Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 8945035 | Latitude | 28° 2' 55.1242 | ||||||||
Name |
BP #610 TWIN BROTHERS FOOD MART 2433 LUCERNE PARK RD |
Longitude | 81° 43' 25.2366 | ||||||||
WINTER HAVEN, FL 33881-1665 | LL Method | DPHO | |||||||||
Contact | SUBHADRUBEN PATEL | LL Status | REVIEWED | ||||||||
Phone | (863) 297-9248 | Status Date | 06/28/2021 | ||||||||
Account Owner Information | |||||||||||
Name | PATEL, PRAVIN & SUBHADRABEN 2433 LUCERNE PARK RD WINTER HAVEN, FL 33881-1665 |
Effective Date | 03/11/2008 | ||||||||
Contact | SUSI PATEL OR NISHAN PATEL | ||||||||||
Phone | (863) 297-9248 | ||||||||||
NISHAN2MITTAL@YAHOO.COM | |||||||||||
Placard # / Date | 690965 - 06/19/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | PATEL, PRAVIN & SUBHADRABEN 2433 LUCERNE PARK RD WINTER HAVEN, FL 33881-1665 |
Effective Date | 03/11/2008 | ||||||||
Contact | SUSI PATEL OR NISHAN PATEL | ||||||||||
Phone | (863) 297-9248 | ||||||||||
NISHAN2MITTAL@YAHOO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 20000 | Vehicular Diesel (D) | 12/01/2007 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Unleaded Gas (B) | 05/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 4000 | Unleaded Gas (B) | 05/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Unleaded Gas (B) | 05/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/08/2023 | 02/08/2025 | CRUM & FORSTER SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 02/08/2019 | 02/08/2021 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 02/08/2017 | 02/08/2019 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 02/08/2015 | 02/08/2017 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 02/08/2013 | 02/08/2015 | AMERICAN SAFETY | ||||||||
INSURANCE | 02/08/2013 | 02/08/2015 | AMERICAN SAFETY | ||||||||
INSURANCE | 02/11/2011 | 02/11/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/11/2010 | 02/11/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/11/2008 | 02/11/2010 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
DRFR | 05/03/2006 | 05/03/2006 | CASSELS_CR | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes GALLONS: UNK; AFFECTED: GW; METH OF DISC: CLOSR ASSESS ANALYTICALS; TYPE OF SUBSTANCE: GASOLINE; CAUSE: UNK | |||||||||||
IRFR | 04/20/2006 | 04/25/2006 | CROWELL_M | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes DISCOVERY: 06/06/05. MONITORING: SIR. SUBSTANCE: GASOLINE. TIGHTNESS TEST TO BE SCHEDULED. | |||||||||||
IRFR | 04/20/2006 | 04/25/2006 | CROWELL_M | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes DISCOVERY: 4/5/05. MONITORING: SIR. SUBSTANCE: GASOLINE. TIGHTNESS TEST TO BE SCHEDULED. | |||||||||||
RRBD | 04/20/2006 | 04/25/2006 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED INF, RESOLVES VIOLATION #1010 & 1138. | |||||||||||
LTR | 04/03/2006 | 04/03/2006 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NCLI FOLLOW UP LETTER. | |||||||||||
NCLI | 03/07/2006 | 03/10/2006 | CROWELL_M | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: INF, SIR REPORT, RELEASE DETECTION RESPONSE LEVEL STATEMENT AND TESTING RESULTS, CATHODIC PROTECTION SYSTEM TEST. RESOLVES VIOLATION #1122. | |||||||||||
TXIF | 02/28/2006 | 03/10/2006 | IN-COMPLIANCE | SLAPPEY_W | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes TWO PHOTOS. CLOSED: 3 - 4000 GALLON SINGLE WALL STEEL FIBERGLASS CLAD TANKS, APPROX 40 FT SINGLE WALL FIBERGLASS PIPING. | |||||||||||
TCI | 02/23/2006 | 03/10/2006 | MINOR OUT-OF-COMPLIANCE | CROWELL_M | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes TWO PHOTOS. PIPING: FACILITY FILE RECORD SHOWS SINGLE WALLED RIGID FIBERGLASS PIPING WITH CATHODIC PROTECTION ON THE SWING JOINTS. | |||||||||||
RRBD | 05/25/2005 | 06/01/2005 | NEWBERG_D | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes RECEIVED TANK TEST, RESOLVES 4/22/05 INF. NO DISCHARGE. | |||||||||||
RRBD | 05/25/2005 | 05/27/2005 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #1010. | |||||||||||
IRFR | 05/19/2005 | 05/27/2005 | NEWBERG_D | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes DISCOVERY: UNKNOWN. TANK TEST. | |||||||||||
NCLI | 04/22/2005 | 05/12/2005 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: INF AND INVESTIGATION. | |||||||||||
TCI | 04/22/2005 | 05/12/2005 | MINOR OUT-OF-COMPLIANCE | NEWBERG_D | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND RIGID SINGLE-WALLED FIBERGLASS. | |||||||||||
