DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/23/2025        Last Data Refresh: 02/22/2025        Report Generated from DOPPLER
 
District Southeast   Type    Retail Station
 
County Broward   Status    OPEN
 
ID 9046902   Latitude    26° 18' 36.8352
 
Name MOBIL-COCO CREEK #716
6600 N HWY 7
Longitude    80° 12' 6.3806
  POMPANO BEACH, FL 33073-3617 LL Method    DPHO
 
Contact DAVID KLEIN   LL Status    REVIEWED
 
Phone (772) 321-7181   Status Date    12/29/2003
 
Account Owner Information
 
Name 6600 NSR-7 REALTY LLC
23311 MIRABELLA CIRCLE N
BOCA RATON, FL 33433
Effective Date    12/20/2013
 
Contact DAVID KLEIN
 
Phone (772) 321-7181
 
Email JOEYSTANGG@AOL.COM
  Placard # / Date    703155 - 10/28/2024
Property Owner Information
 
Name 6600 NSR-7 REALTY LLC
23311 MIRABELLA CIRCLE N
BOCA RATON, FL 33433
Effective Date    12/20/2013
 
Contact DAVID KLEIN
 
Phone (772) 321-7181
 
Email JOEYSTANGG@AOL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 02/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 02/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 02/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
4 10000 Vehicular Diesel (D) 02/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 4000 Other Non Regulated (Z) 02/01/1991 UNDERGROUND Deleted - Data Error (D)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
  (F) Double wall (8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   CONSOLIDATED
INSURANCE   11/13/2024 11/13/2025 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   11/13/2022 11/13/2023 CRUM & FORSTER INDEMNITY COMPANY
INSURANCE   11/13/2021 11/13/2022 CRUM & FORSTER INDEMNITY
INSURANCE   11/13/2021 11/13/2022 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   11/13/2019 11/13/2020 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   12/13/2015 12/13/2016 CONSOLIDATED
INSURANCE   12/03/2012 12/03/2013 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   04/30/2011 04/30/2012 ILLINOIS UNION
INSURANCE   04/30/2010 04/30/2011 ANCON INSURANCE CO INC
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2009 04/30/2010
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 10/06/2005 IN-COMPLIANCE MARTINEZ_J 0/4 COMPLIANCE ASSURANCE
 
TCI 09/17/2004 09/17/2004 IN-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCI 08/28/2003 08/29/2003 IN-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCR 03/25/2003 04/04/2003 IN-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCI 02/06/2003 02/24/2003 SIGNIFICANT OUT-OF-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCI 04/10/2002 04/12/2002 IN-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCR 03/26/2001 04/04/2001 IN-COMPLIANCE COMPLIANCE ASSURANCE
 
TCI 02/07/2001 02/28/2001 MINOR OUT-OF-COMPLIANCE MARTINEZ_J 0/5 COMPLIANCE ASSURANCE
 
TCR 05/12/2000 05/30/2000 IN-COMPLIANCE JOHNSON_LJ 0/4 COMPLIANCE ASSURANCE
 
TCI 05/08/2000 05/23/2000 MINOR OUT-OF-COMPLIANCE JOHNSON_LJ 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 01/21/2025 Satisfied HAMILTON_TP Compliance Assistance
 
Site Inspection 01/21/2025 Major Out of Compliance HAMILTON_TP 0/4 Routine Compliance
 
Phone Conversation 01/02/2025 Satisfied HAMILTON_TP Routine Compliance
 
Electronic Communication 12/27/2024 Satisfied HAMILTON_TP Routine Compliance
 
Phone Conversation 12/27/2024 Satisfied HAMILTON_TP Routine Compliance
 
Enforcement Tracking 12/15/2023 Closed Without Enforcement KOENIG_EJ_1 Enforcement
 
Letter 10/23/2023 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Record Document 10/23/2023 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Record Document 10/20/2023 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Enforcement Referral 02/07/2023 Accepted KOENIG_EJ_1 Enforcement
 
Record Document 11/17/2022 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Letter 07/25/2022 Satisfied GRAJEDACARDENAS_CJ_1 Compliance Assistance
 
Site Inspection 07/25/2022 Major Out of Compliance GRAJEDACARDENAS_CJ_1 0/4 Routine Compliance
 
Electronic Communication 07/25/2022 Satisfied GRAJEDACARDENAS_CJ_1 Routine Compliance
 
Record Document 12/17/2021 Satisfied SCOTT_DC_1 Compliance Assistance
 
Letter 12/17/2021 Satisfied SCOTT_DC_1 Compliance Assistance
 
Letter 05/04/2021 Satisfied SCOTT_DC_1 Compliance Assistance
 
Site Inspection 05/04/2021 Major Out of Compliance SCOTT_DC_1 0/4 Routine Compliance
 
Phone Conversation 04/16/2021 Satisfied SCOTT_DC_1 Routine Compliance
 
Enforcement Tracking 02/04/2020 Closed Without Enforcement GOMEZ_AE_1 Enforcement
 
Site Inspection 02/04/2020 In Compliance JEANBAPTISTE_C_1 0/4 Compliance Assistance
 
