Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 03/19/2025 Last Data Refresh: 03/18/2025 Report Generated from DOPPLER | |||||||
District | Southeast | Type | Agricultural | ||||
County | Indian River | Status | OPEN | ||||
ID | 8944195 | Latitude | 27° 38' 58.9196 | ||||
Name |
TWENTY MILE BEND GROVES LLC 22200 SR 60 |
Longitude | 80° 46' 38.2521 | ||||
VERO BEACH, FL 32966 | LL Method | DPHO | |||||
Contact | J KEVIN BYNUM | LL Status | REVIEWED | ||||
Phone | (561) 562-5030 | Status Date | 07/03/2003 | ||||
Account Owner Information | |||||||
Name | TWENTY MILE BEND GROVES LLC PO BOX 690877 VERO BEACH, FL 32969-877 |
Effective Date | 11/09/1998 | ||||
Contact | J KEVIN BYNUM | ||||||
Phone | (561) 562-5030 | ||||||
Placard # / Date | 641395 - 06/29/2022 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 1000 | Vehicular Diesel (D) | 01/01/1988 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact | (Q) Visual inspection of ASTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 1000 | Generator/Pump Diesel (H) | 01/01/1988 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact | (Q) Visual inspection of ASTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 1000 | Generator/Pump Diesel (H) | 01/01/1988 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact | (Q) Visual inspection of ASTs | |||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 07/19/2011 | 07/19/2012 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/19/2010 | 07/19/2011 | COMMERCE & INDUSTRY | ||||
INSURANCE | 05/10/2009 | 05/10/2010 | COMMERCE & INDUSTRY | ||||
INSURANCE | 05/10/2008 | 05/10/2009 | COMMERCE & INDUSTRY | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 06/08/2005 | 06/14/2005 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCR | 06/07/2004 | 06/09/2004 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCI | 06/07/2004 | 06/09/2004 | MINOR OUT-OF-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCI | 06/13/2003 | 06/18/2003 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCI | 05/31/2002 | 06/13/2002 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCI | 05/25/2001 | 06/07/2001 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
TCI | 06/23/2000 | 06/30/2000 | IN-COMPLIANCE | VOGT | 2/0 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Site Inspection | 06/21/2022 | Major Out of Compliance | GRANTHAM_JW_1 | 3/0 | Routine Compliance | ||
Letter | 06/21/2022 | Satisfied | GRANTHAM_JW_1 | Compliance Assistance | |||
Letter | 05/10/2019 | Satisfied | WEST_KE_1 | Compliance Assistance | |||
Electronic Communication | 05/10/2019 | Satisfied | WEST_KE_1 | Routine Compliance | |||
Site Inspection | 05/10/2019 | Major Out of Compliance | WEST_KE_1 | 3/0 | Routine Compliance | ||
Electronic Communication | 05/10/2019 | Satisfied | WEST_KE_1 | Routine Compliance | |||
Letter | 06/08/2016 | Satisfied | WEST_KE_1 | Non-Compliance | |||
Site Inspection | 06/08/2016 | Major Out of Compliance | WEST_KE_1 | 3/0 | Non-Compliance | ||
Electronic Communication | 04/28/2016 | Satisfied | WEST_KE_1 | Routine Compliance | |||
Site Inspection | 04/28/2016 | Minor Out of Compliance | WEST_KE_1 | 3/0 | Routine Compliance | ||
Letter | 04/28/2016 | Satisfied | WEST_KE_1 | Non-Compliance | |||
Electronic Communication | 04/28/2016 | Satisfied | WEST_KE_1 | Routine Compliance | |||
Site Inspection | 03/29/2012 | In Compliance | VOGT_CL_1 | 3/0 | Routine Compliance | ||
Site Inspection | 03/30/2011 | In Compliance | VOGT_CL_1 | 3/0 | Routine Compliance | ||
Site Inspection | 03/17/2010 | In Compliance | VOGT_CL_1 | 3/0 | Routine Compliance | ||
Site Inspection | 04/24/2009 | In Compliance | VOGT_CL_1 | 2/0 | Routine Compliance | ||
Site Inspection | 05/05/2008 | In Compliance | VOGT_CL_1 | 2/0 | Routine Compliance | ||
Site Inspection | 06/06/2007 | In Compliance | VOGT_CL_1 | 2/0 | Routine Compliance | ||
Site Inspection | 05/12/2006 | In Compliance | VOGT_CL_1 | 2/0 | Routine Compliance | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
06/06/2022 | 7001 | Minor | 1.1 No reasonable access provided. | Update contact information for future inspections. Provide a facility representative to access storage tanks and components. | |||
06/08/2016 | 2049 | SNC-B | 3.37 Piping not meeting referenced standards and/or approved per 762.851(2). | Install proper piping above ground or install FDEP approved double-wall underground piping. Provide proper notifications to this office prior to removal of existing underground piping and installation of new piping. Perform required testing pursuant to manufacturers recommendations. | |||
06/08/2016 | 2059 | Minor | 3.47 No valves meeting NFPA 30A standards required for piping systems with gravity head. | Ensure that there are proper valves installed per NFPA 30A on the piping at this facility. Provide documentation to this office that the valves have been installed. | |||
06/08/2016 | 2046 | SNC-B | 3.34 Not installed according to reference standards - NFPA 30, 30A, ASME B31.4 and manufacturer's instructions. | Provide proper emergency relief venting and normal venting for the storage tanks at this site, pursuant to NFPA 30. | |||
06/08/2016 | 2017 | SNC-B | 3.5 Secondary containment / liners does not meet standards. | Coat the concrete secondary containments with an FDEP Approved coating/liner. Use the FDEP Approved Equipment list to find a coating. Contact this office upon completion for follow up inspection. | |||
06/06/2016 | 2001 | Minor | 1.1 Systems not registered. | Register the fourth tank as in service or out of service. Alternatively, you may register the fourth tank as closed in place and it may not be used until such time the registration is changed. | |||
06/06/2016 | 2004 | SNC-B | 1.4 No financial responsibility | Immediately provide this office with proof of financial responsibility. | |||
06/06/2016 | 2133 | Minor | 1.14 Records requiring 2 year documentation period not kept by facility. | Provide this office with repair/maintenance as well as release detection records for the last two years for the fuel tanks at this facility. | |||
No Discharges Found |