DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District South   Type    Retail Station
 
County Collier   Status    OPEN
 
ID 8943963   Latitude    26° 9' 18.0143
 
Name SOUTHERN PETRO HOLDINGS
8901 DAVIS BLVD EXT E
Longitude    81° 41' 13.3351
  NAPLES, FL 34104 LL Method    DPHO
 
Contact Paola Serrano   LL Status    REVIEWED
 
Phone (941) 769-5519   Status Date    04/22/2003
 
Account Owner Information
 
Name SOUTHERN PETRO HOLDINGS LLC
1909 W ATLANTIC AVE
Delray Beach, FL 33444
Effective Date    05/23/2023
 
Contact PAOLA
 
Phone (954) 227-5948
 
Email PAOLA@UNITEDPETROMANAGEMENT.COM
  Placard # / Date    678257 - 06/05/2024
Property Owner Information
 
Name SOUTHERN PETRO HOLDINGS LLC
1909 W ATLANTIC AVE
Delray Beach, FL 33444
Effective Date    05/23/2023
 
Contact PAOLA
 
Phone (954) 227-5948
 
Email PAOLA@UNITEDPETROMANAGEMENT.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 10000 Unleaded Gas (B) 01/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
11 10000 Unleaded Gas (B) 01/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
12 10000 Unleaded Gas (B) 01/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
13 10000 Vehicular Diesel (D) 01/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 07/01/1978 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (C) Fiberglass (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 07/01/1978 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (C) Fiberglass (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 07/01/1978 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (C) Fiberglass (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 5000 Vehicular Diesel (D) 07/01/1978 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (C) Fiberglass (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
5 5000 Vehicular Diesel (D) 07/01/1978 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (C) Fiberglass (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
6 10000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
7 10000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
8 10000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
9 10000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   04/25/2020 04/25/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/18/2016 04/18/2017 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/08/2016 04/08/2016 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/07/2016 04/25/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/07/2016 04/25/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/09/2015 04/08/2016 ACE AMERICAN INSURANCE COMPANY
INSURANCE   04/08/2013 04/08/2014 AMERICAN SAFETY
INSURANCE   04/08/2011 04/08/2012 COMMERCE & INDUSTRY
INSURANCE   04/25/2010 04/25/2011 COMMERCE & INDUSTRY
INSURANCE   04/25/2009 04/25/2010 COMMERCE & INDUSTRY
INSURANCE   04/25/2008 04/25/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 01/10/2006 01/30/2006 SIGNIFICANT OUT-OF-COMPLIANCE OWEN_JA 4/0 COMPLIANCE ASSURANCE
 
 Completion Notes 4 VIOLATIONS. #1072-CLOSE MONITORING WELLS NOT IN USE, #1077, 1103 & 1117-TIGHTNESS TEST ON PIPING OVERDUE, MLLD ANNUAL TEST OVERDUE, VEEDER ROOT OPERABILITY ANNUAL TEST OVERDUE
 
CWOE 04/20/2005 04/21/2005 KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSED #1123
 
RRBD 04/20/2005 04/21/2005 KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes CP SURVEY PASSED ..CLOSE #1112
 
TCI 02/11/2005 02/17/2005 MINOR OUT-OF-COMPLIANCE KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes #1123: PROVIDE CP RECORDS
 
CWOE 04/13/2004 04/15/2004 KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes VERIFIED SHEAR VALVES ANCHORED ==>CLOSED #144 & PCW REMOVED FROM LINERS & SPILL CONTAINMENT ==> CLOSED #155
 
TCI 04/13/2004 04/15/2004 IN-COMPLIANCE KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: SW STEEL WITH CP
 
RRBD 09/09/2003 09/11/2003 KOLANDA 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes REC'D CP SURVEY
 
NCLI 04/16/2003 04/21/2003 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes TCI DATE 4/8/03
 
TCI 04/08/2003 04/08/2003 MINOR OUT-OF-COMPLIANCE HOGAN_S 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes CP SURVEY PAST DUE. REMOVE PCW FROM SPILL BUCKETS. REMOVE ABSORBENT PADS FROM DISPENSER #7/8. RE-ANCHOR SHEAR VALVE ON DISPENSER #7/8. PIPING IS SW STEEL WITH CP.
 
RRBD 11/03/2001 11/05/2001 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RRBD FROM COMPLIANCE SERVICES REPRESENTING AMOCO FOOD MART. CHARLOTTE MONITORING SYSTEMS TESTED THE CATHODIC PROTECTION ON THE TANKS AND PIPING. PASSED RESULTS. CLOSE VIOLATION.
 
