Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Local Government | ||||
County | Pinellas | Status | OPEN | ||||
ID | 9045769 | Latitude | 27° 52' 30.3664 | ||||
Name |
PINELLAS CNTY SCHOOL BD-POWNALL 11111 S BELCHER RD |
Longitude | 82° 44' 30.5468 | ||||
LARGO, FL 33773 | LL Method | DPHO | |||||
Contact | ALBERTO SANDOVAL / TIM CAUGHEY | LL Status | REVIEWED | ||||
Phone | (727) 638-3378 | Status Date | 02/09/2004 | ||||
Account Owner Information | |||||||
Name | PINELLAS CNTY SCHOOL BD 11111 S BELCHER RD LARGO, FL 33773 |
Effective Date | 01/30/1990 | ||||
Contact | TIM CAUGHEY | ||||||
Phone | (727) 638-2119 | ||||||
CAUGHEYT@PCSB.ORG | |||||||
Placard # / Date | 687045 - 06/12/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 10000 | Vehicular Diesel (D) | 10/01/1989 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 10000 | Vehicular Diesel (D) | 10/01/1989 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 10000 | Unleaded Gas (B) | 10/01/1989 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
4 | 650 | Waste Oil (L) | 12/01/1996 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(6) External piping monitoring (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 07/01/2023 | 07/01/2024 | LIBERTY SURPLUS INSURANCE CORPORATION | ||||
INSURANCE | 07/01/2022 | 07/01/2023 | LIBERTY SURPLUS INSURANCE CORPORATION | ||||
INSURANCE | 07/01/2021 | 07/01/2022 | LIBERTY SURPLUS INSURANCE CORP | ||||
INSURANCE | 07/01/2020 | 07/01/2021 | LIBERTY SURPLUS INSURANCE CORP | ||||
INSURANCE | 07/01/2019 | 07/01/2020 | ACE AMERICAN INSURANCE COMPANY | ||||
INSURANCE | 07/01/2018 | 07/01/2019 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2017 | 07/01/2018 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2016 | 07/01/2017 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2015 | 07/01/2016 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2014 | 07/01/2015 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2013 | 07/01/2014 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2012 | 07/01/2013 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2011 | 07/01/2012 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2010 | 07/01/2011 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2009 | 07/01/2010 | COMMERCE & INDUSTRY | ||||
INSURANCE | 07/01/2008 | 07/01/2009 | COMMERCE & INDUSTRY | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
LTR | 09/27/2005 | 10/04/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
IRFR | 09/06/2005 | 10/04/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes LIQUID DETECTOR ALARM | |||||||
NCLI | 06/20/2005 | 06/21/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
NCLI | 06/20/2005 | 06/21/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 06/06/2005 | 06/21/2005 | MINOR OUT-OF-COMPLIANCE | FRAZIER | 1/3 | COMPLIANCE ASSURANCE | |
TIN | 06/06/2005 | 06/20/2005 | MINOR OUT-OF-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |
Completion Notes NEW STP SUMPS, PUMP AND FILL RISERS INSTALLED | |||||||
LTR | 04/15/2005 | 04/15/2005 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes "IN ACCORDANCE WITH" LETTER ISSUED AFTER CONSULTATION WITH STAFF OF PINCHD CLEANUP SECTION. | |||||||
DSNR | 04/15/2005 | 04/15/2005 | SOWERS | 0/0 | DISCHARGE PROJECT | ||
Completion Notes DETERMINED AFTER CONSULTATION WITH STAFF OF THE PINELLAS CHD CLEANUP STAFF. | |||||||
RRBD | 02/17/2005 | 04/15/2005 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes SUBMITTAL OF CLOSURE REPORT WITH ASSESSMENT; REVIEW ASSISSTANCE BY BONNIE BERGEN OF CLEANUP SECTION. | |||||||
DRFR | 02/15/2005 | 04/15/2005 | SOWERS | 0/0 | DISCHARGE PROJECT | ||
Completion Notes DRF RECEIVED IN CLOSURE ASSESSMENT REPORT | |||||||
IRFR | 01/14/2005 | 06/02/2005 | ROGGELIN | 0/1 | DISCHARGE PROJECT | ||
Completion Notes L-3 TANK #3 REGULAR UNLEADED (SENSOR DEFINITION APPEARS TO HAVE CHANGED) | |||||||
IRFR | 11/29/2004 | 06/02/2005 | ROGGELIN | 0/1 | DISCHARGE PROJECT | ||
Completion Notes L-3 TANK #3 REGULAR UNLEADED (NOTE: SENSOR DEFINITION APPEARS TO HAVE CHANGED) | |||||||
IRFR | 08/03/2004 | 06/02/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes L-1 REG UNLEADED TANK INTERSTICE ALARM & L-4 MIDGRADE SUMP ALARM. BASED ON DATA SUBMITTED: 8/3/04 ALARMS ON L-1, L-2, L-4, L-5, & L-6. ON 8/4/04 ALARMS ON L-2, L-5, & L-6. UNLEADED TANK APPEARS TO HAVE RCVD STORMWATER (24" PRODUCT & 8" WATER) | |||||||
RRBD | 07/29/2004 | 06/02/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes LETTER & RECEIPTS INDICATING BOTH DIESEL TANKS HAD PRODUCT REMOVED BY A & S OIL CO. | |||||||
