DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Marine/Coastal Fuel Storage
 
County Pinellas   Status    OPEN
 
ID 9046565   Latitude    27° 45' 20.3471
 
Name HARBORAGE MARINA LLC
1500 2ND ST S
Longitude    82° 38' 5.7664
  SAINT PETERSBURG, FL 33701-5506 LL Method    DPHO
 
Contact GENERAL MANAGER   LL Status    REVIEWED
 
Phone (727) 821-6347   Status Date    10/29/2003
 
Account Owner Information
 
Name MAXIMO HARBORAGE MARINA LLC
1500 2ND ST SOUTH
Saint Petersburg, FL 33701-5500
Effective Date    04/13/2000
 
Contact SHAWN DUDLEY
 
Phone (727) 821-6347
 
Email CASSELSTINE@WATERVIEWMARINAS.COM
  Placard # / Date    701713 - 10/02/2024
Property Owner Information
 
Name HARBORAGE LAND LLC
11226 Indian Trl
Dallas, TX 75229-3518
Effective Date    08/18/2015
 
Contact MARSHALL FUNK
 
Phone (727) 821-6347
 
Email HARBORAGE@WATERVIEWMARINAS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1R1 10000 Unleaded Gas (B) 06/01/1990 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(F) Double wall
(G) Pipe trench liner
(J) Pressurized piping system
(K) Dispenser liners
(L) Bulk product system
(X) No piping associated w/tank
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2R1 6000 Vehicular Diesel (D) 06/01/1990 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(F) Double wall
(G) Pipe trench liner
(J) Pressurized piping system
(K) Dispenser liners
(L) Bulk product system
(X) No piping associated w/tank
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 888 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 888 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/30/2023 05/30/2026 INDIAN HARBOR INSURANCE COMPANY
INSURANCE   05/30/2020 05/30/2023 INDIAN HARBOR INSURANCE COMPANY
INSURANCE   04/30/2017 04/30/2020 INDIAN HARBOR
INSURANCE   04/30/2014 04/30/2017 INDIAN HARBOR
INSURANCE   04/30/2011 04/30/2014 GREENWICH
INSURANCE   04/02/2008 04/02/2011 GREENWICH
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
FR 02/10/2006 02/10/2006 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RD VIOLATIONS CITED 11/10/06 CLOSED - ADDRESSED WITH ENF CASE CLOSED 7/05
 
RRBD 11/14/2005 12/06/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
NCLI 11/10/2005 11/22/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TCI 11/10/2005 11/22/2005 SIGNIFICANT OUT-OF-COMPLIANCE FRAZIER 0/2 COMPLIANCE ASSURANCE
 
SV 08/25/2005 10/18/2005 FRAZIER 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes INVESTIGATION OF COMPLAINT OF FUEL IN WATER - NO EVIDENCE OF TANK SYSTEM LEAKS
 
CCD 07/20/2005 07/25/2005 RICCI_L 0/0 COMPLIANCE ASSURANCE
 
SCOE 07/20/2005 07/25/2005 RICCI_L 0/0 COMPLIANCE ASSURANCE
 
EPI 06/13/2005 06/15/2005 REEDER_J 0/0 COMPLIANCE ASSURANCE
 
LTR 11/05/2004 11/08/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
LTR 11/05/2004 11/29/2004 BARNETT 0/0 TERMINAL FACILITY PROJECT
 
DPRI 11/04/2004 11/29/2004 IN-COMPLIANCE BARNETT 0/0 TERMINAL FACILITY PROJECT
 
TCI 11/04/2004 11/08/2004 IN-COMPLIANCE BARNETT 0/2 COMPLIANCE ASSURANCE
 
CRDE 06/11/2004 06/11/2004 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
TEQA 03/19/2004 07/01/2004 IN-COMPLIANCE RANDOLPH_L 0/0 COMPLIANCE ASSURANCE
 
RRBD 03/01/2004 04/13/2004 PINK 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO CORRECTIONS
 
RRBD 02/16/2004 03/01/2004 PINK 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SUBMITTAL OF LLD TEST RESULTS AND SENSOR TEST RESULTS - ALL O K 2/10/04
 
