DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/23/2025        Last Data Refresh: 02/22/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 9102159   Latitude    27° 45' 23.5068
 
Name STETSON UNIV-COLLEGE OF LAW
1401 S 61ST ST
Longitude    82° 43' 7.9407
  GULFPORT, FL 33707 LL Method    DPHO
 
Contact BEAU HOWELLS   LL Status    REVIEWED
 
Phone (727) 562-7328   Status Date    08/04/2006
 
Account Owner Information
 
Name STETSON UNIVERSITY
1401 S 61ST ST
GULFPORT, FL 33707
Effective Date    05/29/1991
 
Contact PATTY JOHNSON
 
Phone (727) 562-7847
 
Email BHOWELLS@LAW.STETSON.EDU
  Placard # / Date    702493 - 10/23/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
5 2000 Emerg Generator Diesel (G) 09/01/2015 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
4 2000 Emerg Generator Diesel (G) 10/01/2000 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 888 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 888 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 888 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/01/2020 06/01/2021 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   06/01/2019 06/01/2020 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2018 05/13/2019 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2017 05/13/2018 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2016 05/13/2017 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2015 05/13/2016 CRUM & FORSTER INDEMNITY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 02/20/2025 Major Out of Compliance PUHR_NM_1 1/0 Routine Compliance
 
Electronic Communication 02/20/2025 Satisfied PUHR_NM_1 Routine Compliance
 
Letter 11/10/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 11/10/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 05/17/2021 Major Out of Compliance COLSON_NJ_1 1/0 Routine Compliance
 
Letter 05/17/2021 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 04/01/2021 Satisfied COLSON_NJ_1 Routine Compliance
 
Enforcement Tracking 02/05/2019 Closed Without Enforcement WESTERVELT_H Enforcement
 
Enforcement Referral 02/05/2019 Accepted COLSON_NJ_1 Enforcement
 
Record Document 02/01/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 02/01/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 01/29/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 01/29/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 10/31/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 10/31/2018 Major Out of Compliance COLSON_NJ_1 1/0 Routine Compliance
 
Phone Conversation 10/01/2018 Satisfied COLSON_NJ_1 Routine Compliance
 
Issue Document 04/21/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 04/21/2016 In Compliance COLSON_NJ_1 1/0 Routine Compliance
 
Electronic Communication 03/29/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
Record Document 10/29/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 10/09/2015 Major Out of Compliance COLSON_NJ_1 1/0 Installation
 
Letter 10/09/2015 Satisfied COLSON_NJ_1 Closure
 
TCAR 10/09/2015 Satisfied COLSON_NJ_1 Closure
 
Letter 10/09/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 10/08/2015 Minor Out of Compliance COLSON_NJ_1 1/0 Closure
 
Letter 10/08/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Record Document 08/05/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Record Document 07/20/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 05/28/2015 Major Out of Compliance COLSON_NJ_1 1/0 Non-Compliance
 
Letter 05/28/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 03/24/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 03/24/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 03/24/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 03/24/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Letter 02/05/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Letter 12/05/2014 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 12/05/2014 Major Out of Compliance COLSON_NJ_1 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/20/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Violation resolved with the testing of the Kreuger Level Gauge during this inspection (2/6/2025).
 
02/20/2025 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. *Submit the missing FR from 06/01/2021 to current to this office.
 
02/20/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. *Investigate the Rupture Basin Alarm System and test for operability every 12 months.
 
 
 
No Discharges Found