Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Central | Type | Retail Station | ||||
County | Volusia | Status | OPEN | ||||
ID | 8944610 | Latitude | 28° 54' 9.0878 | ||||
Name |
CIRCLE K #2721263 1380 HOWLAND BLVD |
Longitude | 81° 10' 15.5369 | ||||
DELTONA, FL 32738-9765 | LL Method | DPHO | |||||
Contact | GRAHAM BIGGS | LL Status | REVIEWED | ||||
Phone | (919) 774-6700 | Status Date | 11/03/2003 | ||||
Account Owner Information | |||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 01/07/2016 | ||||
Contact | IRA LEWIS | ||||||
Phone | (423) 400-2480 | ||||||
ILEWIS@CIRCLEK.COM | |||||||
Placard # / Date | 697907 - 06/29/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
4 | 12000 | Unleaded Gas (B) | 11/01/2005 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
5 | 16000 | Unleaded Gas (B) | 11/01/2005 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (L) Compartmented (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 10000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (L) Automatic tank gauging - USTs (M) Manual tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 10000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (M) Manual tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 10000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (M) Manual tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 04/30/2023 | 08/28/2024 | |||||
INSURANCE | 12/01/2021 | 12/01/2022 | NAVIGATORS SPECIALTY INSURANCE CO | ||||
INSURANCE | 12/01/2020 | 12/01/2021 | NAVIGATORS SPECIALTY INSURANCE CO | ||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||
INSURANCE | 12/01/2018 | 12/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/09/2016 | 11/09/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2016 | 11/01/2017 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2015 | 11/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2014 | 11/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2013 | 11/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2012 | 11/01/2013 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2011 | 11/01/2012 | IRONSHORE SPECIALTY INSURANCE CO | ||||
INSURANCE | 11/01/2010 | 11/01/2011 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||
INSURANCE | 11/01/2009 | 11/01/2010 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||
INSURANCE | 11/01/2008 | 11/01/2009 | ENDURANCE AMERICAN SPECIALTY INS CO | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TIN | 03/08/2006 | 03/09/2006 | IN-COMPLIANCE | MOSER_T | 0/2 | COMPLIANCE ASSURANCE | |
Completion Notes FINAL INSPECTION/PASS. | |||||||
TCI | 11/28/2005 | 12/01/2005 | IN-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
Completion Notes FACILITY UNDER CONSTRUCTION. NO VIOLATIONS NOTED. | |||||||
TXI | 10/20/2005 | 10/27/2005 | IN-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
Completion Notes HIGH WATER TABLE MAKES FOR A CHALLENGING REMOVAL. SITE WILL BE RETANKED AND PIPED. | |||||||
SV | 10/14/2005 | 10/14/2005 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes MET W/ REP. FROM FUELING COMPONENTS RE: TANK CLOSURE. WATER TABLE @ 6". THE COMPANY WILL HAVE TO DISCHARGE OFF-SITE. TOLD HIM A PERMIT FROM FDEP IS REQUIRED. THEY ARE TO COORDINATE W/ CENTRAL DISTRICT. | |||||||
CWOE | 11/30/2004 | 01/03/2005 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes NFA CONCERNING THE LATEST TCI. | |||||||
RRBD | 11/30/2004 | 01/03/2005 | DJ | 0/3 | COMPLIANCE ASSURANCE | ||
Completion Notes RECEIVED DOCUMENTATION INDICATING THE RD DEVICE WAS TESTED AND PASSED. | |||||||
TCI | 11/16/2004 | 12/03/2004 | MINOR OUT-OF-COMPLIANCE | DJ | 0/3 | COMPLIANCE ASSURANCE | |
Completion Notes RD DEVICE REQUIRES ANNUAL TESTING. THE PREVIOUS VIOLATION CONCERNING WATER IN THE SUMPS WAS RESOLVED WITH THIS INSPECTION. | |||||||
TCI | 11/18/2003 | 11/26/2003 | MINOR OUT-OF-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
TCI | 11/19/2002 | 11/20/2002 | IN-COMPLIANCE | DJ | 0/3 | COMPLIANCE ASSURANCE | |
TCI | 11/28/2001 | 12/04/2001 | IN-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
TCI | 11/29/2000 | 12/01/2000 | IN-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
RRBD | 02/22/2000 | 02/22/2000 | MOSER_T | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 01/20/2000 | 02/02/2000 | MINOR OUT-OF-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |
TCI | 01/13/1999 | 03/25/1999 | IN-COMPLIANCE | VANDERBLEEK | 0/3 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Letter | 03/12/2025 | Satisfied | JONES_JEL | Enforcement | |||
Enforcement Referral | 06/11/2024 | Accepted | GREGORY_JW_1 | Enforcement | |||