LTR 02/10/2004 02/11/2004 PINK 0/0 TERMINAL FACILITY PROJECT
 
NCLI 02/10/2004 02/16/2004 PINK 0/0 COMPLIANCE ASSURANCE
 
DPRI 02/09/2004 02/11/2004 IN-COMPLIANCE PINK 0/0 TERMINAL FACILITY PROJECT
 
 Completion Notes CERTIFICATE ISSUED 2/10/04
 
TCI 02/09/2004 02/16/2004 SIGNIFICANT OUT-OF-COMPLIANCE PINK 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes REMOTE FILL LINES-DW FRP; PRESSURIZED PIPING-ENVIRON DW FLEX
 
RRBD 03/04/2003 03/06/2003 COMPLIANCE ASSURANCE
 
NCLI 03/03/2003 03/06/2003 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
TCI 02/25/2003 03/06/2003 MINOR OUT-OF-COMPLIANCE STRAUSS 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes AMERON DW FRP REMOTE FILL LINES, ENVIRON DW COAX, ENVIRON STP SUMP, MECHANICAL LLD, RED JACKET PPM2000 TANK INTERSTICE W/ SENSORS
 
DPRI 02/25/2003 03/06/2003 IN-COMPLIANCE STRAUSS 0/0 TERMINAL FACILITY PROJECT
 
RRBD 06/11/2002 06/23/2002 COMPLIANCE ASSURANCE
 
RRBD 05/31/2002 06/03/2002 COMPLIANCE ASSURANCE
 
RRBD 04/23/2002 05/07/2002 COMPLIANCE ASSURANCE
 
DPRI 03/27/2002 06/14/2002 IN-COMPLIANCE TAM 0/0 TERMINAL FACILITY PROJECT
 
NCLI 03/27/2002 04/08/2002 TAM 0/0 COMPLIANCE ASSURANCE
 
TCI 03/25/2002 04/02/2002 SIGNIFICANT OUT-OF-COMPLIANCE TAM 0/2 COMPLIANCE ASSURANCE
 
DPRI 03/21/2001 03/27/2001 IN-COMPLIANCE EASTMAN_T 0/0 TERMINAL FACILITY PROJECT
 
TCI 12/20/2000 12/28/2000 IN-COMPLIANCE CASTOR 0/2 COMPLIANCE ASSURANCE
 
RRBD 04/19/2000 06/05/2000 CASTOR 0/0 COMPLIANCE ASSURANCE
 
TCI 03/23/2000 03/24/2000 MINOR OUT-OF-COMPLIANCE CASTOR 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 12/12/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Site Inspection 12/12/2024 Major Out of Compliance PUHR_NM_1 0/2 Routine Compliance
 
Letter 11/21/2024 Satisfied VIXAYO_A Enforcement
 
Enforcement Referral 03/30/2023 Accepted COLSON_NJ_1 Enforcement
 
Electronic Communication 02/10/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 02/10/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 12/09/2022 Major Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Letter 12/09/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 11/03/2022 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 10/30/2020 Major Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Letter 10/30/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 10/08/2020 Satisfied COLSON_NJ_1 Routine Compliance
 
Enforcement Tracking 10/30/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Letter 10/29/2018 Satisfied BROWNLEE_S Enforcement
 
Letter 10/23/2018 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 10/23/2018 Satisfied BROWNLEE_S Enforcement
 
Phone Conversation 10/08/2018 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 06/25/2018 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 06/01/2018 Accepted COLSON_NJ_1 Enforcement
 
Electronic Communication 05/24/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 05/24/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 02/08/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 02/08/2018 Minor Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Electronic Communication 01/22/2018 Satisfied COLSON_NJ_1 Routine Compliance
 
Issue Document 01/21/2016 Satisfied PEDIGO_L Routine Compliance
 
Issue Document 10/02/2015 Satisfied COLSON_NJ_1 Installation
 
Site Inspection 10/02/2015 In Compliance COLSON_NJ_1 0/1 Installation
 
Issue Document 10/02/2015 Satisfied COLSON_NJ_1 Closure
 
Site Inspection 10/02/2015 In Compliance COLSON_NJ_1 0/2 Closure
 
Site Inspection 09/16/2015 Minor Out of Compliance COLSON_NJ_1 0/2 Routine Compliance
 
Letter 09/16/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Phone Conversation 08/31/2015 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 11/25/2013 In Compliance STRAUSS_RH_1 0/2 Closure
 
Site Inspection 11/25/2013 In Compliance STRAUSS_RH_1 0/2 Installation
 
Issue Document 11/25/2013 Satisfied STRAUSS_RH_1 Closure
 
Site Inspection 11/22/2013 In Compliance STRAUSS_RH_1 0/2 Non-Compliance
 
Issue Document 11/22/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 11/01/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 08/16/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 08/16/2013 Minor Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Issue Document 09/06/2011 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 08/26/2011 In Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Discharge Reporting 04/05/2011 Satisfied LASHBROOK_SJ_1 Discharge
 
