DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Marine/Coastal Fuel Storage
 
County Volusia   Status    OPEN
 
ID 8944989   Latitude    29° 4' 45.9254
 
Name OCEAN SUPPORT INC
4950 S PENINSULA DR
Longitude    80° 55' 40.7436
  DAYTONA BEACH, FL 32127-7312 LL Method    DPHO
 
Contact JOHN HINTON   LL Status    REVIEWED
 
Phone (386) 547-4019   Status Date    11/03/2003
 
Account Owner Information
 
Name OCEAN SUPPORT INC
4950 S PENINSULA DR
DAYTONA BEACH, FL 32127-7312
Effective Date    10/02/1989
 
Contact JOHN T HINTON JR
 
Phone (386) 547-4019
 
Email DEERMEAT308@GMAIL.COM
  Placard # / Date    646606 - 11/17/2022
Property Owner Information
 
Name OCEAN SUPPORT INC
4950 S PENINSULA DR
DAYTONA BEACH, FL 32127-7312
Effective Date    11/20/2021
 
Contact JOHN T HINTON JR
 
Phone (386) 547-4019
 
Email DEERMEAT308@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 3000 Vehicular Diesel (D) 04/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 3000 Gasohol (C) 04/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Vehicular Diesel (D) 10/01/1990 UNDERGROUND Out of Service (T)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   08/26/2022 08/26/2023 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   08/26/2021 08/26/2022 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   08/16/2020 08/16/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   08/16/2019 08/16/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   08/16/2018 08/16/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   08/16/2017 08/16/2018 COMMERCE & INDUSTRY
INSURANCE   08/16/2016 08/16/2017 COMMERCE & INDUSTRY
INSURANCE   08/16/2015 08/16/2016 COMMERCE & INDUSTRY
INSURANCE   08/16/2013 08/16/2014 COMMERCE & INDUSTRY
INSURANCE   08/16/2011 08/16/2012 COMMERCE & INDUSTRY
INSURANCE   08/16/2010 08/16/2011 COMMERCE & INDUSTRY
INSURANCE   07/16/2009 08/16/2010 COMMERCE & INDUSTRY
INSURANCE   08/16/2008 08/16/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 02/20/2006 02/20/2006 MML 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes INFORMATION RECEIVED, DPRC ISSUED
 
TCI 12/20/2005 12/21/2005 IN-COMPLIANCE DJ 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes THE FACILITY IS IN COMPLIANCE W/ LATEST TCI HOWEVER THE DPRI INSPECTION IS NOT IN COMPLIANCE BECAUSE NO DCP IS AVAILABLE.
 
DPRI 12/20/2005 12/21/2005 DJ 0/1 TERMINAL FACILITY PROJECT
 
 Completion Notes DCP WAS NOT AVAILABLE. OWNER WILL CONTRACT AFTER FIRST OF YEAR WITH THIRD PARTY CONTRACTOR FOR CLEANUP.
 
RRBD 06/27/2005 06/27/2005 EJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes STORM WATER WAS REMOVED, REC'D 2 MOS OF LD MONITORING. PT JUST STARTED DOING THIS FOR THEM. VEEDED ROOT WAS REMOVED. METHOD OF LEAK DETECTION NOW IS MANUAL INTERSTITIAL OF TANK.
 
CALL 06/24/2005 06/27/2005 EJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes POLLY CALLED. JERRY @ PETRO TECH SAID THIS WAS ALREADY SENT. HE WILL RESEND.
 
CALL 06/23/2005 06/27/2005 EJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes CALLED POLLY-OTHER 2 NC ITEMS HAVE BEEN DONE. HAVE PETRO TECH SEND PAPERWORK.
 
RRBD 06/14/2005 06/27/2005 EJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes REC'D RESULTS OF LINE LEAK DETECTOR TEST.
 
WLI 05/31/2005 06/03/2005 DJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO FURTHER RESPONSE.
 
CALL 04/15/2005 04/15/2005 EJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes PETRO TECH WILL TAKE CARE OF N/C ON MON.
 
NCLI 04/11/2005 04/12/2005 DJ 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO RESPONSE FROM FACILITY.
 