NCLI 10/12/2001 10/18/2001 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NCLI FOR TCI DATED 10/12/01.
 
TCI 10/10/2001 10/12/2001 IN-COMPLIANCE HOGAN_S 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes CATHODIC PROTECTION NEEDS ANNUAL TEST. CSLD IS IN ALARM FOR TANK 1/TANK 2. FACILITY SHALL INVESTIGATE AND PROVIDE RESULTS WITHIN 14 DAYS. CSLD WAS INSTALLED IN JULY 2001.
 
DSNR 11/14/2000 12/04/2000 HOGAN_S 0/4 DISCHARGE PROJECT
 
 Completion Notes GASOLINE TANKS PASSED TESTS. LINES PASSED TESTS. LEAK DETECTORS PASSED.
 
DSNR 11/14/2000 12/01/2000 HOGAN_S 0/4 DISCHARGE PROJECT
 
 Completion Notes GASOLINE TANKS ARE TIGHT. LINES PASSED TEST. LEAK DETECTOR PASSED.
 
RRBD 11/14/2000 12/04/2000 HOGAN_S 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes RECIEVED TANK, LINE, AND LEAK DETECTOR TEST RESULTS.
 
RRBD 11/14/2000 12/04/2000 HOGAN_S 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes RECIEVED TANK, LINE, AND LEAK DETECTOR TEST RESULTS. ALL PASSED.
 
IRFR 10/19/2000 12/04/2000 HOGAN_S 0/4 DISCHARGE PROJECT
 
 Completion Notes FAULTY SENSOR ON ATG
 
IRFR 09/07/2000 12/01/2000 HOGAN_S 0/4 DISCHARGE PROJECT
 
 Completion Notes FAULTY SENSOR ON ATG
 
TCI 08/28/2000 08/30/2000 IN-COMPLIANCE SILLERY_W 0/4 COMPLIANCE ASSURANCE
 
TCI 09/10/1999 09/14/1999 IN-COMPLIANCE SILLERY_W 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Tracking 12/10/2024 Closed Without Enforcement COLLINS_TJ Enforcement
 
Enforcement Referral 11/06/2024 Accepted HERNANDEZ_N_5 Enforcement
 
Site Inspection 10/18/2024 Major Out of Compliance STANDIFORD_JA 0/4 Routine Compliance
 
Site Inspection 04/26/2024 Major Out of Compliance BATES_TD_1 0/4 Complaint
 
Electronic Communication 04/22/2024 Satisfied BATES_TD_1 Complaint
 
Electronic Communication 04/22/2024 Satisfied BATES_TD_1 Complaint
 
Site Inspection 08/09/2022 Major Out of Compliance HERNANDEZ_N_5 0/4 Routine Compliance
 
Electronic Communication 08/08/2022 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Enforcement Referral 03/18/2021 Accepted HERNANDEZ_N_5 Enforcement
 
Electronic Communication 01/05/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 12/08/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 11/23/2020 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Electronic Communication 11/06/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Letter 11/05/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Site Inspection 11/05/2020 Major Out of Compliance HERNANDEZ_N_5 0/4 Routine Compliance
 
Electronic Communication 11/02/2020 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Letter 06/15/2020 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 06/08/2020 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/30/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 08/16/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Record Document 08/07/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 08/07/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 07/31/2019 Satisfied BATES_TD_1 Routine Compliance
 
Electronic Communication 11/07/2018 Satisfied BATES_TD_1 Routine Compliance
 
Electronic Communication 11/07/2018 Satisfied BATES_TD_1 Routine Compliance
 
Electronic Communication 11/07/2018 Satisfied BATES_TD_1 Routine Compliance
 
Site Inspection 11/07/2018 Major Out of Compliance BATES_TD_1 0/4 Routine Compliance
 
Letter 11/07/2018 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 11/07/2018 Satisfied BATES_TD_1 Routine Compliance
 
Record Document 07/14/2017 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Record Document 07/10/2017 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Letter 06/23/2017 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Site Inspection 06/20/2017 Major Out of Compliance STANDIFORD_JA_2 0/4 Non-Compliance
 
Letter 06/14/2016 Satisfied GRIFFIN_N_1 Non-Compliance
 
Incident 05/24/2016 Has not led to Discharge STANDIFORD_JA_2 Incident
 
Site Inspection 05/23/2016 Minor Out of Compliance STANDIFORD_JA_2 0/4 Installation
 
