DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Okaloosa   Status    OPEN
 
ID 8945546   Latitude    30° 25' 25.2082
 
Name SUNSHINE FOOD MART #475
521 MARY ESTHER CUT OFF
Longitude    86° 38' 59.3894
  FORT WALTON BEACH, FL 32548 LL Method    DPHO
 
Contact JOE FIELDS   LL Status    REVIEWED
 
Phone (321) 631-0245   Status Date    09/21/2023
 
Account Owner Information
 
Name T & M UNITED II LLC
402-A HIGH POINT DR #101
COCOA, FL 32926
Effective Date    05/16/2019
 
Contact JOE FIELDS
 
Phone (321) 631-0245
 
Email JOE@SOUTHEASTPETRO.COM
  Placard # / Date    685594 - 06/07/2024
Property Owner Information
 
Name T & M UNITED II LLC
402-A HIGH POINT DR #101
COCOA, FL 32926
Effective Date    05/16/2019
 
Contact JOE FIELDS
 
Phone (321) 631-0245
 
Email JOE@SOUTHEASTPETRO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
5 25000 Unleaded Gas (B) 09/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(D) External protective coating
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(D) External protective coating
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(D) External protective coating
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 8000 Vehicular Diesel (D) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(D) External protective coating
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/13/2024 05/13/2025 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   05/13/2023 05/13/2024 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   05/13/2022 05/13/2023 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   05/13/2021 05/13/2022 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   05/13/2020 05/13/2021 ASPEN SPECIALTY INSURANCE COMPANY
INSURANCE   03/31/2018 03/31/2019 NAUTILUS INSURANCE COMPANY
INSURANCE   03/31/2017 03/31/2018 NAUTILUS INSURANCE COMPANY
INSURANCE   03/31/2016 03/31/2017 COMMERCE & INDUSTRY
INSURANCE   03/31/2015 03/31/2015 COMMERCE & INDUSTRY
INSURANCE   03/31/2015 03/31/2016 COMMERCE & INDUSTRY
INSURANCE   03/31/2014 03/31/2015 COMMERCE & INDUSTRY
INSURANCE   03/31/2012 03/31/2013 ILLINOIS UNION
INSURANCE   03/31/2012 03/31/2013 NAUTILUS INSURANCE COMPANY
INSURANCE   11/11/2009 11/11/2010 ZURICH-AMERICAN
INSURANCE   11/11/2008 11/11/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 10/14/2005 10/24/2005 MINOR OUT-OF-COMPLIANCE J. SCOTT HALE 0/4 COMPLIANCE ASSURANCE
 
TCI 10/13/2004 10/18/2004 IN-COMPLIANCE J. SCOTT HALE 0/3 COMPLIANCE ASSURANCE
 
RRBD 12/11/2003 12/12/2003 JOHN S. STEVENSON 0/2 COMPLIANCE ASSURANCE
 
TCI 11/20/2003 12/03/2003 SIGNIFICANT OUT-OF-COMPLIANCE JOHN S. STEVENSON 0/4 COMPLIANCE ASSURANCE
 
TCI 07/29/2002 08/09/2002 IN-COMPLIANCE V. PAUL HUTCHERSON 0/4 COMPLIANCE ASSURANCE
 
TCI 08/20/2001 08/28/2001 IN-COMPLIANCE THAYER_JD 0/4 COMPLIANCE ASSURANCE
 
RRBD 10/17/2000 11/16/2000 COMPLIANCE ASSURANCE
 
TCI 09/20/2000 09/23/2000 SIGNIFICANT OUT-OF-COMPLIANCE THAYER_JD 0/4 COMPLIANCE ASSURANCE
 
TCI 09/29/1999 10/01/1999 IN-COMPLIANCE THAYER_JD 0/4 COMPLIANCE ASSURANCE
 
RRBD 09/29/1999 10/11/1999 THAYER_JD 0/0 COMPLIANCE ASSURANCE
 
TDI 04/08/1999 04/29/1999 IN-COMPLIANCE THAYER_J 0/4 DISCHARGE PROJECT
 
UTCR 08/25/1998 09/03/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 10/31/2024 Major Out of Compliance ELLIOTT_EV_1 0/1 Routine Compliance
 
Letter 10/31/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Electronic Communication 10/31/2024 Satisfied ELLIOTT_EV_1 Routine Compliance
 
TCAR 11/21/2023 Satisfied PAYNE_CL_1 Component Closure
 
Document Management 11/21/2023 Satisfied PAYNE_CL_1 Component Closure
 
Letter 11/21/2023 Satisfied PAYNE_CL_1 Component Closure
 
Letter 11/16/2023 Satisfied PAYNE_CL_1 Component Installation
 
Site Inspection 11/16/2023 In Compliance PAYNE_CL_1 0/1 Component Installation
 
Letter 02/07/2023 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 02/03/2023 Satisfied PAYNE_CL_1 Compliance Assistance
 