Electronic Communication | 04/09/2024 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||
Electronic Communication | 03/12/2024 | Satisfied | GREGORY_JW_1 | Compliance Assistance | |||
Letter | 12/04/2023 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||
Site Inspection | 11/29/2023 | Minor Out of Compliance | PIERCE_BN_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 11/27/2023 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||
Letter | 12/29/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||
Electronic Communication | 04/12/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||
Incident | 12/02/2021 | Has not led to Discharge | PIERCE_BN_1 | Incident | |||
Letter | 12/02/2021 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||
Incident | 12/02/2021 | Has not led to Discharge | PIERCE_BN_1 | Incident | |||
Site Inspection | 12/02/2021 | Minor Out of Compliance | PIERCE_BN_1 | 0/2 | Routine Compliance | ||
Electronic Communication | 11/18/2021 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||
Document Management | 02/26/2021 | Satisfied | PIERCE_BN_1 | Incident | |||
Document Management | 02/26/2021 | Satisfied | PIERCE_BN_1 | Incident | |||
Electronic Communication | 11/17/2019 | Satisfied | PERRY_JF_2 | Routine Compliance | |||
Letter | 11/13/2019 | Satisfied | PERRY_JF_2 | Routine Compliance | |||
Site Inspection | 11/13/2019 | In Compliance | PERRY_JF_2 | 0/2 | Routine Compliance | ||
Site Inspection | 02/01/2017 | In Compliance | PERRY_JF_2 | 0/2 | Non-Compliance | ||
Letter | 01/20/2017 | Satisfied | PERRY_JF_2 | Non-Compliance | |||
Site Inspection | 01/20/2017 | Minor Out of Compliance | PERRY_JF_2 | 0/2 | Routine Compliance | ||
Site Inspection | 05/29/2015 | In Compliance | BECKER_GT_1 | 0/2 | Closure | ||
Site Inspection | 05/29/2015 | In Compliance | BECKER_GT_1 | 0/2 | Installation | ||
Site Inspection | 01/22/2015 | Minor Out of Compliance | PERRY_JF_2 | 0/2 | Routine Compliance | ||
Emergency Preparedness Information | 01/22/2015 | Satisfied | PERRY_JF_2 | Routine Compliance | |||
Letter | 01/22/2015 | Satisfied | PERRY_JF_2 | Non-Compliance | |||
Document Management | 08/26/2014 | Complete | RAUENZAHN_RA_1 | Closure | |||
Site Inspection | 07/25/2014 | In Compliance | BECKER_GT_1 | 0/2 | Installation | ||
Site Inspection | 07/25/2014 | In Compliance | BECKER_GT_1 | 0/2 | Closure | ||
Record Document | 07/21/2014 | Satisfied | BECKER_GT_1 | Closure | |||
Site Inspection | 04/24/2013 | In Compliance | PERRY_JF_2 | 0/2 | Routine Compliance | ||
Emergency Preparedness Information | 04/17/2013 | Satisfied | PERRY_JF_2 | Routine Compliance | |||
Site Inspection | 02/02/2012 | In Compliance | STAFFORD_P_1 | 0/2 | Routine Compliance | ||
Site Inspection | 01/13/2011 | In Compliance | COIL_JM_1 | 0/2 | Routine Compliance | ||
Site Inspection | 01/20/2010 | In Compliance | COIL_JM_1 | 0/2 | Routine Compliance | ||
Record Document | 02/17/2009 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||
Letter | 02/13/2009 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||
Site Inspection | 01/02/2009 | Minor Out of Compliance | COIL_JM_1 | 0/2 | Routine Compliance | ||
Record Document | 03/13/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||
Issue Document | 01/31/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||
Site Inspection | 01/14/2008 | Minor Out of Compliance | MOSER_T | 0/2 | Routine Compliance | ||
Emergency Preparedness Information | 02/14/2007 | Satisfied | LEIGH_MM_1 | Routine Compliance | |||
Site Inspection | 02/08/2007 | In Compliance | MOSER_T | 0/3 | Routine Compliance | ||
Emergency Preparedness Information | 09/19/2006 | Satisfied | MOSER_T | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
11/29/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Please have the PCW removed from the STP sumps & dispenser sumps. Please supply a manifest for disposal and pictures/work order showing the liquid was removed. | |||
11/29/2023 | 6029 | Minor | 4.1 Any component(s) of the storage tank system not installed according to manufacturer's instructions. | Please replace the DSL STP sump lid to allow for safer, more efficient monthly visual inspections. Please supply a picture for review once replaced. | |||
11/29/2023 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Please have the liquid removed from the secondary space of the spill bucket. Please have a vacuum test performed to ensure the integrity of the spill bucket is still intact. Please supply a work order & vacuum testing for review once complete. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
07/21/1993 | COMPLETED | ||||||