Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||
District | Northeast | Type | Retail Station | ||||
County | Baker | Status | OPEN | ||||
ID | 9046892 | Latitude | 30° 16' 52.951 | ||||
Name |
EXXON STATION-DOWNTOWN 695 W MACCLENNY AVE |
Longitude | 82° 7' 58.2624 | ||||
MACCLENNY, FL 32063-2081 | LL Method | DPHO | |||||
Contact | RICKY DAVIS | LL Status | REVIEWED | ||||
Phone | (904) 613-6023 | Status Date | 06/15/2023 | ||||
Account Owner Information | |||||||
Name | R H DAVIS OIL CO INC PO BOX 387 MACCLENNY, FL 32063-387 |
Effective Date | 08/31/1990 | ||||
Contact | RICKHARD DAVIS | ||||||
Phone | (904) 259-1999 | ||||||
MDAVIS@RHDAVISOIL.COM | |||||||
Placard # / Date | 687443 - 06/13/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 10000 | Unleaded Gas (B) | 08/01/1990 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 10000 | Ethanol E85 (9) | 08/01/1990 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 10000 | Unleaded Gas (B) | 08/01/1990 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
4 | 10000 | Vehicular Diesel (D) | 08/01/1990 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 09/24/2024 | 09/24/2025 | LIBERTY SURPLUS INSURANCE CORPORATION | ||||
INSURANCE | 09/24/2023 | 09/24/2024 | LIBERTY SURPLUS INSURANCE CORPORATION | ||||
INSURANCE | 09/24/2022 | 09/24/2023 | LIBERTY SURPLUS INSURANCE CORPORATION | ||||
INSURANCE | 09/24/2021 | 09/24/2022 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||
INSURANCE | 09/24/2020 | 09/24/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 09/24/2019 | 09/24/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 09/24/2019 | 09/24/2020 | LIBERTY SURPLUS INSURANCE CORP | ||||
INSURANCE | 09/24/2018 | 09/24/2019 | COMMERCE & INDUSTRY | ||||
INSURANCE | 09/24/2017 | 09/24/2018 | COMMERCE & INDUSTRY | ||||
INSURANCE | 09/24/2016 | 09/24/2017 | COMMERCE & INDUSTRY | ||||
INSURANCE | 09/24/2014 | 09/24/2016 | COMMERCE & INDUSTRY | ||||
INSURANCE | 04/19/2012 | 04/19/2013 | ACE | ||||
INSURANCE | 09/24/2010 | 09/24/2011 | COMMERCE & INDUSTRY | ||||
INSURANCE | 09/24/2009 | 09/24/2010 | COMMERCE & INDUSTRY | ||||
INSURANCE | 09/24/2008 | 09/24/2009 | COMMERCE & INDUSTRY | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 09/28/2005 | 10/03/2005 | IN-COMPLIANCE | MCNEIL | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 10/05/2004 | 10/11/2004 | COMPLIANCE ASSURANCE | ||||
TCI | 08/17/2004 | 08/26/2004 | MINOR OUT-OF-COMPLIANCE | VELEZ | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 09/19/2003 | 09/22/2003 | COMPLIANCE ASSURANCE | ||||
TCI | 08/12/2003 | 08/21/2003 | MINOR OUT-OF-COMPLIANCE | GODWIN | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes FAILURE TO PROPERLY COLOR CODE FILL BOXES ACCORDING TO API RP 1637. FAILURE TO REMOVE WATER COLLECTED IN STP SUMPS. | |||||||
RRBD | 12/05/2002 | 01/07/2003 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
WLI | 12/04/2002 | 12/16/2002 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
NCLI | 10/30/2002 | 11/04/2002 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
TCI | 10/28/2002 | 11/04/2002 | MINOR OUT-OF-COMPLIANCE | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 01/18/2002 | 01/29/2002 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
WLI | 12/13/2001 | 12/26/2001 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
RRBD | 12/03/2001 | 12/26/2001 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
Completion Notes RESPONSE INADEQUATE; REQUESTED MORE INFO | |||||||
NCLI | 11/09/2001 | 12/10/2001 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
TCI | 10/17/2001 | 11/07/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | TURNRE_MS | 0/4 | COMPLIANCE ASSURANCE | |
NCLI | 08/25/2000 | 08/30/2000 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
RRBD | 08/23/2000 | 10/06/2000 | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | ||
TCI | 08/23/2000 | 08/30/2000 | MINOR OUT-OF-COMPLIANCE | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | |
