District | Southwest | Type | Retail Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 8945515 | Latitude | 27° 53' 16.9702 | ||||||||
Name |
SHELL FOOD MART 7336 SR 60 E |
Longitude | 81° 28' 15.0846 | ||||||||
LAKE WALES, FL 33853 | LL Method | DPHO | |||||||||
Contact | UDAY SURABHI (847)767.4223 | LL Status | REVIEWED | ||||||||
Phone | (863) 696-3840 | Status Date | 02/12/2024 | ||||||||
Account Owner Information | |||||||||||
Name | SURABHI, UDAY 7336 STATE ROAD 60 E LAKE WALES, FL 33898 |
Effective Date | 08/10/2012 | ||||||||
Contact | UDAY SURABHI | ||||||||||
Phone | (847) 767-4223 | ||||||||||
SURABHI.UDAY@YAHOO.COM | |||||||||||
Placard # / Date | 687791 - 06/13/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CONVENIENCE CENTER DEV ASSOC 5041 BLIND PASS RD SAINT PETERSBURG, FL 33706 |
Effective Date | 09/30/2009 | ||||||||
Contact | PAUL RESOP | ||||||||||
Phone | (727) 360-4079 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 20000 | Unleaded Gas (B) | 09/01/2005 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Unleaded Gas (B) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 08/20/2024 | 08/20/2025 | LLOYD'S UNDERWRITERS | ||||||||
INSURANCE | 08/20/2023 | 08/20/2024 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 08/20/2022 | 08/20/2023 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 08/20/2021 | 08/20/2022 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 03/20/2020 | 03/20/2021 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/20/2019 | 03/20/2020 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/20/2018 | 03/20/2019 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/20/2017 | 03/20/2018 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/20/2016 | 03/20/2017 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/20/2015 | 03/20/2016 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 02/20/2013 | 02/20/2014 | AMERICAN SAFETY | ||||||||
INSURANCE | 02/16/2012 | 02/16/2013 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/16/2011 | 02/16/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/16/2010 | 02/16/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/30/2008 | 09/30/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||||||
INSURANCE | 10/01/2000 | 10/01/2003 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/04/1993 | 06/04/1996 | PLUS | ||||||||
INSURANCE | 06/04/1990 | 07/18/1990 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 03/23/2006 | 04/05/2006 | IN-COMPLIANCE | CASSELS_C | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS. PIPING: DOUBLE WALL FIBERGLASS, PRESSURIZED, INTERSTICE OPEN TO SUMPS, GOOD CONDITION. | |||||||||||
CRDE | 11/09/2005 | 02/15/2006 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 11/02/2005 | 11/02/2005 | CASSELS_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED LIMITED CLOSURE REPORT. | |||||||||||
NCLI | 10/05/2005 | 10/10/2005 | GONZALEZ_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 09/28/2005 | 03/30/2006 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED LINE TEST RESULTS, RESOLVES VIOLATION #1028. | |||||||||||
RRBD | 09/28/2005 | 11/18/2005 | CASSELS_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED MANIFEST. | |||||||||||
RRBD | 09/28/2005 | 11/08/2005 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED: PUMP OUT INVOICE, RELEASE DETECTION RESPONSE LEVELS #1. | |||||||||||
TIN | 09/28/2005 | 10/10/2005 | MINOR OUT-OF-COMPLIANCE | GONZALEZ_J | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes 7 PHOTOS TAKEN. INSTALLED 1 DW COMPARTMENTED STEEL FIBERGLASS TANK. PIPING: RIGID DW FIBERGLASS AMERON DUALOY 3000/L EQ-378. 2 STP SUMPS, 4 DISPENSER LINERS, 2 SPILL BUCKETS, MECHANICAL LLDETECTOR & VEEDER ROOM LEAK/LIQUID DETECTOR. | |||||||||||
SV | 09/27/2005 | 10/18/2005 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 7 PHOTOS TAKEN. FINAL INSPECTION OF SYSTEM. | |||||||||||
RRBD | 09/26/2005 | 11/08/2005 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED REGISTRATION FORM, PSSSC FORM. | |||||||||||
SV | 09/15/2005 | 09/23/2005 | SLAPPEY_W | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 3 PHOTOS TAKEN. HYDRO TEST ON STP SUMPS & SPILL BUCKETS. SECONDARY LINE TEST. ALL TESTS PASSED. | |||||||||||
SV | 09/14/2005 | 11/08/2005 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 4 PHOTOS TAKEN. PRIMARY LINE TEST BETWEEN DISPENSER PIPING AND UST. | |||||||||||
