DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    Fuel user/Non-retail
 
County Monroe   Status    OPEN
 
ID 9045633   Latitude    24° 42' 47.6858
 
Name FL KEYS COUNTRY CLUB
4000 SOMBRERO BLVD
Longitude    81° 4' 34.1498
  MARATHON, FL 33050-2458 LL Method    DPHO
 
Contact TONY YOUNG   LL Status    REVIEWED
 
Phone (352) 643-1555   Status Date    03/07/2024
 
Account Owner Information
 
Name FL KEYS RESORT LLC
4000 SOMBRERO BLVD
MARATHON, FL 33050
Effective Date    09/10/2015
 
Contact DIANE MCHEFFEY
 
Phone (305) 743-3433
 
Email ACCOUNTING@FLORIDAKEYSCC.COM
  Placard # / Date    682680 - 06/05/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
3 1000 Unleaded Gas (B) 09/01/2006 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
(V) Suction pump check valve
 
 
Tank Tank Size Content Installed Placement Status
4 3500 Vehicular Diesel (D) 09/01/2006 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
(V) Suction pump check valve
 
 
Tank Tank Size Content Installed Placement Status
1 550 Unleaded Gas (B) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (A) Abv, no soil contact (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
2 550 Vehicular Diesel (D) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (A) Abv, no soil contact (I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   11/17/2021 11/17/2023 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   11/17/2019 11/17/2021 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   11/17/2017 11/17/2019 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   11/01/2015 11/01/2017 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   11/17/2011 11/17/2013 AMERICAN SAFETY
INSURANCE   11/17/2009 11/17/2011 AMERICAN SAFETY
INSURANCE   11/17/2008 11/17/2009 AMERICAN SAFETY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 10/09/2023 Major Out of Compliance SHANBERG_V 2/0 Routine Compliance
 
Letter 05/18/2020 Satisfied WINKLER_MG_1 Compliance Assistance
 
Site Inspection 05/18/2020 Minor Out of Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Letter 12/29/2017 Satisfied WINKLER_MG_1 Routine Compliance
 
Site Inspection 12/28/2017 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 04/06/2017 In Compliance WINKLER_MG_1 2/0 Non-Compliance
 
Phone Conversation 03/06/2017 Satisfied WINKLER_MG_1 Non-Compliance
 
Electronic Communication 03/06/2017 Satisfied WINKLER_MG_1 Non-Compliance
 
Letter 07/24/2015 Satisfied WINKLER_MG_1 Non-Compliance
 
Site Inspection 07/24/2015 Major Out of Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Phone Conversation 07/22/2015 Satisfied WINKLER_MG_1 Routine Compliance
 
Site Inspection 10/30/2013 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 12/06/2011 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 01/28/2011 In Compliance WINKLER_MG_1 2/0 Non-Compliance
 
Letter 11/17/2010 Satisfied WINKLER_MG_1 Non-Compliance
 
Site Inspection 11/16/2010 Minor Out of Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 01/04/2010 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 02/13/2009 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 03/05/2008 In Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 06/14/2007 Minor Out of Compliance WINKLER_MG_1 2/0 Routine Compliance
 
Site Inspection 06/14/2007 Minor Out of Compliance MELE_V 2/0 QA/QC
 
Site Inspection 09/12/2006 In Compliance WINKLER_MG_1 2/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/09/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Use an AST monthly visual checklist to look at every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances and provide documentation to the Department.
 
10/09/2023 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. Clean, paint, and seal the tank's exterior and send photo documentation to the department.
 
09/14/2023 7105 Minor 1.14 Closure Report not submitted. The facility will need to submit a Closure report in accordance with Instructions for Conducting Sampling During Aboveground Storage Tank Closure, July 2019 Edition, to the Department.
 
06/15/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide annual operability testing documentation for overfill protection device for 2021, 2022, and 2023 to the Department.
 
06/15/2023 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. Clean, paint, and seal the tank's spill bucket and send photo documentation to the department.
 
06/15/2023 7043 Minor 1.11 Fillbox covers not marked according to requirements. Properly mark fill box cover using the API Color-Symbol System to Mark Equipment and Vehicles for Product Identification at Gasoline Dispensing Facilities and Distribution Terminals and send photo documentation to the Department.
 
06/15/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Provide release detection annual operability testing documentation for 2021, 2022, and 2023 to the Department.
 
06/15/2023 7066 SNC-B 3.5 Electronic and mechanical release detection not installed, calibrated, operated and maintained per manufacturer's specifications. Install and maintain proper release detection for the storage tank and provide pictures of the device to Department.
 
06/15/2023 7002 Minor 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Update the storage tank registration (provided) at this time, and contact tankregistration@floridadep.gov for assistance if necessary. Cc: Vincent.Shanberg@floridaDEP.gov
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/12/1992   COMPLETED 8 PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE