Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Retail Station | ||||||||
County | Gilchrist | Status | OPEN | ||||||||
ID | 8944788 | Latitude | 29° 35' 29.218 | ||||||||
Name |
STOP & GO #1 7560 N US HWY 19 |
Longitude | 82° 55' 58.5671 | ||||||||
FANNING SPRINGS, FL 32693 | LL Method | DPHO | |||||||||
Contact | S RAHMAN | LL Status | REVIEWED | ||||||||
Phone | (352) 463-0010 | Status Date | 02/05/2024 | ||||||||
Account Owner Information | |||||||||||
Name | STOP & GO 27764 SE HWY 19 OLD TOWN, FL 32680 |
Effective Date | 08/23/2007 | ||||||||
Contact | GOLAM KAWSAR | ||||||||||
Phone | (352) 870-7876 | ||||||||||
RAJU84@MSN.COM | |||||||||||
Placard # / Date | 644939 - 09/06/2022 | ||||||||||
Property Owner Information | |||||||||||
Name | STOP & GO 27764 SE HWY 19 OLD TOWN, FL 32680 |
Effective Date | 04/24/2009 | ||||||||
Contact | GOLAM KAWSAR | ||||||||||
Phone | (352) 870-7876 | ||||||||||
RAJU84@MSN.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 20000 | Unleaded Gas (B) | 02/01/2007 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 5000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (H) Mechanical line leak detector (L) Automatic tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 5000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (H) Mechanical line leak detector (L) Automatic tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 5000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (H) Mechanical line leak detector (L) Automatic tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 2000 | Unleaded Gas (B) | 07/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (I) Suction piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (L) Automatic tank gauging - USTs (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/13/2022 | 10/13/2023 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/13/2021 | 10/13/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/13/2020 | 10/13/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/07/2019 | 09/07/2020 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 09/07/2018 | 09/07/2019 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 09/07/2017 | 09/07/2018 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 05/07/2014 | 05/07/2015 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 04/09/2012 | 04/09/2013 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 04/09/2010 | 04/09/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 04/09/2010 | 04/09/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 04/09/2009 | 04/09/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 03/18/1999 | 03/18/2000 | UNITED CAPITOL | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 06/13/2005 | 06/13/2005 | SHEFFIELD_C | /4 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REC'D LETTER STATING INSPECTIONS WOULD BE WITHIN THE 35 DAY TIMEFRAME. ATG, LINE, AND LEAK DET TESTS PERFORMED BY CLEMEMS ON 6-7-05. ALSO REC'D CFR, RDRL AND S.T. REGISTRATION FORM. | |||||||||||
TCI | 03/24/2005 | 04/13/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes LEAK DETECTORS TESTED 6-14-04, TANK TEST DUE 4-17-06 | |||||||||||
TCI | 02/05/2004 | 03/12/2004 | IN-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes TANK, LINE AND LEAK DETECTORS TESTED 4-17-03 | |||||||||||
TCR | 07/23/2003 | 08/13/2003 | IN-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes INSTALLED ZIP BOOTS ON THE METAL PIPING AT STP AREAS. | |||||||||||
RRBD | 05/15/2003 | 06/18/2003 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REC'D RESULTS OF TANK TESTS, LINE TESTS, AND LEAK DETECTOR TESTS DONE ON 4-17-03 BY CLEMENS (ALL PASSED) | |||||||||||
NCLI | 05/12/2003 | 05/13/2003 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/17/2003 | 05/13/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes S/W FIBERGLASS CLAD STEEL,S/W FIBERGLASS PIPING, VIOLATION #76 IS A SNCB TO VERIFY PRESENCE OF CORROSION RESISTANCE AT STP AND UNDER DISPENSER. | |||||||||||
TCR | 05/06/2002 | 05/06/2002 | IN-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes FLAPPER INSTALLED | |||||||||||
RRBD | 02/22/2002 | 03/20/2002 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/11/2002 | 02/25/2002 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 01/23/2002 | 02/25/2002 | SIGNIFICANT OUT-OF-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
TCR | 06/12/2001 | 06/15/2001 | IN-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/15/2001 | 06/01/2001 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 05/07/2001 | 05/14/2001 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
RRBD | 04/12/2001 | 04/13/2001 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
NCLI | 03/15/2001 | 04/13/2001 | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/09/2001 | 03/16/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 02/10/2000 | 03/06/2000 | MINOR OUT-OF-COMPLIANCE | SHEFFIELD_C | 0/4 | COMPLIANCE ASSURANCE | |||||
RRBD | 03/18/1999 | 04/01/1999 | ASBELL_G | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 01/29/1999 | 03/11/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | ASBELL_G | 4/0 | COMPLIANCE ASSURANCE | |||||
UTCI | 10/10/1997 | 11/07/1997 | SIGNIFICANT OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 06/14/2023 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||||||
Letter | 06/14/2023 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Electronic Communication | 06/14/2023 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||||||
Site Inspection | 06/14/2023 | Major Out of Compliance | KEIM_MJ_1 | 0/1 | Routine Compliance | ||||||
Meeting | 02/02/2023 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Meeting | 02/02/2023 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Meeting | 02/02/2023 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Meeting | 02/01/2023 | Satisfied | KEIM_MJ_1 | Component Installation | |||||||