DPRI 12/13/2004 01/03/2005 MINOR OUT-OF-COMPLIANCE DJ 0/1 TERMINAL FACILITY PROJECT
 
 Completion Notes LD REQUIRES ANNUAL TESTING. RD DEVICE REQUIRES ANNUALTESTING. DISPENSERS CONTAIN STORMWATER.
 
TCI 12/13/2004 01/03/2005 MINOR OUT-OF-COMPLIANCE DJ 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes LD REQUIRES ANNUAL TESTING. RELEASE DET. DEVICE REQUIRES ANNUAL TESTING. ALL DISPENSERS CONTAIN STORMWATER.
 
TCR 03/08/2004 04/13/2004 IN-COMPLIANCE MOSER_T 0/1 COMPLIANCE ASSURANCE
 
TCI 12/16/2003 01/06/2004 SIGNIFICANT OUT-OF-COMPLIANCE MOSER_T 0/1 COMPLIANCE ASSURANCE
 
DPRI 12/16/2003 01/07/2004 IN-COMPLIANCE MOSER_T 0/1 TERMINAL FACILITY PROJECT
 
TCR 02/06/2003 02/21/2003 IN-COMPLIANCE TM 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes FILL BOX HAS BEEN PROPERLY MARKED. PRODUCT HAS BEEN REMOVED FROM THE STP SUMP.
 
TCI 12/02/2002 12/17/2002 MINOR OUT-OF-COMPLIANCE MOSER_T 0/1 COMPLIANCE ASSURANCE
 
DPRI 12/02/2002 12/12/2002 IN-COMPLIANCE MOSER_T 0/1 TERMINAL FACILITY PROJECT
 
DPRI 12/14/2001 12/21/2001 IN-COMPLIANCE TERRY MOSER 0/0 TERMINAL FACILITY PROJECT
 
TCI 08/08/2001 09/05/2001 IN-COMPLIANCE MOSER_T 0/1 COMPLIANCE ASSURANCE
 
LTR 01/30/2001 02/01/2001 COTTRELL_S 0/0 TERMINAL FACILITY PROJECT
 
 Completion Notes CERTIFICATE # 98651
 
DPRR 01/30/2001 01/30/2001 IN-COMPLIANCE COTTRELL_S 0/0 TERMINAL FACILITY PROJECT
 
 Completion Notes CERTIFICATE #
 
NCLI 12/28/2000 01/02/2001 COTTRELL_S 0/0 TERMINAL FACILITY PROJECT
 
 Completion Notes CURRENT SPILL CONTRACT NOT AVAILABLE
 
DPRI 12/27/2000 12/28/2000 COTTRELL_S 0/0 TERMINAL FACILITY PROJECT
 
TCR 08/10/2000 08/11/2000 IN-COMPLIANCE LLW 0/1 COMPLIANCE ASSURANCE
 
TCI 08/03/2000 08/04/2000 MINOR OUT-OF-COMPLIANCE LLW 0/1 COMPLIANCE ASSURANCE
 
DPRI 12/27/1999 01/11/2000 COTTRELL_S 0/0 TERMINAL FACILITY PROJECT
 
 Completion Notes CERTIF. # 98614
 
TCI 08/24/1999 08/30/1999 IN-COMPLIANCE VANDERBLEE_R 0/1 COMPLIANCE ASSURANCE
 
TIN 04/21/1999 04/29/1999 IN-COMPLIANCE VANDERBLEE_R 0/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 03/06/2025 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 02/28/2025 Satisfied PIERCE_BN_1 Compliance Assistance
 
Phone Conversation 02/28/2025 Satisfied PIERCE_BN_1 Compliance Assistance
 
Enforcement Referral 08/29/2024 Accepted RIVERA_JX_2 Enforcement
 
Electronic Communication 11/08/2023 Satisfied KIDDER_MS_1 Installation
 
Phone Conversation 08/03/2023 Satisfied KIDDER_MS_1 Installation
 
Phone Conversation 07/17/2023 Satisfied KIDDER_MS_1 Installation
 
Electronic Communication 07/14/2023 Satisfied BECKER_GT_1 Closure
 
Electronic Communication 07/14/2023 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 07/14/2023 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/09/2023 Satisfied PIERCE_BN_1 Component Closure
 
Letter 06/08/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 06/07/2023 Satisfied PIERCE_BN_1 Component Closure
 
Electronic Communication 06/07/2023 Satisfied PIERCE_BN_1 Routine Compliance
 
Electronic Communication 06/07/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Document Management 06/07/2023 Satisfied PIERCE_BN_1 Closure
 