RRBD | 07/29/2004 | 06/02/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes NORRIS & SAMON REPLACED REGULAR INTERSTICE DUAL FLOAT SENSOR | |||||||
IRFR | 07/27/2004 | 06/02/2005 | ROGGELIN | 0/1 | DISCHARGE PROJECT | ||
Completion Notes DISCOVERY DATE 7/26/04 - OPERATOR ATTEMPTS TO REMOVE WATER FROM L-1 REGULAR INTERSTICE | |||||||
RRBD | 07/26/2004 | 06/02/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes FACILITY LETTER CONCERNING DIESEL OUT-OF-SERVICE; INCLUDES 7/22/04 TANK & LINE TIGHTNESS TEST DATA | |||||||
IRFR | 07/22/2004 | 06/02/2005 | ROGGELIN | 0/2 | DISCHARGE PROJECT | ||
Completion Notes MULTIPLE INFS: L-2 DIESEL #1 INTERSTICE & L-3 (APPEARS TO BE TEST OF SENSOR) | |||||||
IRFR | 07/21/2004 | 06/02/2005 | ROGGELIN | 0/3 | DISCHARGE PROJECT | ||
Completion Notes MULTIPLE INFS: 6/2/04 (L-1 REGULAR INTERSTICE & L-2 DIESEL INTERSTICE); 6/3/04 (INTERSTICE ALARM); 6/8/04 (L-1 & L-2) - APPEARS TO BE CONTINUOUS ALARM EVENTS | |||||||
IRFR | 07/21/2004 | 06/02/2005 | ROGGELIN | 0/3 | DISCHARGE PROJECT | ||
Completion Notes MULTIPLE INFS: 7/3/04 (WATER PUMPED FROM DIESEL AND GAS SUMP AND TANK INTERSTICE); 7/14/04 (L-2 DIESEL #2 INTERSTICE LOW LIQUID); 7/21/04 (L-2 DIESEL & GAS, PUMPED 1600-GALS FROM SUMP & TANK INTERSTICE); 8/31/03 (L-4 TANK #3 SUMP ALARM & L-5 TANK #2 SUMP | |||||||
LTR | 07/21/2004 | 06/02/2005 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
IRFR | 07/19/2004 | 06/02/2005 | ROGGELIN | 0/2 | DISCHARGE PROJECT | ||
Completion Notes INF 7/12/04: L-2 DIESEL 1 & L-3 DIESEL 2 - TANK INTERSTICE ALARMS | |||||||
NCLI | 06/22/2004 | 06/24/2004 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 06/08/2004 | 06/24/2004 | MINOR OUT-OF-COMPLIANCE | FRAZIER | 1/3 | COMPLIANCE ASSURANCE | |
LTR | 10/14/2003 | 10/21/2003 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
IRFR | 04/29/2003 | 10/21/2003 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||
Completion Notes LIQUID IN DIESEL SUMP | |||||||
LTR | 03/03/2003 | 03/06/2003 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 02/27/2003 | 03/06/2003 | IN-COMPLIANCE | STRAUSS | 1/3 | COMPLIANCE ASSURANCE | |
Completion Notes VISUAL ON SUMPS/DISPENSERS, VEEDER ROOT TLS350 W/ SUMP & TANK INTERSTICE SENSORS, MECHANICAL LLD (FUNCTION 4/9/02). USED OIL AST DW, MANUAL CHECK | |||||||
RRBD | 04/04/2002 | 05/07/2002 | COMPLIANCE ASSURANCE | ||||
NCLI | 03/14/2002 | 03/18/2002 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 03/13/2002 | 03/18/2002 | MINOR OUT-OF-COMPLIANCE | TAM | 1/3 | COMPLIANCE ASSURANCE | |
RRBD | 08/03/2001 | 08/26/2001 | COMPLIANCE ASSURANCE | ||||
TCI | 05/16/2001 | 05/30/2001 | MINOR OUT-OF-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |
RRBD | 11/10/1999 | 11/24/1999 | PUGH | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 11/10/1999 | 11/24/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | PUGH | 0/3 | COMPLIANCE ASSURANCE | |
RRBD | 07/28/1999 | 07/28/1999 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 06/15/1999 | 06/24/1999 | MINOR OUT-OF-COMPLIANCE | SOWERS | 1/3 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Electronic Communication | 01/16/2025 | Satisfied | REIS_A | Enforcement | |||
Letter | 04/26/2024 | Satisfied | REIS_A | Enforcement | |||
Site Inspection | 11/21/2023 | Major Out of Compliance | SHOCK_E_1 | 1/3 | Routine Compliance | ||
Letter | 11/21/2023 | Satisfied | SHOCK_E_1 | Compliance Assistance | |||
Electronic Communication | 10/25/2023 | Satisfied | SHOCK_E_1 | Routine Compliance | |||
Enforcement Referral | 06/06/2023 | Accepted | COLSON_NJ_1 | Enforcement | |||
Electronic Communication | 04/17/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 04/17/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 04/17/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Record Document | 02/03/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Letter | 09/13/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 09/13/2021 | Minor Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||
Electronic Communication | 08/23/2021 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Letter | 05/28/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Record Document | 04/01/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 02/15/2019 | Minor Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||