SV | 09/07/2005 | 09/27/2005 | COOK_J | 0/1 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 20,000-GAL UST SET & ANCHORED. METAL PRODUCTS CO. 'ELUTRON' (STEEL/FRP), EQ-333, UL# M757073. COMPARTMENTED 14K/6K. INTERSTICE VACUUM 23 -IN HG. BEFORE & AFTER PLACEMENT. 4 PHOTOS TAKEN. | |||||||||||
SV | 08/24/2005 | 09/03/2005 | GONZALEZ_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 5 PHOTOS TAKEN. SECONDARY LINE PRESSURE TEST & STATIC HYDRAULIC TEST OF DISPENSER LINERS. | |||||||||||
SV | 08/18/2005 | 09/03/2005 | CASSELS_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 8 PHOTOS TAKEN. PRIMARY LINE TEST. | |||||||||||
CWOE | 08/10/2005 | 09/03/2005 | CASSELS_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TXI | 08/10/2005 | 09/03/2005 | IN-COMPLIANCE | CASSELS_C | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes 10 PHOTOS TAKEN. CLOSED: 2-10,000 GAL SW UNDERGROUND TANKS, #1 & 2. APPROX 50' PIPING, 2 SPILL BUCKETS, 2 SUMPS, AND 4 DISPENSERS. OTHER SECTIONS OF PIPE RUN TO DISPENSER ISLANDS TO BE CAPPED IN PLACE. CLOSURE REPORT DUE 10/9/05. RESOLVES VIO #1105. | |||||||||||
NCLI | 07/14/2005 | 07/14/2005 | COOK_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #1091. | |||||||||||
TCI | 06/27/2005 | 07/10/2005 | MINOR OUT-OF-COMPLIANCE | COOK_J | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes 1 PHOTO TAKEN. PIPING: DOUBLE-WALL FIBERGLASS DISCOLORED. INDICATED LIKELY PRODUCT IS SMITH RED THREAD. DEEP CORROSION ALONG BOTTOM SEAMS OF STEEL DISPENSER LINERS, POSSIBLE PERFORATIONS. TEST & REPAIR INDICATED. | |||||||||||
TCI | 10/23/2003 | 11/05/2003 | IN-COMPLIANCE | HUGHES_J | 0/2 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. | |||||||||||
RRBD | 02/13/2003 | 03/07/2003 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
CWOE | 02/13/2003 | 03/07/2003 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 12/04/2002 | 12/04/2002 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/21/2002 | 12/04/2002 | MINOR OUT-OF-COMPLIANCE | SACLARIDES_M | /2 | COMPLIANCE ASSURANCE | |||||
TCI | 08/08/2001 | 08/10/2001 | IN-COMPLIANCE | RANDOLPH_L | 0/2 | COMPLIANCE ASSURANCE | |||||
CALL | 07/24/2001 | 08/10/2001 | RANDOLPH_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes SCHEDULED TCI | |||||||||||
RRBD | 01/16/2001 | 01/19/2001 | RANDOLPH | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 01/16/2001 | 01/19/2001 | COOK | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes RESOLVED-NO DISCHARGE | |||||||||||
TCI | 11/02/2000 | 11/16/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | RANDOLPH | 0/2 | COMPLIANCE ASSURANCE | |||||
RRBD | 01/27/2000 | 02/04/2000 | RONEY_B | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 11/18/1999 | 11/18/1999 | RONEY_B | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/16/1999 | 11/18/1999 | MINOR OUT-OF-COMPLIANCE | RONEY_B | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 03/25/1999 | 04/13/1999 | IN-COMPLIANCE | COOK_J | 0/2 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 11/07/2024 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 11/07/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 11/07/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 10/29/2024 | Major Out of Compliance | GLENN_LE_1 | 0/1 | Routine Compliance | ||||||
Letter | 01/31/2023 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 01/31/2023 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 01/31/2023 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 02/28/2022 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 02/28/2022 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 02/28/2022 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 02/28/2022 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Site Inspection | 02/26/2022 | Minor Out of Compliance | GLENN_LE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 03/19/2020 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 03/19/2020 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 03/19/2020 | Minor Out of Compliance | GLENN_LE_1 | 0/1 | Routine Compliance | ||||||