Site Inspection 09/02/2010 In Compliance STRAUSS_RH_1 0/2 Non-Compliance
 
Issue Document 08/13/2010 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 08/12/2010 Minor Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Letter 08/12/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Issue Document 07/26/2010 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 11/16/2009 In Compliance STRAUSS_RH_1 0/2 Non-Compliance
 
Record Document 11/16/2009 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 09/15/2009 Major Out of Compliance STRAUSS_RH_1 0/2 Routine Compliance
 
Letter 09/15/2009 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 07/23/2008 In Compliance BARNETT_JX 0/2 Routine Compliance
 
Enforcement Tracking 05/08/2008 Closed With Enforcement RANDOLPH_L Enforcement
 
Site Inspection 03/20/2008 In Compliance LONGEN_JL_1 0/2 Non-Compliance
 
Record Document 02/29/2008 Satisfied STRAUSS_RH_1 Non-Compliance
 
TCAR 02/13/2008 Satisfied STRAUSS_RH_1 Closure
 
Letter 02/13/2008 Satisfied STRAUSS_RH_1 Discharge
 
Site Inspection 01/22/2008 In Compliance MARSH_L 0/2 QA/QC
 
Enforcement Referral 01/04/2008 Accepted RANDOLPH_L Enforcement
 
Record Document 01/04/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 12/12/2007 Major Out of Compliance LONGEN_JL_1 0/2 Installation
 
Letter 12/12/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 11/30/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 11/30/2007 Major Out of Compliance LONGEN_JL_1 0/2 Closure
 
Letter 10/22/2007 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 07/31/2007 Major Out of Compliance LONGEN_JL_1 0/2 Routine Compliance
 
Letter 07/31/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/12/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. *Perform the required testing and submit documentation to this office for review.
 
12/12/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. *Repair the opening and submit a photo/documentation to this office for review.
 
12/12/2024 6062 Minor 2.5 Release detection devices not tested annually. *Perform testing of the Monitoring Panel and Sensors and submit results to this office for review.
 
12/12/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. *Submit an explanation/resolution for the two interstitial alarms and be sure to record an explanation/resolution for all future alarms.
 
12/12/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Violation resolved with the submission of passing test results dated 12/02/2024.
 
12/09/2022 6060 SNC-B 4.11 Release detection methods do not meet monitoring requirements. Establish a proper release detection method for the Diesel tank interstice. Notify this office once corrected.
 
12/09/2022 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Be sure to perform release detection inspections every month & no more than 35 days apart. Maintain records on file for at least 36 months. Begin proper inspection of the Diesel tank interstice by either repairing the electronic monitoring or gain access to perform manual checks of the interstitial space. Submit inspection results to this office for consecutive months, showing proper documentation is now being recorded.
 
12/09/2022 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair the broken pipe. Hydro test the sump following repairs. Submit work receipt(s) and post-repair test results to this office for review.
 
12/09/2022 6062 Minor 2.5 Release detection devices not tested annually. Submit current operability test results for the (4) liquid sensors and Veeder Root monitoring panel.
 
12/09/2022 6017 Minor 4.4 All incident records, including test results not kept until storage tank system closure. Submit explanations & resolution documentation for the (6) unexplained tank interstice alarms. Alternatively, have integrity tests performed on both of the tank interstices & submit results to this office.
 
12/09/2022 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Submit current test results for the (2) mechanical line leak detectors.
 
12/09/2022 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Reprogram the L4 Diesel Tank Interstice sensor. Submit resolution documentation once corrected.
 
12/09/2022 6066 Minor 4.4 Not repaired per applicable standards. Reposition the piping within the blueprint of the liner or create a means for any potential line leaks to be directed back into the under dispenser containment.
 
12/09/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Submit current integrity (vacuum) test results for the two double walled spill buckets.
 
10/30/2020 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Submit current copies of integrity (hydro) test results for the (2) STP sumps and the (2) piping transition sumps.
 
10/30/2020 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Submit the missing test results, if found. Submit current operability test results for the overfill protection devices to this office for review.
 
10/30/2020 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Submit current copies of integrity (hydro) test results for the (2) dispenser liners.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
06/05/1990   INACTIVE 6 PETROLEUM CLEANUP PARTICIPATION PROGRAM-PARTIAL