Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Fuel user/Non-retail | ||||||||
County | Osceola | Status | OPEN | ||||||||
ID | 8944269 | Latitude | 28° 17' 57.2442 | ||||||||
Name |
HCA Florida Osceola Hospital 700 W OAK ST |
Longitude | 81° 24' 31.1168 | ||||||||
KISSIMMEE, FL 34741-4938 | LL Method | DPHO | |||||||||
Contact | Johnathan Johnston | LL Status | REVIEWED | ||||||||
Phone | (407) 518-3577 | Status Date | 08/18/2010 | ||||||||
Account Owner Information | |||||||||||
Name | OSCEOLA REGIONAL MEDICAL CTR 700 W OAK ST Kissimmee, FL 34741-8004 |
Effective Date | 10/13/1998 | ||||||||
Contact | GREGG GARREN | JUAN GOMEZ | ||||||||||
Phone | (407) 908-8129 | ||||||||||
JUAN.GOMEZ@HCAHEALTHCARE.COM | |||||||||||
Placard # / Date | 700058 - 07/24/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | OSCEOLA REGIONAL MEDICAL CTR 700 W OAK ST Kissimmee, FL 34741-8004 |
Effective Date | 10/13/1998 | ||||||||
Contact | GREGG GARREN | JUAN GOMEZ | ||||||||||
Phone | (407) 908-8129 | ||||||||||
JUAN.GOMEZ@HCAHEALTHCARE.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 12000 | Emerg Generator Diesel (G) | 06/01/2012 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 1000 | Unleaded Gas (B) | 06/01/2006 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(M) Spill containment bucket (R) Double wall - tank jacket (X) Concrete |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(2) Visual inspect pipe sumps (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 8000 | Emerg Generator Diesel (G) | 05/01/2012 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 550 | Emerg Generator Diesel (G) | 09/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket (O) Tight fill |
(B) Steel/galvanized metal | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 1000 | Emerg Generator Diesel (G) | 10/01/1985 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (M) Spill containment bucket (O) Tight fill |
(B) Steel/galvanized metal | (8) Manually sampled wells (I) Not required |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 2000 | Emerg Generator Diesel (G) | 10/01/1985 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (M) Spill containment bucket (O) Tight fill |
(B) Steel/galvanized metal | (8) Manually sampled wells (I) Not required |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 8000 | Emerg Generator Diesel (G) | 09/01/1992 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (I) Suction piping system |
(F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 2000 | Emerg Generator Diesel (G) | 06/01/1995 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 12000 | Emerg Generator Diesel (G) | 09/01/1996 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall |
(F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 12000 | Emerg Generator Diesel (G) | 03/01/2004 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/01/2019 | 09/01/2023 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2018 | 09/01/2019 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 09/01/2013 | 09/01/2015 | ACE | ||||||||
INSURANCE | 09/01/2012 | 09/01/2013 | ACE | ||||||||
INSURANCE | 09/01/2011 | 09/01/2012 | STEADFAST | ||||||||
INSURANCE | 09/01/2009 | 09/01/2010 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 07/12/2005 | 07/17/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | MARK GILL | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes REGISTRATION AND INSURANCE OK. VIOLATION OF 62-761.640(3)(D) ATG SYSTEM NOT IN TEST MODE EVERY 30 DAYS. VIOLATION OF 62-761.700(1)(C)3 NO ANNUAL LEAK DETECTOR TEST. VIOLATION OF 62-761.400 (3) TANK # 7 (8K) NOT LISTED ON INSURANCE. | |||||||||||
TIN | 08/05/2004 | 08/06/2004 | IN-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes FACILITY APPEARS TO BE IN COMPLIANCE | |||||||||||
TCI | 07/06/2004 | 07/06/2004 | IN-COMPLIANCE | BILL BRADSHAW | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes FACILITY APPEARS TO BE IN COMPLIANCE | |||||||||||
TCR | 12/15/2003 | 12/15/2003 | IN-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes THIS FACILITY NOW APPEARS TO BE IN COMPLIANCE | |||||||||||
TCI | 07/21/2003 | 07/21/2003 | MINOR OUT-OF-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes FACILITY OUT OF COMPLIANCE | |||||||||||