Letter 02/04/2020 Satisfied JEANBAPTISTE_C_1 Routine Compliance
 
Electronic Communication 01/08/2020 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Electronic Communication 01/08/2020 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Enforcement Referral 11/20/2019 Accepted GOMEZ_AE_1 Enforcement
 
Electronic Communication 11/19/2019 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Phone Conversation 11/19/2019 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Letter 11/14/2019 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Meeting 11/14/2019 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Electronic Communication 04/02/2018 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Site Inspection 02/28/2018 Major Out of Compliance JEANBAPTISTE_C_1 0/4 Routine Compliance
 
Letter 02/28/2018 Satisfied JEANBAPTISTE_C_1 Compliance Assistance
 
Electronic Communication 02/22/2018 Satisfied JEANBAPTISTE_C_1 Routine Compliance
 
Electronic Communication 12/27/2017 Satisfied JEANBAPTISTE_C_1 Routine Compliance
 
Phone Conversation 02/24/2016 Satisfied JEANBAPTISTE_C_1 Non-Compliance
 
Site Inspection 02/24/2016 In Compliance JEANBAPTISTE_C_1 0/4 Routine Compliance
 
Electronic Communication 02/23/2016 Satisfied JEANBAPTISTE_C_1 Non-Compliance
 
Meeting 02/23/2016 Satisfied JEANBAPTISTE_C_1 Non-Compliance
 
Site Inspection 10/22/2013 In Compliance MARTINEZ_JA_1 0/4 Routine Compliance
 
Emergency Preparedness Information 10/22/2013 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Site Inspection 04/23/2012 In Compliance MARTINEZ_JA_1 0/4 Closure
 
Emergency Preparedness Information 01/18/2012 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Site Inspection 01/18/2012 In Compliance MARTINEZ_JA_1 0/4 Routine Compliance
 
Emergency Preparedness Information 03/16/2011 Satisfied SINGER_SD_1 Routine Compliance
 
Site Inspection 03/16/2011 In Compliance SINGER_SD_1 0/4 Routine Compliance
 
Document Management 07/20/2010 Complete GOMEZ_AE_1 Discharge
 
Site Inspection 09/14/2009 In Compliance MARTINEZ_JA_1 0/4 Non-Compliance
 
Emergency Preparedness Information 09/11/2009 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Letter 09/11/2009 Satisfied MARTINEZ_JA_1 Non-Compliance
 
Site Inspection 09/11/2009 Major Out of Compliance MARTINEZ_JA_1 0/4 Routine Compliance
 
Site Inspection 12/04/2008 In Compliance MARTINEZ_JA_1 0/4 Routine Compliance
 
Emergency Preparedness Information 12/04/2008 Satisfied MARTINEZ_JA_1 Routine Compliance
 
TCAR 07/25/2008 Satisfied GOMEZ_AE_1 Closure
 
Site Inspection 04/14/2008 In Compliance MARTINEZ_JA_1 0/4 Installation
 
Site Inspection 03/25/2008 In Compliance MARTINEZ_JA_1 0/4 Closure
 
Letter 02/20/2008 Satisfied DRICE_GK_1 Discharge
 
Site Inspection 10/11/2007 In Compliance MARTINEZ_JA_1 0/5 Routine Compliance
 
Emergency Preparedness Information 10/11/2007 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Issue Document 06/21/2007 Satisfied GOMEZ_AE_1 Closure
 
TCAR 06/21/2007 Satisfied GOMEZ_AE_1 Closure
 
Record Document 05/09/2007 Satisfied DRICE_GK_1 Discharge
 
Emergency Preparedness Information 02/08/2007 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied MARTINEZ_JA_1 Routine Compliance
 
Site Inspection 02/03/2007 In Compliance MARTINEZ_JA_1 0/5 Discharge
 
Site Inspection 01/24/2007 In Compliance MARTINEZ_JA_1 0/5 Installation
 
Site Inspection 01/22/2007 In Compliance MARTINEZ_JA_1 0/5 Closure
 
Letter 11/16/2006 Satisfied MARTINEZ_JA_1 Non-Compliance
 
Site Inspection 11/07/2006 Major Out of Compliance MARTINEZ_JA_1 0/5 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied MARTINEZ_JA_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
01/21/2025 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. At least once a month, but not exceeding 35 days, every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances that can be inspected visually shall be visually inspected and documented. Conduct complete visual inspections of the tank system, including the fill sumps. Send January and February visual inspection reports to tahamilton@broward.org.
 
01/21/2025 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. Complete Part P (Certificate of Financial Responsibility) of insurance policy and send a copy to tahamilton@broward.org.
 
01/21/2025 6066 Minor 4.4 Not repaired per applicable standards. Make the necessary repairs so that all fill sumps have sensors. All sensors must be operational and monitored by the Veeder Root. Send a picture of the Liquid or Sensor status report indicating the presence of all fill sump sensors to tahamilton@broward.org.
 
01/21/2025 6002 Minor 2.1 Operator Training records not available. Obtain Class A, B and C Operator training certificates for owners and operators of the gas station. There must be one person on site at all times with atleast a Class C operator training certification. Send copies of training certificates to tahamilton@broward.org.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/23/1991   COMPLETED 49 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE