Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/23/2025 Last Data Refresh: 02/22/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Retail Station | ||||||||
County | Broward | Status | OPEN | ||||||||
ID | 9046902 | Latitude | 26° 18' 36.8352 | ||||||||
Name |
MOBIL-COCO CREEK #716 6600 N HWY 7 |
Longitude | 80° 12' 6.3806 | ||||||||
POMPANO BEACH, FL 33073-3617 | LL Method | DPHO | |||||||||
Contact | DAVID KLEIN | LL Status | REVIEWED | ||||||||
Phone | (772) 321-7181 | Status Date | 12/29/2003 | ||||||||
Account Owner Information | |||||||||||
Name | 6600 NSR-7 REALTY LLC 23311 MIRABELLA CIRCLE N BOCA RATON, FL 33433 |
Effective Date | 12/20/2013 | ||||||||
Contact | DAVID KLEIN | ||||||||||
Phone | (772) 321-7181 | ||||||||||
JOEYSTANGG@AOL.COM | |||||||||||
Placard # / Date | 703155 - 10/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | 6600 NSR-7 REALTY LLC 23311 MIRABELLA CIRCLE N BOCA RATON, FL 33433 |
Effective Date | 12/20/2013 | ||||||||
Contact | DAVID KLEIN | ||||||||||
Phone | (772) 321-7181 | ||||||||||
JOEYSTANGG@AOL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Unleaded Gas (B) | 02/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 02/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 10000 | Unleaded Gas (B) | 02/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 10000 | Vehicular Diesel (D) | 02/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 4000 | Other Non Regulated (Z) | 02/01/1991 | UNDERGROUND | Deleted - Data Error (D) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass |
(F) Double wall | (8) Manually sampled wells (H) Mechanical line leak detector |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | CONSOLIDATED | ||||||||||
INSURANCE | 11/13/2024 | 11/13/2025 | CRUM & FORSTER SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 11/13/2022 | 11/13/2023 | CRUM & FORSTER INDEMNITY COMPANY | ||||||||
INSURANCE | 11/13/2021 | 11/13/2022 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 11/13/2021 | 11/13/2022 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 11/13/2019 | 11/13/2020 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 12/13/2015 | 12/13/2016 | CONSOLIDATED | ||||||||
INSURANCE | 12/03/2012 | 12/03/2013 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 04/30/2011 | 04/30/2012 | ILLINOIS UNION | ||||||||
INSURANCE | 04/30/2010 | 04/30/2011 | ANCON INSURANCE CO INC | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 05/01/2009 | 04/30/2010 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 10/06/2005 | IN-COMPLIANCE | MARTINEZ_J | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/17/2004 | 09/17/2004 | IN-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCI | 08/28/2003 | 08/29/2003 | IN-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCR | 03/25/2003 | 04/04/2003 | IN-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCI | 02/06/2003 | 02/24/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCI | 04/10/2002 | 04/12/2002 | IN-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCR | 03/26/2001 | 04/04/2001 | IN-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
TCI | 02/07/2001 | 02/28/2001 | MINOR OUT-OF-COMPLIANCE | MARTINEZ_J | 0/5 | COMPLIANCE ASSURANCE | |||||
TCR | 05/12/2000 | 05/30/2000 | IN-COMPLIANCE | JOHNSON_LJ | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 05/08/2000 | 05/23/2000 | MINOR OUT-OF-COMPLIANCE | JOHNSON_LJ | 0/4 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 01/21/2025 | Satisfied | HAMILTON_TP | Compliance Assistance | |||||||
Site Inspection | 01/21/2025 | Major Out of Compliance | HAMILTON_TP | 0/4 | Routine Compliance | ||||||
Phone Conversation | 01/02/2025 | Satisfied | HAMILTON_TP | Routine Compliance | |||||||
Electronic Communication | 12/27/2024 | Satisfied | HAMILTON_TP | Routine Compliance | |||||||
Phone Conversation | 12/27/2024 | Satisfied | HAMILTON_TP | Routine Compliance | |||||||
Enforcement Tracking | 12/15/2023 | Closed Without Enforcement | KOENIG_EJ_1 | Enforcement | |||||||
Letter | 10/23/2023 | Satisfied | GRAJEDACARDENAS_CJ_1 | Compliance Assistance | |||||||
Record Document | 10/23/2023 | Satisfied | GRAJEDACARDENAS_CJ_1 | Compliance Assistance | |||||||
Record Document | 10/20/2023 | Satisfied | GRAJEDACARDENAS_CJ_1 | Compliance Assistance | |||||||
Enforcement Referral | 02/07/2023 | Accepted | KOENIG_EJ_1 | Enforcement | |||||||
Record Document | 11/17/2022 | Satisfied | GRAJEDACARDENAS_CJ_1 | Compliance Assistance | |||||||
Letter | 07/25/2022 | Satisfied | GRAJEDACARDENAS_CJ_1 | Compliance Assistance | |||||||
Site Inspection | 07/25/2022 | Major Out of Compliance | GRAJEDACARDENAS_CJ_1 | 0/4 | Routine Compliance | ||||||
Electronic Communication | 07/25/2022 | Satisfied | GRAJEDACARDENAS_CJ_1 | Routine Compliance | |||||||
Record Document | 12/17/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Letter | 12/17/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Letter | 05/04/2021 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Site Inspection | 05/04/2021 | Major Out of Compliance | SCOTT_DC_1 | 0/4 | Routine Compliance | ||||||
Phone Conversation | 04/16/2021 | Satisfied | SCOTT_DC_1 | Routine Compliance | |||||||
Enforcement Tracking | 02/04/2020 | Closed Without Enforcement | GOMEZ_AE_1 | Enforcement | |||||||
Site Inspection | 02/04/2020 | In Compliance | JEANBAPTISTE_C_1 | 0/4 | Compliance Assistance | ||||||
Letter | 02/04/2020 | Satisfied | JEANBAPTISTE_C_1 | Routine Compliance | |||||||