Record Document 06/07/2023 Satisfied PIERCE_BN_1 Component Closure
 
Site Inspection 05/31/2023 Minor Out of Compliance PIERCE_BN_1 0/1 Routine Compliance
 
Electronic Communication 05/23/2023 Satisfied BECKER_GT_1 Component Installation
 
Electronic Communication 09/21/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Letter 07/14/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 01/14/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 01/14/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Phone Conversation 01/12/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Phone Conversation 01/11/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 01/10/2022 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 11/09/2021 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 08/16/2021 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 03/04/2021 Satisfied PIERCE_BN_1 Compliance Assistance
 
Letter 09/15/2020 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 09/14/2020 Minor Out of Compliance PIERCE_BN_1 0/1 Routine Compliance
 
Electronic Communication 09/11/2020 Satisfied PIERCE_BN_1 Routine Compliance
 
Letter 04/29/2018 Satisfied PERRY_JF_2 Routine Compliance
 
Site Inspection 04/29/2018 In Compliance PERRY_JF_2 0/1 Routine Compliance
 
Meeting 01/25/2017 Satisfied JOHNSON_CJ Routine Compliance
 
Meeting 01/25/2017 Satisfied JOHNSON_CJ Routine Compliance
 
Site Inspection 04/06/2016 In Compliance PERRY_JF_2 0/1 Routine Compliance
 
Emergency Preparedness Information 09/01/2013 Satisfied PERRY_JF_2 Routine Compliance
 
Site Inspection 09/01/2013 In Compliance PERRY_JF_2 0/1 Routine Compliance
 
Meeting 08/26/2013 Satisfied JOHNSON_CJ Routine Compliance
 
Site Inspection 03/29/2012 In Compliance JOHNSON_CJ 0/1 QA/QC
 
Site Inspection 03/29/2012 In Compliance CRAFT_TT_1 0/1 Routine Compliance
 
Site Inspection 01/28/2011 In Compliance CRAFT_TT_1 0/1 Routine Compliance
 
Site Inspection 01/26/2011 In Compliance JOHNSON_CJ 0/1 QA/QC
 
Record Document 12/03/2010 Satisfied STAFFORD_P_1 Non-Compliance
 
Letter 11/18/2010 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 05/25/2010 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 04/08/2010 Minor Out of Compliance COIL_JM_1 0/1 Routine Compliance
 
Letter 04/08/2010 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 04/06/2010 In Compliance JOHNSON_CJ 0/1 QA/QC
 
Site Inspection 02/05/2009 In Compliance JOHNSON_CJ 0/1 QA/QC
 
Site Inspection 01/23/2009 In Compliance COIL_JM_1 0/1 Routine Compliance
 
Site Inspection 01/29/2008 In Compliance JOHNSON_CJ 0/3 QA/QC
 
Record Document 12/20/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 12/17/2007 Minor Out of Compliance SHIELDS_DJ 0/1 Routine Compliance
 
Record Document 05/10/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 05/10/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Phone Conversation 04/04/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 04/04/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 01/29/2007 Warning Letter Issued LEIGH_MM_1 Non-Compliance
 
Site Inspection 12/11/2006 Minor Out of Compliance SHIELDS_DJ 0/1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/31/2023 6002 Minor 2.1 Operator Training records not available. *If tank will be left in service: Please have applicable representatives complete operator A/B & C training. Please use the following link to access approved operator training for Florida: https://floridadep.gov/waste/permitting-compliance-assistance/content/underground-storage-tank-operator-training *If tank will be taken out of service: please complete all applicable out of service requirements to close this violation.
 
05/31/2023 6062 Minor 2.5 Release detection devices not tested annually. *If tank will be left in service: Please arrange for testing to be completed. Please supply testing for review. *If tank will be taken out of service: please complete all applicable out of service requirements to close this violation.
 
05/31/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. *If tank will be left in service: Please arrange for testing to be completed. Please supply testing for review. *If tank will be taken out of service: please complete all applicable out of service requirements to close this violation.
 
05/31/2023 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. *If tank will be left in service: Please arrange for testing to be completed. Please supply testing for review. *If tank will be taken out of service: please complete all applicable out of service requirements to close this violation.
 
 
 
No Discharges Found