Letter 04/12/2016 Satisfied STANDIFORD_JA_2 Non-Compliance
 
Site Inspection 04/11/2016 Major Out of Compliance STANDIFORD_JA_2 0/4 Routine Compliance
 
Document Management 04/11/2016 Complete STANDIFORD_JA_2 Incident
 
Site Inspection 04/08/2014 In Compliance SNYDERBURN_PJ_2 0/4 Routine Compliance
 
Emergency Preparedness Information 09/27/2013 Satisfied SNYDERBURN_PJ_2 Routine Compliance
 
Site Inspection 02/02/2012 In Compliance SNYDERBURN_PJ_2 0/4 Routine Compliance
 
Record Document 02/07/2011 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Letter 01/24/2011 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 01/24/2011 Minor Out of Compliance SNYDERBURN_PJ_2 0/4 Routine Compliance
 
Emergency Preparedness Information 01/14/2011 Satisfied SNYDERBURN_PJ_2 Routine Compliance
 
Letter 01/19/2010 Satisfied NOVAK_KM_1 Non-Compliance
 
TCAR 01/13/2010 Satisfied SNYDERBURN_PJ_2 Closure
 
Document Management 01/13/2010 Complete SNYDERBURN_PJ_2 Closure
 
Letter 01/13/2010 Satisfied SNYDERBURN_PJ_2 Closure
 
Site Inspection 01/12/2010 In Compliance SNYDERBURN_PJ_2 0/4 Installation
 
Emergency Preparedness Information 01/12/2010 Satisfied SNYDERBURN_PJ_2 Installation
 
Site Inspection 01/08/2010 In Compliance SNYDERBURN_PJ_2 0/4 Closure
 
Record Document 03/13/2009 Satisfied NOVAK_KM_1 Non-Compliance
 
Emergency Preparedness Information 01/16/2009 Satisfied NOVAK_KM_1 Routine Compliance
 
Site Inspection 01/16/2009 Major Out of Compliance NOVAK_KM_1 0/4 Routine Compliance
 
Record Document 02/04/2008 Satisfied POTTS_CR Non-Compliance
 
Letter 12/26/2007 Satisfied POTTS_CR Non-Compliance
 
Site Inspection 10/19/2007 Minor Out of Compliance POTTS_CR 0/4 Routine Compliance
 
Emergency Preparedness Information 10/19/2007 Satisfied POTTS_CR Routine Compliance
 
Letter 10/19/2007 Satisfied POTTS_CR Non-Compliance
 
Record Document 04/16/2007 Satisfied POTTS_CR Non-Compliance
 
Letter 03/27/2007 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 03/20/2007 Major Out of Compliance POTTS_CR 0/4 Routine Compliance
 
Emergency Preparedness Information 02/05/2007 Satisfied POTTS_CR Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied POTTS_CR Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/17/2024 6002 Minor 2.1 Operator Training records not available. Provide Class A,B, & C operator training records via email to FDEP South District Office.
 
10/16/2024 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Provide documentation via email to FDEP South District Office that states the DSL (L8) sensor was repaired/replaced, and re-tested.
 
08/08/2022 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Provide proof of financial responsibility.
 
08/08/2022 6066 Minor 4.4 Not repaired per applicable standards. Take care of the corrosion and send photos by email to the County inspector. Replace hoses and send photos by email to the County inspector.
 
08/08/2022 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Water in excess of one inch in depth, or any regulated substance collected in secondary containment, spill containment systems, or in piping sumps and dispenser sumps shall be removed within 72 hours of discovery and be either reused or properly disposed. Removed the liquid and send photos or manifests showing that the liquid was removed. Removed the water and send photos or manifest by email to the County inspector.
 
11/23/2020 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. Complete Part P and send it back by email to the County inspector.
 
11/02/2020 4072 Minor 4.7 Corrosion protection systems are not being operated and maintained to provide for continuous corrosion protection. Corrosion to metal components must be maintained to prevent discharges from structural failure. Prep, paint , and send pictures by email to the inspector.
 
11/02/2020 4078 Minor 2.6 Required records not available within 5 working days notice. All records, whether in paper or electronic format, shall be dated and available for inspection by the Department or county at time of inspection.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
11/30/1988   COMPLETED 30 EARLY DETECTION INCENTIVE-ELIGIBLE