Letter | 03/19/2020 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 03/19/2020 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 03/19/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 03/19/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 03/19/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 02/06/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 02/06/2018 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 02/06/2018 | Minor Out of Compliance | GLENN_LE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 01/03/2018 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Site Inspection | 03/11/2016 | In Compliance | WILLIAMSON_KE_1 | 0/1 | Non-Compliance | ||||||
Electronic Communication | 03/11/2016 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Electronic Communication | 01/28/2016 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||||||
Letter | 01/28/2016 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Site Inspection | 01/28/2016 | Minor Out of Compliance | WILLIAMSON_KE_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 01/12/2016 | Satisfied | WILLIAMSON_KE_1 | Routine Compliance | |||||||
Site Inspection | 11/18/2013 | In Compliance | WINN_JP_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 11/18/2013 | Satisfied | WINN_JP_1 | Routine Compliance | |||||||
Letter | 10/16/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Phone Conversation | 10/10/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Letter | 09/25/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Record Document | 09/25/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Site Inspection | 09/25/2012 | Minor Out of Compliance | NEWBERG_DR_1 | 0/1 | Non-Compliance | ||||||
Phone Conversation | 09/25/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Letter | 08/28/2012 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Site Inspection | 08/28/2012 | Minor Out of Compliance | NEWBERG_DR_1 | 0/1 | Routine Compliance | ||||||
Record Document | 05/05/2011 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Phone Conversation | 04/29/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Electronic Communication | 04/29/2011 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Site Inspection | 04/28/2011 | In Compliance | MEETZE_A | 0/1 | QA/QC | ||||||
Record Document | 04/06/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Letter | 03/28/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 03/28/2011 | Major Out of Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 02/15/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Record Document | 01/21/2011 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Letter | 12/21/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 12/21/2010 | Major Out of Compliance | CASSELS_CR_1 | 0/1 | Non-Compliance | ||||||
Phone Conversation | 07/26/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Record Document | 06/18/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Meeting | 06/18/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 06/11/2010 | Minor Out of Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Letter | 06/11/2010 | Satisfied | CASSELS_CR_1 | Non-Compliance | |||||||
Site Inspection | 03/26/2009 | In Compliance | CASSELS_CR_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 03/11/2009 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Site Inspection | 05/29/2008 | In Compliance | WINN_JP_1 | 0/1 | Routine Compliance | ||||||
Enforcement Tracking | 02/15/2008 | Closed Without Enforcement | RANDOLPH_L | Enforcement | |||||||
Enforcement Referral | 02/15/2008 | Accepted | RANDOLPH_L | Enforcement | |||||||
Record Document | 02/15/2008 | Satisfied | RANDOLPH_L | Enforcement | |||||||
Letter | 12/20/2007 | Satisfied | DERY_WC_1 | Closure | |||||||
TCAR | 12/20/2007 | Satisfied | DERY_WC_1 | Closure | |||||||
TCAR | 08/22/2007 | Satisfied | DERY_WC_1 | Closure | |||||||
Site Inspection | 05/16/2007 | In Compliance | NEWBERG_DR_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 04/05/2007 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 02/07/2007 | Satisfied | CASSELS_CR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/22/2006 | Satisfied | CROWELL_MP | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/29/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Dispenser #4 whip hose must be replaced and the Department notified. | |||||||
10/29/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Test valves must be removed and the Department notified. | |||||||
10/29/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Dirt, debris and water must be removed from dispenser liners and the Department notified. | |||||||