Letter 12/20/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 12/20/2022 Major Out of Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Electronic Communication 12/14/2022 Satisfied PAYNE_CL_1 Routine Compliance
 
Issue Document 02/10/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 02/10/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 02/05/2021 Satisfied PAYNE_CL_1 Compliance Assistance
 
Issue Document 12/11/2020 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 12/11/2020 Minor Out of Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Letter 12/11/2020 Satisfied WILSON_ML_1 Compliance Assistance
 
Electronic Communication 12/10/2020 Satisfied PAYNE_CL_1 Routine Compliance
 
Enforcement Tracking 09/12/2019 Closed Without Enforcement BRISTOL_S Enforcement
 
Enforcement Referral 05/22/2019 Accepted WILSON_ML_1 Enforcement
 
Electronic Communication 09/17/2018 Satisfied PAYNE_CL_1 Routine Compliance
 
Issue Document 09/17/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 09/17/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 09/17/2018 Minor Out of Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Site Inspection 11/22/2016 In Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Site Inspection 06/15/2015 In Compliance FOXWORTH_S_1 0/1 Non-Compliance
 
Letter 05/29/2015 Satisfied WILSON_ML_1 Non-Compliance
 
Letter 01/05/2015 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 12/30/2014 Minor Out of Compliance FOXWORTH_S_1 0/1 Routine Compliance
 
Record Document 06/03/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 11/27/2012 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 11/21/2012 Minor Out of Compliance KHAN_MR_1 0/1 Routine Compliance
 
Emergency Preparedness Information 11/21/2012 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 07/27/2011 In Compliance HALE_JS_1 0/1 Routine Compliance
 
Document Management 12/21/2010 Complete TISSINGTON_AB_1 Discharge
 
Letter 09/22/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 08/27/2010 Major Out of Compliance TISSINGTON_AB_1 0/1 Routine Compliance
 
Emergency Preparedness Information 08/26/2010 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Discharge Reporting 02/17/2010 Satisfied TISSINGTON_AB_1 Discharge
 
Letter 02/17/2010 Satisfied PIERCE_LL_1 Discharge
 
Site Inspection 11/19/2009 In Compliance TISSINGTON_AB_1 0/1 Routine Compliance
 
Site Inspection 10/06/2009 In Compliance TISSINGTON_AB_1 0/1 Discharge
 
Record Document 10/06/2009 Satisfied TISSINGTON_AB_1 Discharge
 
Site Inspection 09/03/2009 In Compliance THAYER_JD_1 0/1 Installation
 
Site Inspection 08/11/2009 In Compliance TISSINGTON_AB_1 0/4 Closure
 
Emergency Preparedness Information 08/27/2008 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Site Inspection 08/27/2008 In Compliance TISSINGTON_AB_1 0/4 Routine Compliance
 
Record Document 06/26/2008 Satisfied STEVENSON_JS Non-Compliance
 
Letter 03/13/2008 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 02/29/2008 Minor Out of Compliance STEVENSON_JS 0/4 Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied HALE_JS_1 Routine Compliance
 
Site Inspection 11/16/2006 In Compliance STEVENSON_JS 0/4 Routine Compliance
 
Emergency Preparedness Information 09/27/2006 Satisfied HALE_JS_1 Routine Compliance
 
Site Inspection 06/22/2006 In Compliance THAYER_JD_1 0/4 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have the long hose on the diesel dispenser 10 replaced. Once work is completed, email a copy of the work invoice to the inspector for review to clear the violation. The work invoice must indicate that the hose has been replaced. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Have a certified contractor remove the nipple and coupling before the plug beneath dispenser 5/6. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the nipple and coupling have been removed. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the Spill Containment Gauges for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have a certified contractor repair or replace the Regular Spill Containment Gauge. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov.
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Remove the liquid from the secondary and re-install or replace the interstitial gauge as necessary. The integrity of the premium spill containment must be tested before it brought back into service. If the spill containment needs to be replaced, contact the inspector prior to work beginning. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Have a certified contractor remove the valves beneath dispenser 3/4. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the valves have been removed. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have the short hose on dispenser 9 replaced. Once work is completed, email a copy of the work invoice to the inspector for review to clear the violation. The work invoice must indicate that the hose has been replaced. Email: Emily.Elliott@FLHealth.gov
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have a certified contractor replace the damaged component(s) to ensure dispenser 5/6 sump is liquid tight. Contact the inspector a minimum of 30 days prior to replacement activities for to receive the appropriate paperwork. Once work is completed have the integrity of dispenser 5/6 sump tested to verify, they are liquid tight. Email: Emily.Elliott@FLHealth.gov
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
08/29/2009   COMPLETED 70
 
04/09/1999   COMPLETED 70