2015 Satisfied GRAHAM_DL_1 Non-Compliance
 
Phone Conversation 04/30/2015 Satisfied GRAHAM_DL_1 Non-Compliance
 
Letter 12/09/2014 Satisfied GRAHAM_DL_1 Non-Compliance
 
Meeting 12/09/2014 Satisfied GRAHAM_DL_1 Non-Compliance
 
Site Inspection 03/28/2014 Minor Out of Compliance GRAHAM_DL_1 0/1 Routine Compliance
 
Letter 03/28/2014 Satisfied GRAHAM_DL_1 Non-Compliance
 
Issue Document 01/30/2013 Satisfied LUBINSKI_D Non-Compliance
 
Phone Conversation 01/03/2013 Satisfied GRAHAM_DL_1 Non-Compliance
 
Site Inspection 12/19/2012 Major Out of Compliance GRAHAM_DL_1 0/1 Routine Compliance
 
Letter 12/19/2012 Satisfied GRAHAM_DL_1 Non-Compliance
 
Emergency Preparedness Information 12/19/2012 Satisfied GRAHAM_DL_1 Routine Compliance
 
Site Inspection 06/24/2011 In Compliance LUBINSKI_D 0/1 QA/QC
 
Site Inspection 03/11/2011 In Compliance GRAHAM_DL_1 0/1 Non-Compliance
 
Letter 02/03/2011 Satisfied GRAHAM_DL_1 Non-Compliance
 
Site Inspection 02/03/2011 Minor Out of Compliance GRAHAM_DL_1 0/1 Routine Compliance
 
Emergency Preparedness Information 02/03/2011 Satisfied GRAHAM_DL_1 Routine Compliance
 
Emergency Preparedness Information 11/13/2009 Satisfied GRAHAM_DL_1 Routine Compliance
 
Letter 11/13/2009 Satisfied GRAHAM_DL_1 Non-Compliance
 
Site Inspection 11/13/2009 Minor Out of Compliance GRAHAM_DL_1 0/1 Routine Compliance
 
Emergency Preparedness Information 07/16/2009 Satisfied GRAHAM_DL_1 Routine Compliance
 
Meeting 06/24/2009 Satisfied GRAHAM_DL_1 Routine Compliance
 
Letter 06/19/2009 Satisfied GRAHAM_DL_1 Closure
 
TCAR 06/19/2009 Satisfied GRAHAM_DL_1 Closure
 
Site Inspection 06/18/2009 In Compliance GRAHAM_DL_1 0/1 Installation
 
Record Document 03/23/2009 Satisfied GRAHAM_DL_1 Routine Compliance
 
Site Inspection 03/23/2009 In Compliance GRAHAM_DL_1 0/3 Closure
 
Letter 12/30/2008 Satisfied GRAHAM_DL_1 Non-Compliance
 
Meeting 12/30/2008 Satisfied GRAHAM_DL_1 Routine Compliance
 
Record Document 12/30/2008 Satisfied GRAHAM_DL_1 Routine Compliance
 
Site Inspection 11/21/2008 Major Out of Compliance GRAHAM_DL_1 0/3 Routine Compliance
 
Letter 11/21/2008 Satisfied GRAHAM_DL_1 Non-Compliance
 
Emergency Preparedness Information 11/21/2008 Satisfied GRAHAM_DL_1 Routine Compliance
 
Site Inspection 10/01/2007 In Compliance HUTCHERSON_P 0/3 Routine Compliance
 
Emergency Preparedness Information 09/18/2007 Satisfied HUTCHERSON_P Routine Compliance
 
Emergency Preparedness Information 05/23/2007 Satisfied HUTCHERSON_P Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied HUTCHERSON_P Routine Compliance
 
Letter 10/25/2006 Satisfied HUTCHERSON_P Non-Compliance
 
Site Inspection 10/02/2006 Major Out of Compliance HUTCHERSON_P 0/3 Routine Compliance
 
Emergency Preparedness Information 09/19/2006 Satisfied HUTCHERSON_P Routine Compliance
 
Phone Conversation 09/11/2006 Satisfied HUTCHERSON_P Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/27/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove liquid from Premium STP sump; email proof of violation resolution – work order/invoice and picture after liquid removal to ACEPD.
 
10/27/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have all of the spill buckets containment integrity evaluation tested and certified; email passing test certification to ACEPD.
 
10/27/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have all of the under dispenser containments and STP sumps containment integrity evaluation tested and certified; email passing test certification to ACEPD.
 
10/27/2023 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Have all of the overfill protection device ball check valves operability tested and certified; email passing test certification to ACEPD.
 
10/27/2023 6062 Minor 2.5 Release detection devices not tested annually. Have all of the line leak detectors operability tested and certified; email passing test certification to ACEPD.
 
10/27/2023 6062 Minor 2.5 Release detection devices not tested annually. Have the electronic release detection system operability tested and certified; email passing test certification to ACEPD.
 
 
 
No Discharges Found