Electronic Communication | 01/08/2020 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Electronic Communication | 01/08/2020 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Enforcement Referral | 11/20/2019 | Accepted | GOMEZ_AE_1 | Enforcement | |||||||
Electronic Communication | 11/19/2019 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Phone Conversation | 11/19/2019 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Letter | 11/14/2019 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Meeting | 11/14/2019 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Electronic Communication | 04/02/2018 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Site Inspection | 02/28/2018 | Major Out of Compliance | JEANBAPTISTE_C_1 | 0/4 | Routine Compliance | ||||||
Letter | 02/28/2018 | Satisfied | JEANBAPTISTE_C_1 | Compliance Assistance | |||||||
Electronic Communication | 02/22/2018 | Satisfied | JEANBAPTISTE_C_1 | Routine Compliance | |||||||
Electronic Communication | 12/27/2017 | Satisfied | JEANBAPTISTE_C_1 | Routine Compliance | |||||||
Phone Conversation | 02/24/2016 | Satisfied | JEANBAPTISTE_C_1 | Non-Compliance | |||||||
Site Inspection | 02/24/2016 | In Compliance | JEANBAPTISTE_C_1 | 0/4 | Routine Compliance | ||||||
Electronic Communication | 02/23/2016 | Satisfied | JEANBAPTISTE_C_1 | Non-Compliance | |||||||
Meeting | 02/23/2016 | Satisfied | JEANBAPTISTE_C_1 | Non-Compliance | |||||||
Site Inspection | 10/22/2013 | In Compliance | MARTINEZ_JA_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 10/22/2013 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Site Inspection | 04/23/2012 | In Compliance | MARTINEZ_JA_1 | 0/4 | Closure | ||||||
Emergency Preparedness Information | 01/18/2012 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Site Inspection | 01/18/2012 | In Compliance | MARTINEZ_JA_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 03/16/2011 | Satisfied | SINGER_SD_1 | Routine Compliance | |||||||
Site Inspection | 03/16/2011 | In Compliance | SINGER_SD_1 | 0/4 | Routine Compliance | ||||||
Document Management | 07/20/2010 | Complete | GOMEZ_AE_1 | Discharge | |||||||
Site Inspection | 09/14/2009 | In Compliance | MARTINEZ_JA_1 | 0/4 | Non-Compliance | ||||||
Emergency Preparedness Information | 09/11/2009 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Letter | 09/11/2009 | Satisfied | MARTINEZ_JA_1 | Non-Compliance | |||||||
Site Inspection | 09/11/2009 | Major Out of Compliance | MARTINEZ_JA_1 | 0/4 | Routine Compliance | ||||||
Site Inspection | 12/04/2008 | In Compliance | MARTINEZ_JA_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 12/04/2008 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
TCAR | 07/25/2008 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Site Inspection | 04/14/2008 | In Compliance | MARTINEZ_JA_1 | 0/4 | Installation | ||||||
Site Inspection | 03/25/2008 | In Compliance | MARTINEZ_JA_1 | 0/4 | Closure | ||||||
Letter | 02/20/2008 | Satisfied | DRICE_GK_1 | Discharge | |||||||
Site Inspection | 10/11/2007 | In Compliance | MARTINEZ_JA_1 | 0/5 | Routine Compliance | ||||||
Emergency Preparedness Information | 10/11/2007 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Issue Document | 06/21/2007 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
TCAR | 06/21/2007 | Satisfied | GOMEZ_AE_1 | Closure | |||||||
Record Document | 05/09/2007 | Satisfied | DRICE_GK_1 | Discharge | |||||||
Emergency Preparedness Information | 02/08/2007 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 02/06/2007 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
Site Inspection | 02/03/2007 | In Compliance | MARTINEZ_JA_1 | 0/5 | Discharge | ||||||
Site Inspection | 01/24/2007 | In Compliance | MARTINEZ_JA_1 | 0/5 | Installation | ||||||
Site Inspection | 01/22/2007 | In Compliance | MARTINEZ_JA_1 | 0/5 | Closure | ||||||
Letter | 11/16/2006 | Satisfied | MARTINEZ_JA_1 | Non-Compliance | |||||||
Site Inspection | 11/07/2006 | Major Out of Compliance | MARTINEZ_JA_1 | 0/5 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | MARTINEZ_JA_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/21/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | At least once a month, but not exceeding 35 days, every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances that can be inspected visually shall be visually inspected and documented. Conduct complete visual inspections of the tank system, including the fill sumps. Send January and February visual inspection reports to tahamilton@broward.org. | |||||||
01/21/2025 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Complete Part P (Certificate of Financial Responsibility) of insurance policy and send a copy to tahamilton@broward.org. | |||||||
01/21/2025 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Make the necessary repairs so that all fill sumps have sensors. All sensors must be operational and monitored by the Veeder Root. Send a picture of the Liquid or Sensor status report indicating the presence of all fill sump sensors to tahamilton@broward.org. | |||||||
01/21/2025 | 6002 | Minor | 2.1 Operator Training records not available. | Obtain Class A, B and C Operator training certificates for owners and operators of the gas station. There must be one person on site at all times with atleast a Class C operator training certification. Send copies of training certificates to tahamilton@broward.org. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/23/1991 | COMPLETED | 49 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||