Meeting | 02/01/2023 | Satisfied | KEIM_MJ_1 | Component Installation | |||||||
Meeting | 02/01/2023 | Satisfied | KEIM_MJ_1 | Component Installation | |||||||
Record Document | 10/30/2022 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Record Document | 07/13/2021 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Phone Conversation | 09/20/2020 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||||||
Letter | 09/20/2020 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||||||
Site Inspection | 09/20/2020 | Major Out of Compliance | KEIM_MJ_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 09/20/2020 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||||||
Letter | 09/15/2017 | Satisfied | RAMSEY_TH_1 | Compliance Assistance | |||||||
Site Inspection | 09/15/2017 | Minor Out of Compliance | RAMSEY_TH_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 09/15/2017 | Satisfied | RAMSEY_TH_1 | Routine Compliance | |||||||
Phone Conversation | 08/31/2017 | Satisfied | RAMSEY_TH_1 | Routine Compliance | |||||||
Phone Conversation | 08/31/2017 | Satisfied | RAMSEY_TH_1 | Routine Compliance | |||||||
Electronic Communication | 08/31/2017 | Satisfied | RAMSEY_TH_1 | Routine Compliance | |||||||
Electronic Communication | 08/21/2017 | Satisfied | RAMSEY_TH_1 | Routine Compliance | |||||||
Meeting | 11/24/2015 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 04/08/2015 | In Compliance | SHULAW_BJ_1 | 0/1 | Non-Compliance | ||||||
Letter | 03/05/2015 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 09/07/2014 | Minor Out of Compliance | SHULAW_BJ_1 | 0/1 | Routine Compliance | ||||||
Letter | 09/07/2014 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Record Document | 11/30/2012 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Letter | 10/19/2012 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Site Inspection | 10/19/2012 | Minor Out of Compliance | KASSEES_RP_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 10/09/2012 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||||||
Site Inspection | 04/01/2011 | In Compliance | SHULAW_BJ_1 | 0/1 | Routine Compliance | ||||||
Record Document | 01/17/2011 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Letter | 08/30/2010 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 06/14/2010 | Major Out of Compliance | SHULAW_BJ_1 | 0/1 | Routine Compliance | ||||||
Letter | 06/14/2010 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 07/30/2009 | In Compliance | SHULAW_BJ_1 | 0/1 | Non-Compliance | ||||||
Letter | 05/18/2009 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 05/18/2009 | Major Out of Compliance | SHULAW_BJ_1 | 0/1 | Non-Compliance | ||||||
Site Inspection | 04/23/2009 | Major Out of Compliance | SHULAW_BJ_1 | 0/1 | Non-Compliance | ||||||
Letter | 04/23/2009 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Letter | 03/31/2009 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||||||
Site Inspection | 03/31/2009 | Major Out of Compliance | SHULAW_BJ_1 | 0/1 | Routine Compliance | ||||||
TCAR | 07/11/2008 | Satisfied | KASSEES_RP_1 | Closure | |||||||
Site Inspection | 07/11/2008 | In Compliance | KASSEES_RP_1 | 0/1 | Non-Compliance | ||||||
Issue Document | 04/30/2008 | Satisfied | KASSEES_RP_1 | Closure | |||||||
Letter | 04/17/2008 | Satisfied | OYMAYAN_AJ_1 | Non-Compliance | |||||||
Site Inspection | 04/17/2008 | Major Out of Compliance | OYMAYAN_AJ_1 | 0/1 | Non-Compliance | ||||||
Letter | 02/13/2008 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Site Inspection | 02/13/2008 | Major Out of Compliance | KASSEES_RP_1 | 0/1 | Non-Compliance | ||||||
Site Inspection | 11/14/2007 | Major Out of Compliance | KASSEES_RP_1 | 0/1 | Routine Compliance | ||||||
Letter | 11/14/2007 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 11/06/2007 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||||||
Letter | 07/15/2007 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Letter | 07/15/2007 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Site Inspection | 07/15/2007 | In Compliance | KASSEES_RP_1 | 0/4 | Non-Compliance | ||||||
Letter | 07/13/2007 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 05/23/2007 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||||||
Site Inspection | 03/16/2007 | Minor Out of Compliance | KASSEES_RP_1 | 0/4 | Closure | ||||||
Site Inspection | 03/16/2007 | In Compliance | KASSEES_RP_1 | 0/1 | Installation | ||||||
Emergency Preparedness Information | 02/16/2007 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||||||
Site Inspection | 11/25/2006 | In Compliance | KASSEES_RP_1 | 0/4 | Non-Compliance | ||||||
Emergency Preparedness Information | 09/29/2006 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||||||
Site Inspection | 09/12/2006 | Major Out of Compliance | KASSEES_RP_1 | 0/4 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
06/13/2023 | 6001 | Minor | 2.1 No reasonable access provided. | Contact the inspector or FDEP enforcement to schedule an inspection. | |||||||
09/20/2020 | 4059 | SNC-B | 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. | Provide the monthly visual inspections from 10-17-2017 until current to the inspector to address this violation. | |||||||
09/20/2020 | 4081 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Obtain the training certificates and forward them to the inspector to address this violation. | |||||||
09/20/2020 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | Complete incident notification form provided with this report to the inspector to address this violation. | |||||||
09/20/2020 | 4068 | Minor | 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. | Complete the incident notification form provided and have the entry boots repaired. Forward the results of the investigation to the inspector and repairs to the inspector to address the violation. | |||||||
No Discharges Found |