DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Fuel user/Non-retail
 
County Osceola   Status    OPEN
 
ID 8944269   Latitude    28° 17' 57.2442
 
Name HCA Florida Osceola Hospital
700 W OAK ST
Longitude    81° 24' 31.1168
  KISSIMMEE, FL 34741-4938 LL Method    DPHO
 
Contact Johnathan Johnston   LL Status    REVIEWED
 
Phone (407) 518-3577   Status Date    08/18/2010
 
Account Owner Information
 
Name OSCEOLA REGIONAL MEDICAL CTR
700 W OAK ST
Kissimmee, FL 34741-8004
Effective Date    10/13/1998
 
Contact GREGG GARREN | JUAN GOMEZ
 
Phone (407) 908-8129
 
Email JUAN.GOMEZ@HCAHEALTHCARE.COM
  Placard # / Date    700058 - 07/24/2024
Property Owner Information
 
Name OSCEOLA REGIONAL MEDICAL CTR
700 W OAK ST
Kissimmee, FL 34741-8004
Effective Date    10/13/1998
 
Contact GREGG GARREN | JUAN GOMEZ
 
Phone (407) 908-8129
 
Email JUAN.GOMEZ@HCAHEALTHCARE.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 12000 Emerg Generator Diesel (G) 06/01/2012 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
 
 
Tank Tank Size Content Installed Placement Status
8 1000 Unleaded Gas (B) 06/01/2006 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(M) Spill containment bucket
(R) Double wall - tank jacket
(X) Concrete
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(2) Visual inspect pipe sumps
(R) Monitor tank bottom space
 
 
Tank Tank Size Content Installed Placement Status
9 8000 Emerg Generator Diesel (G) 05/01/2012 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
 
 
Tank Tank Size Content Installed Placement Status
1 550 Emerg Generator Diesel (G) 09/01/1984 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
2 1000 Emerg Generator Diesel (G) 10/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal (8) Manually sampled wells
(I) Not required
 
 
Tank Tank Size Content Installed Placement Status
3 2000 Emerg Generator Diesel (G) 10/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal (8) Manually sampled wells
(I) Not required
 
 
Tank Tank Size Content Installed Placement Status
4 8000 Emerg Generator Diesel (G) 09/01/1992 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(I) Suction piping system
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 2000 Emerg Generator Diesel (G) 06/01/1995 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
 
 
 
Tank Tank Size Content Installed Placement Status
6 12000 Emerg Generator Diesel (G) 09/01/1996 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
7 12000 Emerg Generator Diesel (G) 03/01/2004 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(F) Monitor dbl wall tank space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   09/01/2019 09/01/2023 ACE AMERICAN INSURANCE COMPANY
INSURANCE   09/01/2018 09/01/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   09/01/2013 09/01/2015 ACE
INSURANCE   09/01/2012 09/01/2013 ACE
INSURANCE   09/01/2011 09/01/2012 STEADFAST
INSURANCE   09/01/2009 09/01/2010 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 07/12/2005 07/17/2005 SIGNIFICANT OUT-OF-COMPLIANCE MARK GILL 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes REGISTRATION AND INSURANCE OK. VIOLATION OF 62-761.640(3)(D) ATG SYSTEM NOT IN TEST MODE EVERY 30 DAYS. VIOLATION OF 62-761.700(1)(C)3 NO ANNUAL LEAK DETECTOR TEST. VIOLATION OF 62-761.400 (3) TANK # 7 (8K) NOT LISTED ON INSURANCE.
 
TIN 08/05/2004 08/06/2004 IN-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes FACILITY APPEARS TO BE IN COMPLIANCE
 
TCI 07/06/2004 07/06/2004 IN-COMPLIANCE BILL BRADSHAW 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes FACILITY APPEARS TO BE IN COMPLIANCE
 
TCR 12/15/2003 12/15/2003 IN-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes THIS FACILITY NOW APPEARS TO BE IN COMPLIANCE
 
TCI 07/21/2003 07/21/2003 MINOR OUT-OF-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes FACILITY OUT OF COMPLIANCE
 
TCI 08/07/2002 08/07/2002 IN-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes THIS FACILITY APPEARS TO BE IN COMPLIANCE
 
TCI 08/22/2001 08/22/2001 IN-COMPLIANCE BILL BRADSHAW /4 COMPLIANCE ASSURANCE
 
 Completion Notes FACILITY IN COMPLIANCE
 
TCI 08/02/2000 08/02/2000 IN-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes IN COMPLIANCE
 
TCR 11/16/1999 11/16/1999 IN-COMPLIANCE BILL BRADSHAW 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes IN COMPLIANCE
 
NCLI 09/07/1999 09/08/1999 BILL BRADSHAW 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes CERTIFIED LETTER P510-398-792
 
TCI 08/30/1999 08/31/1999 MINOR OUT-OF-COMPLIANCE BRADSHAW_B 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes ATG INOPERATIVE DUE TO LIGHTNING STRIKE IN JULY, UNDER REPAIR. STP SUMP FILLED WITH WATER. LOG MONTHLY VISUAL INSPECTIONS.
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 02/11/2025 Satisfied KIDDER_MS_1 Component Closure
 
Electronic Communication 02/10/2025 Satisfied KIDDER_MS_1 Component Closure
 
Electronic Communication 02/04/2025 Satisfied KIDDER_MS_1 Component Closure
 
Enforcement Referral 11/07/2024 Accepted RIVERA_JX_2 Enforcement
 
Electronic Communication 07/08/2024 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 07/08/2024 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 04/11/2024 Satisfied KIDDER_MS_1 Closure
 
