Report Run Date: 02/23/2025        Last Data Refresh: 02/22/2025        Report Generated from DOPPLER
 
District Southeast   Type    Retail Station
 
County Palm Beach   Status    OPEN
 
ID 8944329   Latitude    26° 43' 18.1109
 
Name MOBIL-COMMUNITY #718
3035 N MILITARY TRL
Longitude    80° 6' 40.2616
  WEST PALM BEACH, FL 33409-2730 LL Method    DPHO
 
Contact RICK HERWEH   LL Status    REVIEWED
 
Phone (813) 681-4279   Status Date    06/13/2003
 
Account Owner Information
 
Name AUTOMATED PETROLEUM & ENERGY CO INC (APEC)
PO BOX 1110
Brandon, FL 33509-1110
Effective Date    11/12/2013
 
Contact BILL MCKNIGHT | RICK HERWEH
 
Phone (813) 681-4279
 
Email RICK@APECGAS.COM
  Placard # / Date    692504 - 06/20/2024
Property Owner Information
 
Name AUTOMATED PETROLEUM & ENERGY CO INC (APEC)
PO BOX 1110
Brandon, FL 33509-1110
Effective Date    11/12/2013
 
Contact BILL MCKNIGHT | RICK HERWEH
 
Phone (813) 681-4279
 
Email RICK@APECGAS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
5 10000 Unleaded Gas (B) 05/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
6 10000 Unleaded Gas (B) 05/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
7 10000 Unleaded Gas (B) 05/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
8 10000 Vehicular Diesel (D) 05/01/2007 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 11/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 11/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(G) Electronic line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 11/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(G) Electronic line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
4 10000 Unleaded Gas (B) 11/01/1988 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(G) Electronic line leak detector
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
LETTER OF CREDIT   01/31/2023 01/31/2026
LETTER OF CREDIT   01/31/2022 01/31/2023
LETTER OF CREDIT   01/31/2021 01/31/2022
LETTER OF CREDIT   01/31/2020 01/31/2021
LETTER OF CREDIT   01/31/2019 01/31/2020
LETTER OF CREDIT   01/31/2018 01/31/2019
LETTER OF CREDIT   01/31/2017 01/31/2018
INSURANCE   01/01/2017 12/31/2017 NAUTILUS INSURANCE COMPANY
INSURANCE   12/31/2015 12/31/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2014 12/31/2015 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/30/2012 12/31/2012 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   04/30/2011 04/30/2012 ILLINOIS UNION
INSURANCE   04/30/2010 04/30/2011 ANCON INSURANCE CO INC
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/30/2009 04/30/2010
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 11/23/2005 12/02/2005 IN-COMPLIANCE ARLINE 0/4 COMPLIANCE ASSURANCE
 
TCI 03/08/2005 03/11/2005 IN-COMPLIANCE ARLINE 0/4 COMPLIANCE ASSURANCE
 
CALL 04/14/2004 05/10/2004 IN-COMPLIANCE WILLE 0/5 COMPLIANCE ASSURANCE
 
TCI 04/08/2004 05/03/2004 IN-COMPLIANCE MORRISON 0/4 COMPLIANCE ASSURANCE
 
TCR 10/21/2002 11/05/2002 SIGNIFICANT OUT-OF-COMPLIANCE MORRISON 0/4 COMPLIANCE ASSURANCE
 
TCI 07/22/2002 07/25/2002 SIGNIFICANT OUT-OF-COMPLIANCE MORRISON 0/4 COMPLIANCE ASSURANCE
 
TCPI 09/19/2001 09/21/2001 IN-COMPLIANCE GREEN 0/4 COMPLIANCE ASSURANCE
 
TCI 07/12/2001 07/23/2001 IN-COMPLIANCE MORRISON 0/4 COMPLIANCE ASSURANCE
 
TCI 07/12/2000 08/04/2000 IN-COMPLIANCE MORRISON 0/4 COMPLIANCE ASSURANCE
 
CRDE 10/19/1999 10/19/1999 WILLE 0/0 COMPLIANCE ASSURANCE
 
TCR 10/07/1999 10/13/1999 SIGNIFICANT OUT-OF-COMPLIANCE CAISSE 0/4 COMPLIANCE ASSURANCE
 
TCI 07/21/1999 07/28/1999 SIGNIFICANT OUT-OF-COMPLIANCE CAISSE 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 02/11/2025 Satisfied FIORITO_AM_1 Compliance Assistance
 