TCI | 08/07/2002 | 08/07/2002 | IN-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes THIS FACILITY APPEARS TO BE IN COMPLIANCE | |||||||||||
TCI | 08/22/2001 | 08/22/2001 | IN-COMPLIANCE | BILL BRADSHAW | /4 | COMPLIANCE ASSURANCE | |||||
Completion Notes FACILITY IN COMPLIANCE | |||||||||||
TCI | 08/02/2000 | 08/02/2000 | IN-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes IN COMPLIANCE | |||||||||||
TCR | 11/16/1999 | 11/16/1999 | IN-COMPLIANCE | BILL BRADSHAW | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes IN COMPLIANCE | |||||||||||
NCLI | 09/07/1999 | 09/08/1999 | BILL BRADSHAW | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CERTIFIED LETTER P510-398-792 | |||||||||||
TCI | 08/30/1999 | 08/31/1999 | MINOR OUT-OF-COMPLIANCE | BRADSHAW_B | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes ATG INOPERATIVE DUE TO LIGHTNING STRIKE IN JULY, UNDER REPAIR. STP SUMP FILLED WITH WATER. LOG MONTHLY VISUAL INSPECTIONS. | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 02/11/2025 | Satisfied | KIDDER_MS_1 | Component Closure | |||||||
Electronic Communication | 02/10/2025 | Satisfied | KIDDER_MS_1 | Component Closure | |||||||
Electronic Communication | 02/04/2025 | Satisfied | KIDDER_MS_1 | Component Closure | |||||||
Enforcement Referral | 11/07/2024 | Accepted | RIVERA_JX_2 | Enforcement | |||||||
Electronic Communication | 07/08/2024 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 07/08/2024 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 04/11/2024 | Satisfied | KIDDER_MS_1 | Closure | |||||||
Electronic Communication | 04/11/2024 | Satisfied | KIDDER_MS_1 | Closure | |||||||
Electronic Communication | 03/28/2024 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 03/28/2024 | Satisfied | KIDDER_MS_1 | Closure | |||||||
Electronic Communication | 03/27/2024 | Satisfied | KIDDER_MS_1 | Installation | |||||||
Electronic Communication | 02/06/2024 | Satisfied | KIDDER_MS_1 | Installation | |||||||
Electronic Communication | 09/28/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 09/28/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 09/21/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 09/21/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 08/22/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 08/17/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 08/08/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 07/17/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 07/17/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Site Inspection | 05/01/2023 | Minor Out of Compliance | KIDDER_MS_1 | 1/2 | Routine Compliance | ||||||
Letter | 05/01/2023 | Satisfied | KIDDER_MS_1 | Compliance Assistance | |||||||
Electronic Communication | 04/27/2023 | Satisfied | KIDDER_MS_1 | Routine Compliance | |||||||
Electronic Communication | 04/27/2023 | Satisfied | KIDDER_MS_1 | Routine Compliance | |||||||
Incident | 03/18/2022 | Has not led to Discharge | BOYLES_S | Incident | |||||||
Enforcement Tracking | 03/18/2022 | Closed Without Enforcement | BOYLES_S | Enforcement | |||||||
Document Management | 03/18/2022 | Satisfied | BOYLES_S | Incident | |||||||
Document Management | 03/18/2022 | Satisfied | BOYLES_S | Incident | |||||||
Incident | 03/18/2022 | Has not led to Discharge | BOYLES_S | Incident | |||||||
Letter | 03/18/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 03/09/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 03/09/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 03/08/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 03/08/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 02/11/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Phone Conversation | 02/09/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 02/08/2022 | Satisfied | BOYLES_S | Enforcement | |||||||
Electronic Communication | 02/04/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 02/04/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 02/04/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 02/04/2022 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 01/26/2022 | Satisfied | SAVOY_JA_1 | Routine Compliance | |||||||