Electronic Communication 04/11/2024 Satisfied KIDDER_MS_1 Closure
 
Electronic Communication 03/28/2024 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 03/28/2024 Satisfied KIDDER_MS_1 Closure
 
Electronic Communication 03/27/2024 Satisfied KIDDER_MS_1 Installation
 
Electronic Communication 02/06/2024 Satisfied KIDDER_MS_1 Installation
 
Electronic Communication 09/28/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 09/28/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 09/21/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 09/21/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 08/22/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 08/17/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 08/08/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 07/17/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 07/17/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Site Inspection 05/01/2023 Minor Out of Compliance KIDDER_MS_1 1/2 Routine Compliance
 
Letter 05/01/2023 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 04/27/2023 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 04/27/2023 Satisfied KIDDER_MS_1 Routine Compliance
 
Incident 03/18/2022 Has not led to Discharge BOYLES_S Incident
 
Enforcement Tracking 03/18/2022 Closed Without Enforcement BOYLES_S Enforcement
 
Document Management 03/18/2022 Satisfied BOYLES_S Incident
 
Document Management 03/18/2022 Satisfied BOYLES_S Incident
 
Incident 03/18/2022 Has not led to Discharge BOYLES_S Incident
 
Letter 03/18/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/09/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/09/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/11/2022 Satisfied BOYLES_S Enforcement
 
Phone Conversation 02/09/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/04/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/04/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/04/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 02/04/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 01/26/2022 Satisfied SAVOY_JA_1 Routine Compliance
 
Electronic Communication 12/29/2021 Satisfied BOYLES_S Enforcement
 
Enforcement Referral 09/24/2018 Accepted RAUENZAHN_RA_1 Enforcement
 
Electronic Communication 09/18/2018 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 09/12/2018 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Letter 09/07/2018 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Site Inspection 07/23/2018 Major Out of Compliance BECKER_GT_1 1/2 Compliance Assistance
 
Letter 07/23/2018 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 07/18/2018 Satisfied BECKER_GT_1 Routine Compliance
 
Electronic Communication 07/17/2018 Satisfied BECKER_GT_1 Compliance Assistance
 
Letter 06/04/2018 Satisfied MOORHEAD_SB_1 Compliance Assistance
 
Site Inspection 06/04/2018 Major Out of Compliance MOORHEAD_SB_1 1/2 Routine Compliance
 
Electronic Communication 05/07/2018 Satisfied MOORHEAD_SB_1 Routine Compliance
 
Site Inspection 08/31/2015 In Compliance BOWERS_M_2 2/1 Routine Compliance
 
Phone Conversation 08/18/2015 Satisfied BOWERS_M_2 Routine Compliance
 
Site Inspection 08/21/2013 In Compliance BOWERS_M_2 1/2 Routine Compliance
 
Site Inspection 08/22/2012 In Compliance GATLIN_K 1/2 Installation
 
Site Inspection 06/18/2012 In Compliance COTTRELL_SA_1 0/1 Closure
 
Site Inspection 06/18/2012 In Compliance COTTRELL_SA_1 0/1 Installation
 
Site Inspection 05/29/2012 In Compliance COTTRELL_SA_1 0/1 Closure
 
Record Document 08/09/2011 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 08/05/2011 Minor Out of Compliance COTTRELL_SA_1 1/2 Routine Compliance
 
Site Inspection 06/29/2011 In Compliance GILL_MA_1 0/1 Closure
 
Discharge Reporting 06/28/2011 Satisfied GILL_MA_1 Discharge
 
Site Inspection 06/29/2010 In Compliance GILL_MA_1 1/2 Non-Compliance
 
Record Document 10/23/2009 Satisfied GILL_MA_1 Discharge
 
Record Document 10/06/2009 Satisfied GILL_MA_1 Non-Compliance
 
Site Inspection 09/23/2009 Minor Out of Compliance GILL_MA_1 1/2 Routine Compliance
 
Site Inspection 09/23/2009 In Compliance JOHNSON_CJ 2/0 QA/QC
 
Phone Conversation 09/15/2009 Satisfied GILL_MA_1 Routine Compliance
 
Site Inspection 09/10/2008 In Compliance COTTRELL_SA_1 1/2 Routine Compliance
 
Phone Conversation 09/02/2008 Satisfied COTTRELL_SA_1 Routine Compliance
 
Record Document 04/16/2008 Satisfied COTTRELL_SA_1 Non-Compliance
 
Record Document 03/19/2008 Satisfied COTTRELL_SA_1 Non-Compliance
 
Letter 03/12/2008 Satisfied COTTRELL_SA_1 Non-Compliance
 
Phone Conversation 03/12/2008 Satisfied COTTRELL_SA_1 Non-Compliance
 
Record Document 03/11/2008 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 02/26/2008 Minor Out of Compliance COTTRELL_SA_1 1/2 Routine Compliance
 
Issue Document 02/26/2008 Satisfied COTTRELL_SA_1 Routine Compliance
 
Phone Conversation 02/17/2008 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 06/30/2007 In Compliance GILL_MA_1 1/2 Routine Compliance
 
Phone Conversation 10/26/2006 Satisfied GILL_MA_1 Routine Compliance
 
Phone Conversation 10/25/2006 Satisfied GILL_MA_1 Routine Compliance
 
Site Inspection 06/14/2006 In Compliance GILL_MA_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/01/2023 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Please provide operability testing results for all overfill protection devices associated with the two USTs.
 
05/01/2023 6062 Minor 2.5 Release detection devices not tested annually. Please provide operability testing results for release detection devices associated with your two USTs.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
10/15/2009   COMPLETED 9