Site Inspection 02/10/2025 Major Out of Compliance FIORITO_AM_1 0/4 Routine Compliance
 
Enforcement Tracking 07/17/2024 Closed Without Enforcement DUSKY_RL_2 Enforcement
 
Electronic Communication 07/09/2024 Satisfied FIORITO_AM_1 Compliance Assistance
 
Letter 07/09/2024 Satisfied FIORITO_AM_1 Compliance Assistance
 
Electronic Communication 02/13/2024 Satisfied FIORITO_AM_1 Compliance Assistance
 
Electronic Communication 01/04/2024 Satisfied FIORITO_AM_1 Compliance Assistance
 
Enforcement Referral 04/14/2023 Accepted DUSKY_RL_2 Enforcement
 
Electronic Communication 02/27/2023 Satisfied FIORITO_AM_1 Compliance Assistance
 
Letter 01/17/2023 Satisfied ESAU_KL_1 Compliance Assistance
 
Site Inspection 01/12/2023 Major Out of Compliance LEVERETTE_VK_1 0/4 Routine Compliance
 
Letter 03/10/2021 Satisfied ESAU_KL_1 Compliance Assistance
 
Site Inspection 03/05/2021 In Compliance JENSEN_AS_2 0/4 Routine Compliance
 
Electronic Communication 02/26/2021 Satisfied JENSEN_AS_2 Routine Compliance
 
Letter 03/07/2019 Satisfied ESAU_KL_1 Compliance Assistance
 
Site Inspection 12/10/2018 In Compliance COFFIELD_LX_1 0/4 Routine Compliance
 
Electronic Communication 12/20/2017 Satisfied COFFIELD_LX_1 Compliance Assistance
 
Letter 06/07/2017 Satisfied COFFIELD_LX_1 Non-Compliance
 
Site Inspection 06/05/2017 Major Out of Compliance COFFIELD_LX_1 0/4 Routine Compliance
 
Site Inspection 04/11/2016 In Compliance ARLINE_JD_1 0/4 Non-Compliance
 
Phone Conversation 04/04/2016 Satisfied ARLINE_JD_1 Non-Compliance
 
Letter 03/26/2015 Satisfied VANATTA_JL_1 Non-Compliance
 
Site Inspection 03/20/2015 Minor Out of Compliance VANATTA_JL_1 0/4 Routine Compliance
 
Emergency Preparedness Information 11/30/2012 Satisfied ARLINE_JD_1 Routine Compliance
 
Site Inspection 11/30/2012 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
Document Management 11/30/2012 Complete ARLINE_JD_1 Non-Compliance
 
Site Inspection 09/19/2011 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
Emergency Preparedness Information 09/08/2011 Satisfied ARLINE_JD_1 Routine Compliance
 
Emergency Preparedness Information 08/31/2010 Satisfied ARLINE_JD_1 Routine Compliance
 
Site Inspection 08/31/2010 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
Site Inspection 10/09/2009 In Compliance ARLINE_JD_1 0/3 Routine Compliance
 
Site Inspection 08/04/2008 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
Site Inspection 10/04/2007 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
TCAR 08/15/2007 Satisfied WILLE_PC_1 Closure
 
Site Inspection 05/15/2007 In Compliance GREEN_WC_1 0/4 Installation
 
Site Inspection 04/12/2007 In Compliance ARLINE_JD_1 0/4 Closure
 
Site Inspection 03/05/2007 In Compliance ARLINE_JD_1 0/4 Routine Compliance
 
Emergency Preparedness Information 02/08/2007 Satisfied ARLINE_JD_1 Routine Compliance
 
Emergency Preparedness Information 09/28/2006 Satisfied ARLINE_JD_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/10/2025 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Please send current testing to Ainsley Fiorito AFiorito@pbc.gov for (single and double wall) spill bucket integrity, dispenser pan integrity, STP sump integrity, Veeder Root certification, overfill protection, and line leak detector.
 
02/10/2025 6066 Minor 4.4 Not repaired per applicable standards. Please clean, apply corrosion inhibitor, and send photos on repairs to Ainsley Fiorito AFiorito@pbc.gov.
 
02/10/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Please remove (Water, PCW, Product) from spill buckets (except premium unleaded) and all STP sumps (except Diesel) and send pictures to Ainsley Fiorito AFiorito@pbc.gov.
 
02/10/2025 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Investigate the cause, and send an Incident Notification Form within 14 days to Ainsley Fiorito AFiorito@pbc.gov.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
04/03/1992   COMPLETED 60 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE