Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Retail Station | ||||||||
County | Okaloosa | Status | OPEN | ||||||||
ID | 8945546 | Latitude | 30° 25' 25.2082 | ||||||||
Name |
SUNSHINE FOOD MART #475 521 MARY ESTHER CUT OFF |
Longitude | 86° 38' 59.3894 | ||||||||
FORT WALTON BEACH, FL 32548 | LL Method | DPHO | |||||||||
Contact | JOE FIELDS | LL Status | REVIEWED | ||||||||
Phone | (321) 631-0245 | Status Date | 09/21/2023 | ||||||||
Account Owner Information | |||||||||||
Name | T & M UNITED II LLC 402-A HIGH POINT DR #101 COCOA, FL 32926 |
Effective Date | 05/16/2019 | ||||||||
Contact | JOE FIELDS | ||||||||||
Phone | (321) 631-0245 | ||||||||||
JOE@SOUTHEASTPETRO.COM | |||||||||||
Placard # / Date | 685594 - 06/07/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | T & M UNITED II LLC 402-A HIGH POINT DR #101 COCOA, FL 32926 |
Effective Date | 05/16/2019 | ||||||||
Contact | JOE FIELDS | ||||||||||
Phone | (321) 631-0245 | ||||||||||
JOE@SOUTHEASTPETRO.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 25000 | Unleaded Gas (B) | 09/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (M) Spill containment bucket (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Unleaded Gas (B) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (D) External protective coating (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8000 | Unleaded Gas (B) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (D) External protective coating (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 8000 | Unleaded Gas (B) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (D) External protective coating (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 8000 | Vehicular Diesel (D) | 11/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (D) External protective coating (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 05/13/2024 | 05/13/2025 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2023 | 05/13/2024 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2022 | 05/13/2023 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2021 | 05/13/2022 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 05/13/2020 | 05/13/2021 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 03/31/2018 | 03/31/2019 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 03/31/2017 | 03/31/2018 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 03/31/2016 | 03/31/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2015 | 03/31/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2015 | 03/31/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2014 | 03/31/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/31/2012 | 03/31/2013 | ILLINOIS UNION | ||||||||
INSURANCE | 03/31/2012 | 03/31/2013 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 11/11/2009 | 11/11/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 11/11/2008 | 11/11/2009 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 10/14/2005 | 10/24/2005 | MINOR OUT-OF-COMPLIANCE | J. SCOTT HALE | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 10/13/2004 | 10/18/2004 | IN-COMPLIANCE | J. SCOTT HALE | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 12/11/2003 | 12/12/2003 | JOHN S. STEVENSON | 0/2 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/20/2003 | 12/03/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | JOHN S. STEVENSON | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 07/29/2002 | 08/09/2002 | IN-COMPLIANCE | V. PAUL HUTCHERSON | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 08/20/2001 | 08/28/2001 | IN-COMPLIANCE | THAYER_JD | 0/4 | COMPLIANCE ASSURANCE | |||||
RRBD | 10/17/2000 | 11/16/2000 | COMPLIANCE ASSURANCE | ||||||||
TCI | 09/20/2000 | 09/23/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | THAYER_JD | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 09/29/1999 | 10/01/1999 | IN-COMPLIANCE | THAYER_JD | 0/4 | COMPLIANCE ASSURANCE | |||||
RRBD | 09/29/1999 | 10/11/1999 | THAYER_JD | 0/0 | COMPLIANCE ASSURANCE | ||||||
TDI | 04/08/1999 | 04/29/1999 | IN-COMPLIANCE | THAYER_J | 0/4 | DISCHARGE PROJECT | |||||
UTCR | 08/25/1998 | 09/03/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 10/31/2024 | Major Out of Compliance | ELLIOTT_EV_1 | 0/1 | Routine Compliance | ||||||
Letter | 10/31/2024 | Satisfied | ELLIOTT_EV_1 | Compliance Assistance | |||||||
Electronic Communication | 10/31/2024 | Satisfied | ELLIOTT_EV_1 | Routine Compliance | |||||||
TCAR | 11/21/2023 | Satisfied | PAYNE_CL_1 | Component Closure | |||||||
Document Management | 11/21/2023 | Satisfied | PAYNE_CL_1 | Component Closure | |||||||
Letter | 11/21/2023 | Satisfied | PAYNE_CL_1 | Component Closure | |||||||
Letter | 11/16/2023 | Satisfied | PAYNE_CL_1 | Component Installation | |||||||
Site Inspection | 11/16/2023 | In Compliance | PAYNE_CL_1 | 0/1 | Component Installation | ||||||
Letter | 02/07/2023 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 02/03/2023 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Letter | 12/20/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 12/20/2022 | Major Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 12/14/2022 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Issue Document | 02/10/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 02/10/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 02/05/2021 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Issue Document | 12/11/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 12/11/2020 | Minor Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Letter | 12/11/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 12/10/2020 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Enforcement Tracking | 09/12/2019 | Closed Without Enforcement | BRISTOL_S | Enforcement | |||||||