TCI | 08/26/1999 | 09/03/1999 | IN-COMPLIANCE | TURNER_MS | 0/4 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Site Inspection | 04/04/2025 | Major Out of Compliance | VILLEGASAVILA_OE_1 | 0/4 | Routine Compliance | ||
Letter | 04/04/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||
Electronic Communication | 02/18/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||
Letter | 03/10/2023 | Satisfied | ROBBINS_JL_1 | Compliance Assistance | |||
Electronic Communication | 03/07/2023 | Satisfied | ROBBINS_JL_1 | Compliance Assistance | |||
Letter | 03/01/2023 | Satisfied | ROBBINS_JL_1 | Compliance Assistance | |||
Site Inspection | 03/01/2023 | Minor Out of Compliance | ROBBINS_JL_1 | 0/4 | Routine Compliance | ||
Electronic Communication | 01/20/2023 | Satisfied | ROBBINS_JL_1 | Compliance Assistance | |||
Site Inspection | 06/04/2021 | Major Out of Compliance | BRANCH_BL_1 | 0/4 | Routine Compliance | ||
Letter | 06/04/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||
Electronic Communication | 06/04/2021 | Satisfied | BRANCH_BL_1 | Compliance Assistance | |||
Electronic Communication | 07/01/2020 | Satisfied | RICHARDS_JE_1 | Compliance Assistance | |||
Site Inspection | 06/26/2020 | Major Out of Compliance | MONDO_PW_1 | 0/4 | Compliance Assistance | ||
Letter | 06/26/2020 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Issue Document | 06/25/2020 | Satisfied | HARRIS_MJ | Routine Compliance | |||
Document Management | 06/11/2020 | Satisfied | HARRIS_MJ | Discharge | |||
Record Document | 06/11/2020 | Satisfied | HARRIS_MJ | Discharge | |||
Record Document | 06/11/2020 | Satisfied | HARRIS_MJ | Discharge | |||
Discharge Reporting | 06/11/2020 | Satisfied | HARRIS_MJ | Discharge | |||
Incident | 11/21/2019 | Has not led to Discharge | MONDO_PW_1 | Incident | |||
Document Management | 11/21/2019 | Satisfied | MONDO_PW_1 | Incident | |||
Letter | 11/21/2019 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Electronic Communication | 09/24/2019 | Satisfied | GREGORY_HM_1 | Compliance Assistance | |||
Letter | 09/18/2019 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Site Inspection | 09/16/2019 | Major Out of Compliance | MONDO_PW_1 | 0/4 | Routine Compliance | ||
Letter | 02/15/2019 | Satisfied | RICHARDS_JE_1 | Closure | |||
TCAR | 02/15/2019 | Satisfied | RICHARDS_JE_1 | Closure | |||
Issue Document | 02/07/2019 | Satisfied | LUNN_RJ_1 | Closure | |||
Issue Document | 02/07/2019 | Satisfied | LUNN_RJ_1 | Installation | |||
Site Inspection | 02/06/2019 | In Compliance | LUNN_RJ_1 | 0/1 | Installation | ||
Site Inspection | 01/16/2019 | In Compliance | LUNN_RJ_1 | 0/1 | Closure | ||
Enforcement Tracking | 01/12/2018 | Closed Without Enforcement | HARRIS_MJ | Enforcement | |||
Letter | 01/12/2018 | Satisfied | HARRIS_MJ | Enforcement | |||
Site Inspection | 01/08/2018 | In Compliance | MONDO_PW_1 | 0/4 | Compliance Assistance | ||
Enforcement Referral | 01/08/2018 | Accepted | RICHARDS_JE_1 | Enforcement | |||
Electronic Communication | 12/21/2017 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Phone Conversation | 12/21/2017 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Letter | 08/23/2017 | Satisfied | RICHARDS_JE_1 | Compliance Assistance | |||
Letter | 06/20/2017 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Site Inspection | 06/16/2017 | Major Out of Compliance | MONDO_PW_1 | 0/4 | Routine Compliance | ||
Electronic Communication | 06/16/2017 | Satisfied | MONDO_PW_1 | Compliance Assistance | |||
Phone Conversation | 04/27/2017 | Satisfied | MONDO_PW_1 | Routine Compliance | |||
Letter | 10/06/2015 | Satisfied | DOHANEY_T | Enforcement | |||
Enforcement Tracking | 10/05/2015 | Closed Without Enforcement | DEFALCO_L | Enforcement | |||
Record Document | 10/05/2015 | Satisfied | DOHANEY_T | Enforcement | |||
Enforcement Referral | 09/18/2015 | Accepted | DEFALCO_L | Enforcement | |||