TCI | 03/24/2004 | 04/08/2004 | IN-COMPLIANCE | SACLARIDES_M | 3/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. UNDERGROUND PIPING IS RIGID SINGLE-WALLED FIBERGLASS. RESOLVES VIOLATION #144. | |||||||||||
RRBD | 07/01/2003 | 07/03/2003 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #170 & 171. | |||||||||||
RRBD | 06/30/2003 | 07/03/2003 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #86. | |||||||||||
RRBD | 05/21/2003 | 06/18/2003 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #150. | |||||||||||
NCLI | 04/24/2003 | 04/25/2003 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/03/2003 | 04/25/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes 3 PHOTOS TAKEN. RESOLVES VIOLATION #155. | |||||||||||
NCLI | 05/01/2002 | 05/03/2002 | HAUSCHILD_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/22/2002 | 05/03/2002 | MINOR OUT-OF-COMPLIANCE | HAUSCHILD_T | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/10/2001 | 05/15/2001 | SACLARIDES | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 04/23/2001 | 05/15/2001 | SACLARIDES | 0/0 | COMPLIANCE ASSURANCE | ||||||
SV | 02/08/2001 | 03/28/2001 | MURRAY_K | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes VERIFY DISPENSER LINER | |||||||||||
TCI | 02/06/2001 | 02/09/2001 | MINOR OUT-OF-COMPLIANCE | MURRAY_K | 0/3 | COMPLIANCE ASSURANCE | |||||
CWOE | 11/05/1999 | 11/17/1999 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/05/1999 | 11/17/1999 | IN-COMPLIANCE | NEWBERG_D | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 06/25/1999 | 11/17/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | CALLAHAM_C | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 08/31/2024 | Major Out of Compliance | CASSELS_CR_2 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 09/12/2023 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 08/07/2020 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 08/07/2020 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 08/07/2020 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Letter | 08/06/2020 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Site Inspection | 08/05/2020 | Major Out of Compliance | CASSELS_CR_2 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 11/05/2018 | Satisfied | SELLERS_R | Enforcement | |||||||
Enforcement Tracking | 11/05/2018 | Closed Without Enforcement | SELLERS_R | Enforcement | |||||||
Electronic Communication | 11/03/2018 | Satisfied | JARRETT_SE_1 | Closure | |||||||
Phone Conversation | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Phone Conversation | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Letter | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Phone Conversation | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Electronic Communication | 11/03/2018 | Satisfied | JARRETT_SE_1 | Compliance Assistance | |||||||
Site Inspection | 11/02/2018 | Minor Out of Compliance | JARRETT_SE_1 | 0/1 | Compliance Assistance | ||||||
Issue Document | 10/03/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 09/14/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Enforcement Referral | 09/14/2018 | Accepted | WILLIAMSON_KE_1 | Enforcement | |||||||
Electronic Communication | 09/14/2018 | Satisfied | SELLERS_R | Enforcement | |||||||
Electronic Communication | 09/12/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Phone Conversation | 08/06/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/21/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/21/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Letter | 06/08/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Site Inspection | 06/08/2018 | Major Out of Compliance | WILLIAMSON_KE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 06/08/2018 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 05/07/2018 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||||||
Issue Document | 09/30/2015 | Satisfied | MERRYMAN_DT_1 | Routine Compliance | |||||||
Site Inspection | 09/30/2015 | In Compliance | MERRYMAN_DT_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 01/31/2014 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Electronic Communication | 01/31/2014 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Electronic Communication | 01/30/2014 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 01/08/2014 | Minor Out of Compliance | WINN_JP_1 | 0/1 | Routine Compliance | ||||||