Enforcement Referral | 05/22/2019 | Accepted | WILSON_ML_1 | Enforcement | |||||||
Electronic Communication | 09/17/2018 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Issue Document | 09/17/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 09/17/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 09/17/2018 | Minor Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 11/22/2016 | In Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 06/15/2015 | In Compliance | FOXWORTH_S_1 | 0/1 | Non-Compliance | ||||||
Letter | 05/29/2015 | Satisfied | WILSON_ML_1 | Non-Compliance | |||||||
Letter | 01/05/2015 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Site Inspection | 12/30/2014 | Minor Out of Compliance | FOXWORTH_S_1 | 0/1 | Routine Compliance | ||||||
Record Document | 06/03/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 11/27/2012 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Site Inspection | 11/21/2012 | Minor Out of Compliance | KHAN_MR_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 11/21/2012 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 07/27/2011 | In Compliance | HALE_JS_1 | 0/1 | Routine Compliance | ||||||
Document Management | 12/21/2010 | Complete | TISSINGTON_AB_1 | Discharge | |||||||
Letter | 09/22/2010 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 08/27/2010 | Major Out of Compliance | TISSINGTON_AB_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/26/2010 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Discharge Reporting | 02/17/2010 | Satisfied | TISSINGTON_AB_1 | Discharge | |||||||
Letter | 02/17/2010 | Satisfied | PIERCE_LL_1 | Discharge | |||||||
Site Inspection | 11/19/2009 | In Compliance | TISSINGTON_AB_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 10/06/2009 | In Compliance | TISSINGTON_AB_1 | 0/1 | Discharge | ||||||
Record Document | 10/06/2009 | Satisfied | TISSINGTON_AB_1 | Discharge | |||||||
Site Inspection | 09/03/2009 | In Compliance | THAYER_JD_1 | 0/1 | Installation | ||||||
Site Inspection | 08/11/2009 | In Compliance | TISSINGTON_AB_1 | 0/4 | Closure | ||||||
Emergency Preparedness Information | 08/27/2008 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Site Inspection | 08/27/2008 | In Compliance | TISSINGTON_AB_1 | 0/4 | Routine Compliance | ||||||
Record Document | 06/26/2008 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Letter | 03/13/2008 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Site Inspection | 02/29/2008 | Minor Out of Compliance | STEVENSON_JS | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/13/2007 | Satisfied | HALE_JS_1 | Routine Compliance | |||||||
Site Inspection | 11/16/2006 | In Compliance | STEVENSON_JS | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/27/2006 | Satisfied | HALE_JS_1 | Routine Compliance | |||||||
Site Inspection | 06/22/2006 | In Compliance | THAYER_JD_1 | 0/4 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have the long hose on the diesel dispenser 10 replaced. Once work is completed, email a copy of the work invoice to the inspector for review to clear the violation. The work invoice must indicate that the hose has been replaced. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6046 | Minor | 4.14 Dispensers not installed and maintained according to standards. | Have a certified contractor remove the nipple and coupling before the plug beneath dispenser 5/6. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the nipple and coupling have been removed. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Have a certified technician test the Spill Containment Gauges for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have a certified contractor repair or replace the Regular Spill Containment Gauge. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov. | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove the liquid from the secondary and re-install or replace the interstitial gauge as necessary. The integrity of the premium spill containment must be tested before it brought back into service. If the spill containment needs to be replaced, contact the inspector prior to work beginning. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6046 | Minor | 4.14 Dispensers not installed and maintained according to standards. | Have a certified contractor remove the valves beneath dispenser 3/4. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the valves have been removed. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have the short hose on dispenser 9 replaced. Once work is completed, email a copy of the work invoice to the inspector for review to clear the violation. The work invoice must indicate that the hose has been replaced. Email: Emily.Elliott@FLHealth.gov | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have a certified contractor replace the damaged component(s) to ensure dispenser 5/6 sump is liquid tight. Contact the inspector a minimum of 30 days prior to replacement activities for to receive the appropriate paperwork. Once work is completed have the integrity of dispenser 5/6 sump tested to verify, they are liquid tight. Email: Emily.Elliott@FLHealth.gov | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
08/29/2009 | COMPLETED | 70 | |||||||||
04/09/1999 | COMPLETED | 70 | |||||||||