Electronic Communication | 12/29/2021 | Satisfied | BOYLES_S | Enforcement | |||||||
Enforcement Referral | 09/24/2018 | Accepted | RAUENZAHN_RA_1 | Enforcement | |||||||
Electronic Communication | 09/18/2018 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Electronic Communication | 09/12/2018 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Letter | 09/07/2018 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Site Inspection | 07/23/2018 | Major Out of Compliance | BECKER_GT_1 | 1/2 | Compliance Assistance | ||||||
Letter | 07/23/2018 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Electronic Communication | 07/18/2018 | Satisfied | BECKER_GT_1 | Routine Compliance | |||||||
Electronic Communication | 07/17/2018 | Satisfied | BECKER_GT_1 | Compliance Assistance | |||||||
Letter | 06/04/2018 | Satisfied | MOORHEAD_SB_1 | Compliance Assistance | |||||||
Site Inspection | 06/04/2018 | Major Out of Compliance | MOORHEAD_SB_1 | 1/2 | Routine Compliance | ||||||
Electronic Communication | 05/07/2018 | Satisfied | MOORHEAD_SB_1 | Routine Compliance | |||||||
Site Inspection | 08/31/2015 | In Compliance | BOWERS_M_2 | 2/1 | Routine Compliance | ||||||
Phone Conversation | 08/18/2015 | Satisfied | BOWERS_M_2 | Routine Compliance | |||||||
Site Inspection | 08/21/2013 | In Compliance | BOWERS_M_2 | 1/2 | Routine Compliance | ||||||
Site Inspection | 08/22/2012 | In Compliance | GATLIN_K | 1/2 | Installation | ||||||
Site Inspection | 06/18/2012 | In Compliance | COTTRELL_SA_1 | 0/1 | Closure | ||||||
Site Inspection | 06/18/2012 | In Compliance | COTTRELL_SA_1 | 0/1 | Installation | ||||||
Site Inspection | 05/29/2012 | In Compliance | COTTRELL_SA_1 | 0/1 | Closure | ||||||
Record Document | 08/09/2011 | Satisfied | COTTRELL_SA_1 | Non-Compliance | |||||||
Site Inspection | 08/05/2011 | Minor Out of Compliance | COTTRELL_SA_1 | 1/2 | Routine Compliance | ||||||
Site Inspection | 06/29/2011 | In Compliance | GILL_MA_1 | 0/1 | Closure | ||||||
Discharge Reporting | 06/28/2011 | Satisfied | GILL_MA_1 | Discharge | |||||||
Site Inspection | 06/29/2010 | In Compliance | GILL_MA_1 | 1/2 | Non-Compliance | ||||||
Record Document | 10/23/2009 | Satisfied | GILL_MA_1 | Discharge | |||||||
Record Document | 10/06/2009 | Satisfied | GILL_MA_1 | Non-Compliance | |||||||
Site Inspection | 09/23/2009 | Minor Out of Compliance | GILL_MA_1 | 1/2 | Routine Compliance | ||||||
Site Inspection | 09/23/2009 | In Compliance | JOHNSON_CJ | 2/0 | QA/QC | ||||||
Phone Conversation | 09/15/2009 | Satisfied | GILL_MA_1 | Routine Compliance | |||||||
Site Inspection | 09/10/2008 | In Compliance | COTTRELL_SA_1 | 1/2 | Routine Compliance | ||||||
Phone Conversation | 09/02/2008 | Satisfied | COTTRELL_SA_1 | Routine Compliance | |||||||
Record Document | 04/16/2008 | Satisfied | COTTRELL_SA_1 | Non-Compliance | |||||||
Record Document | 03/19/2008 | Satisfied | COTTRELL_SA_1 | Non-Compliance | |||||||
Letter | 03/12/2008 | Satisfied | COTTRELL_SA_1 | Non-Compliance | |||||||
Phone Conversation | 03/12/2008 | Satisfied | COTTRELL_SA_1 | Non-Compliance | |||||||
Record Document | 03/11/2008 | Satisfied | COTTRELL_SA_1 | Routine Compliance | |||||||
Site Inspection | 02/26/2008 | Minor Out of Compliance | COTTRELL_SA_1 | 1/2 | Routine Compliance | ||||||
Issue Document | 02/26/2008 | Satisfied | COTTRELL_SA_1 | Routine Compliance | |||||||
Phone Conversation | 02/17/2008 | Satisfied | COTTRELL_SA_1 | Routine Compliance | |||||||
Site Inspection | 06/30/2007 | In Compliance | GILL_MA_1 | 1/2 | Routine Compliance | ||||||
Phone Conversation | 10/26/2006 | Satisfied | GILL_MA_1 | Routine Compliance | |||||||
Phone Conversation | 10/25/2006 | Satisfied | GILL_MA_1 | Routine Compliance | |||||||
Site Inspection | 06/14/2006 | In Compliance | GILL_MA_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/01/2023 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Please provide operability testing results for all overfill protection devices associated with the two USTs. | |||||||
05/01/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Please provide operability testing results for release detection devices associated with your two USTs. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
10/15/2009 | COMPLETED | 9 | |||||||||