Letter | 02/15/2019 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 02/05/2019 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Record Document | 01/23/2017 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Letter | 11/04/2016 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Site Inspection | 11/04/2016 | Minor Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||
Electronic Communication | 10/18/2016 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Incident | 01/30/2015 | Has not led to Discharge | COLSON_NJ_1 | Incident | |||
Document Management | 01/30/2015 | Complete | COLSON_NJ_1 | Incident | |||
Issue Document | 03/28/2014 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||
Site Inspection | 03/28/2014 | In Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||
Incident | 01/03/2014 | Has not led to Discharge | JUEDES_HC_1 | Incident | |||
Document Management | 10/08/2013 | Complete | JUEDES_HC_1 | Incident | |||
Document Management | 06/13/2013 | Complete | JUEDES_HC_1 | Incident | |||
Document Management | 06/13/2013 | Complete | JUEDES_HC_1 | Incident | |||
Incident | 06/13/2013 | Has not led to Discharge | JUEDES_HC_1 | Incident | |||
Incident | 02/26/2013 | Has not led to Discharge | SOWERS_JA_1 | Incident | |||
Document Management | 02/26/2013 | Complete | SOWERS_JA_1 | Incident | |||
Document Management | 02/26/2013 | Complete | SOWERS_JA_1 | Incident | |||
Site Inspection | 11/29/2012 | In Compliance | ROGGELIN_EM_1 | 1/3 | Non-Compliance | ||
Site Inspection | 10/18/2012 | Major Out of Compliance | LONGEN_JL_1 | 1/3 | Routine Compliance | ||
Letter | 10/18/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Site Inspection | 02/29/2012 | Minor Out of Compliance | LONGEN_JL_1 | 1/3 | Routine Compliance | ||
Letter | 02/29/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Incident | 02/08/2011 | Has not led to Discharge | LONGEN_JL_1 | Incident | |||
Site Inspection | 02/01/2011 | In Compliance | LONGEN_JL_1 | 1/3 | Routine Compliance | ||
Record Document | 04/16/2010 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Site Inspection | 03/24/2010 | Major Out of Compliance | LONGEN_JL_1 | 1/3 | Routine Compliance | ||
Letter | 03/24/2010 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Record Document | 02/18/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||
Letter | 01/15/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||
Site Inspection | 01/15/2009 | Minor Out of Compliance | BARNETT_JX | 1/3 | Routine Compliance | ||
Issue Document | 01/09/2009 | Satisfied | STRAUSS_RH_1 | Enforcement | |||
Record Document | 01/08/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Record Document | 12/29/2008 | Satisfied | MARSH_L | Non-Compliance | |||
Enforcement Tracking | 12/29/2008 | Closed With Enforcement | MARSH_L | Enforcement | |||
Enforcement Referral | 12/05/2008 | Accepted | MARSH_L | Enforcement | |||
Record Document | 09/10/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Enforcement Referral | 07/24/2008 | Rejected | RANDOLPH_L | Enforcement | |||
Letter | 06/13/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 06/13/2008 | Major Out of Compliance | STRAUSS_RH_1 | 1/3 | Non-Compliance | ||
Record Document | 06/12/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 04/09/2008 | Satisfied | RANDOLPH_L | Non-Compliance | |||
Site Inspection | 04/02/2008 | Major Out of Compliance | RANDOLPH_L | 2/3 | QA/QC | ||
Record Document | 03/27/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 03/11/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 02/21/2008 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 02/21/2008 | Major Out of Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||
Site Inspection | 10/27/2006 | In Compliance | FRAZIER_LA | 1/3 | Routine Compliance | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
11/20/2023 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide an updated copy of the facility's monthly visual inspection checklist to include inspection of the spill buckets and a notation to be sure to visually inspect the STP sumps at least every 6 months. | |||
11/20/2023 | 6002 | Minor | 2.1 Operator Training records not available. | Provide a Class C UST operators certificate for a current employee, and a photo of the posted unmanned facility sign indicating a number to be called in case of an emergency with the UST system, or provide a list or enough Class C UST certificates for current employee such that at least one Class A, Class B or Class C operator is always present during hours of operation. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
02/19/1998 | COMPLETED | ||||||