Letter | 01/08/2014 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Letter | 03/26/2013 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 03/26/2013 | Minor Out of Compliance | WINN_JP_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 01/03/2012 | In Compliance | BELL_JM_1 | 0/1 | Non-Compliance | ||||||
Phone Conversation | 10/14/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||||||
Site Inspection | 08/29/2011 | Minor Out of Compliance | BELL_JM_1 | 0/1 | Routine Compliance | ||||||
Letter | 08/29/2011 | Satisfied | BELL_JM_1 | Non-Compliance | |||||||
Record Document | 10/28/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 10/21/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Electronic Communication | 10/21/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 10/14/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Phone Conversation | 10/14/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Letter | 08/31/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 08/31/2010 | Minor Out of Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Record Document | 08/12/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 07/15/2009 | Minor Out of Compliance | DERY_WC_1 | 0/1 | Routine Compliance | ||||||
Letter | 07/15/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 07/06/2009 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Site Inspection | 09/09/2008 | In Compliance | DERY_WC_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 07/30/2008 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Site Inspection | 02/15/2008 | In Compliance | WINN_JP_1 | 0/1 | Installation | ||||||
Record Document | 10/15/2007 | Satisfied | CASSELS_CR_1 | Installation | |||||||
Record Document | 08/06/2007 | Satisfied | CASSELS_CR_1 | Closure | |||||||
Issue Document | 07/16/2007 | Satisfied | CASSELS_CR_1 | Closure | |||||||
Phone Conversation | 07/16/2007 | Satisfied | CASSELS_CR_1 | Closure | |||||||
TCAR | 07/05/2007 | Satisfied | CASSELS_CR_1 | Closure | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
08/31/2024 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | A copy of the previous financial responsibility documentation for the coverage period 02/08/2021 to 02/08/2023 must be submitted to the Department, including the required DEP Form. | |||||||
08/23/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Premium bucket interstice dipstick must be repaired or replaced, and the Department notified. | |||||||
08/05/2020 | 4015 | Minor | 2.10 Incomplete documentation demonstrating financial responsibility. | The DEP Certification of Financial Responsibility (CFR) Form Part P must be completed for the current policy period (02/08/2019 to 02/08/2021) with a copy submitted to the Department. | |||||||
08/05/2020 | 4067 | Minor | 4.2 Release detection devices not tested annually. | Copies of the 2018 and 2019 annual operability test results of the release detection equipment (Line Leak Detectors) must be submitted to the Department. | |||||||
08/05/2020 | 4067 | Minor | 4.2 Release detection devices not tested annually. | Copies of the 2018 and 2019 annual operability test results of the release detection equipment (Veeder-Root electronic monitoring system) must be submitted to the Department. | |||||||
08/05/2020 | 4076 | Minor | 4.11 Failure to conduct required periodic containment and interstitial integrity testing. | Copies of the integrity test results of the double-walled spill buckets, STP sumps, and dispenser sumps must be submitted to the Department. If the tests have not been performed, they must be performed immediately with the results submitted to the Department. | |||||||
08/05/2020 | 4057 | Minor | 4.31 Overfill protection devices not registered or tested annually. | Copies of the 2019 annual operability test results of the overfill protection equipment (drop tube overfill prevention valves) must be submitted to the Department. | |||||||
11/02/2018 | 4079 | Minor | 2.7 Records requiring 3 years documentation period not kept by facility. | The records must be submitted to the Department. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
03/09/2006 | COMPLETED | 30 | |||||||||