Letter | 09/04/2015 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||
Site Inspection | 09/04/2015 | Minor Out of Compliance | SHULAW_BJ_1 | 0/4 | Non-Compliance | ||
Issue Document | 06/09/2015 | Satisfied | HOLTKAMP_JJ_1 | Non-Compliance | |||
Letter | 06/08/2015 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Record Document | 01/08/2015 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Letter | 12/26/2014 | Satisfied | SHULAW_BJ_1 | Non-Compliance | |||
Emergency Preparedness Information | 12/26/2014 | Satisfied | SHULAW_BJ_1 | Routine Compliance | |||
Site Inspection | 12/26/2014 | Minor Out of Compliance | SHULAW_BJ_1 | 0/4 | Routine Compliance | ||
Issue Document | 12/16/2014 | Satisfied | PEREA_AO_1 | Non-Compliance | |||
Letter | 12/14/2014 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Emergency Preparedness Information | 06/23/2014 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||
Letter | 06/23/2014 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Site Inspection | 06/23/2014 | Minor Out of Compliance | KASSEES_RP_1 | 0/4 | Routine Compliance | ||
Record Document | 05/10/2013 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Issue Document | 03/12/2013 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||
Record Document | 03/12/2013 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Site Inspection | 03/12/2013 | Major Out of Compliance | KASSEES_RP_1 | 0/4 | Routine Compliance | ||
Letter | 03/12/2013 | Satisfied | KASSEES_RP_1 | Non-Compliance | |||
Emergency Preparedness Information | 02/26/2013 | Satisfied | KASSEES_RP_1 | Routine Compliance | |||
Record Document | 08/15/2011 | Satisfied | LUBINSKI_D | Installation | |||
Issue Document | 03/31/2011 | Satisfied | MCNEIL_AP_1 | Routine Compliance | |||
Site Inspection | 03/31/2011 | In Compliance | MCNEIL_AP_1 | 0/4 | Routine Compliance | ||
Issue Document | 09/23/2010 | Satisfied | LUBINSKI_D | Non-Compliance | |||
Record Document | 09/23/2010 | Satisfied | LUBINSKI_D | Non-Compliance | |||
Site Inspection | 08/17/2010 | Major Out of Compliance | LUBINSKI_D | 0/1 | Installation | ||
Site Inspection | 04/05/2010 | In Compliance | MCNEIL_AP_1 | 0/4 | Routine Compliance | ||
Site Inspection | 01/22/2009 | In Compliance | MCNEIL_AP_1 | 0/4 | Routine Compliance | ||
Site Inspection | 02/05/2008 | In Compliance | MCNEIL_AP_1 | 0/4 | Non-Compliance | ||
Letter | 01/14/2008 | Satisfied | MCNEIL_AP_1 | Non-Compliance | |||
Site Inspection | 01/14/2008 | Minor Out of Compliance | MCNEIL_AP_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 05/23/2007 | Satisfied | MCNEIL_AP_1 | Routine Compliance | |||
Emergency Preparedness Information | 02/16/2007 | Satisfied | MCNEIL_AP_1 | Routine Compliance | |||
Site Inspection | 11/27/2006 | In Compliance | MCNEIL_AP_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 09/29/2006 | Satisfied | MCNEIL_AP_1 | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
04/02/2025 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | The facility must submit an Incident Notification Form (INF). The responsible party must determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. | |||
04/02/2025 | 6062 | Minor | 2.5 Release detection devices not tested annually. | The responsible party must conduct operability testing of the interstitial sensor of each tank. Four sensors in total (Regular, Premium, Non-Ethanol, and Diesel). After testing, the passing results must be provided. | |||
04/02/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | The responsible party must repair/replace faulty components on the premium single-walled spill bucket. Additionally, the responsible party must investigate the issue and determine if a release might have occurred. Resolution documentation and passing integrity testing results must be provided. Sampling may be required. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
09/23/2019 | INACTIVE | JORDAN_S | |||||