DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pasco   Status    OPEN
 
ID 9102582   Latitude    28° 13' 2.5284
 
Name NEW PORT RICHEY FOOD MART
8549 OLD COUNTY ROAD 54
Longitude    82° 40' 22.1328
  NEW PORT RICHEY, FL 34653-6463 LL Method    DPHO
 
Contact SONG TANG   LL Status    REVIEWED
 
Phone (727) 375-8536   Status Date    08/31/2003
 
Account Owner Information
 
Name SONG TANG
8549 OLD CR 54, ---
NEW PORT RICHEY, FL 34653-6463
Effective Date    01/01/2017
 
Contact
 
Phone (267) 972-4481
 
Email NEWPORTRICHEYFOODMART@GMAIL.COM
  Placard # / Date    682799 - 06/05/2024
Property Owner Information
 
Name ST LUCKY V LLC
8549 OLD COUNTY ROAD 54
NEW PORT RICHEY, FL 34653-6463
Effective Date    12/22/2016
 
Contact SONG TANG
 
Phone (267) 972-4481
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 06/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Vehicular Diesel (D) 06/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 06/01/1991 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   02/06/2019 02/06/2020 BEAZLEY GROUP
INSURANCE   12/12/2016 12/12/2017 COMMERCE & INDUSTRY
INSURANCE   12/10/2016 12/10/2017 COMMERCE & INDUSTRY
INSURANCE   12/10/2015 12/10/2016 COMMERCE & INDUSTRY
INSURANCE   12/09/2014 12/09/2015 COMMERCE & INDUSTRY
INSURANCE   12/09/2013 12/09/2014 COMMERCE & INDUSTRY
INSURANCE   12/09/2012 12/09/2013 COMMERCE & INDUSTRY
INSURANCE   12/09/2011 12/09/2012 COMMERCE & INDUSTRY
INSURANCE   12/09/2010 12/09/2011 COMMERCE & INDUSTRY
INSURANCE   12/09/2009 12/09/2010 COMMERCE & INDUSTRY
INSURANCE   12/09/2006 12/09/2007 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
NCLI 05/01/2006 05/01/2006 CONDOLEON, G J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 2ND NCLI FROM 2/21/06 INSP. DATE
 
RRBD 03/07/2006 03/17/2006 CONDOLEON, G J 0/0 COMPLIANCE ASSURANCE
 
NCLI 02/27/2006 CONDOLEON, G J 0/0 COMPLIANCE ASSURANCE
 
TCI 02/21/2006 SIGNIFICANT OUT-OF-COMPLIANCE CONDOLEON, G J 0/3 COMPLIANCE ASSURANCE
 
NCLI 02/25/2005 03/15/2005 RODRIGUEZ, IVAN 0/3 COMPLIANCE ASSURANCE
 
TCI 02/22/2005 03/15/2005 MINOR OUT-OF-COMPLIANCE RODRIGUEZ, IVAN 0/3 COMPLIANCE ASSURANCE
 
RRBD 04/15/2004 06/24/2004 RODRIGUEZ, IVAN 0/3 COMPLIANCE ASSURANCE
 
RRBD 03/17/2004 06/14/2004 RODRIGUEZ, IVAN 0/3 COMPLIANCE ASSURANCE
 
NCLI 02/26/2004 02/26/2004 COMPLIANCE ASSURANCE
 
TCI 02/24/2004 02/26/2004 SIGNIFICANT OUT-OF-COMPLIANCE RODRIGUEZ, IVAN 0/3 COMPLIANCE ASSURANCE
 
RRBD 05/07/2003 05/21/2003 COMPLIANCE ASSURANCE
 
TCI 03/14/2003 03/21/2003 MINOR OUT-OF-COMPLIANCE HANSEN, DAVID 0/3 COMPLIANCE ASSURANCE
 
TCR 10/02/2002 10/07/2002 MINOR OUT-OF-COMPLIANCE HANSEN, DAVID 0/3 COMPLIANCE ASSURANCE
 
TCR 07/19/2002 07/25/2002 MINOR OUT-OF-COMPLIANCE HANSEN, DAVID 0/3 COMPLIANCE ASSURANCE
 
TCI 03/11/2002 03/12/2002 MINOR OUT-OF-COMPLIANCE HANSEN, DAVID 0/3 COMPLIANCE ASSURANCE
 
TCR 04/17/2001 04/25/2001 IN-COMPLIANCE HARRIS 0/3 COMPLIANCE ASSURANCE
 
NCLI 12/13/2000 12/13/2000 HARRIS 0/3 COMPLIANCE ASSURANCE
 
TCI 12/07/2000 12/13/2000 MINOR OUT-OF-COMPLIANCE HARRIS 0/3 COMPLIANCE ASSURANCE
 
NCLI 02/23/2000 05/11/2000 PETERSON 0/3 COMPLIANCE ASSURANCE
 
TCI 10/13/1999 11/09/1999 SIGNIFICANT OUT-OF-COMPLIANCE PETERSON 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 07/29/2024 Accepted TUCKER_SX_1 Enforcement
 
Enforcement Tracking 07/29/2024 Closed Without Enforcement GREEN_SM Enforcement
 
Record Document 06/13/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Electronic Communication 06/04/2024 Satisfied TUCKER_SX_1 Routine Compliance
 
Electronic Communication 06/04/2024 Satisfied TUCKER_SX_1 Routine Compliance
 
Record Document 05/31/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Record Document 05/31/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Site Inspection 05/30/2024 Major Out of Compliance TUCKER_SX_1 0/3 Routine Compliance
 
Phone Conversation 07/26/2023 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 07/12/2023 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Letter 11/29/2021 Satisfied GREEN_SM Enforcement
 
Enforcement Referral 11/09/2021 Accepted JUARISTIC_GK_1 Enforcement
 
Electronic Communication 11/05/2021 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 09/29/2021 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Letter 07/23/2021 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 07/23/2021 Major Out of Compliance JUARISTIC_GK_1 0/3 Routine Compliance
 
Electronic Communication 07/20/2021 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 07/02/2021 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Record Document 06/18/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Meeting 06/18/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Phone Conversation 06/13/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Phone Conversation 06/13/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Record Document 06/12/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 06/12/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Site Inspection 03/19/2019 Major Out of Compliance JUARISTIC_GK_1 0/3 Routine Compliance
 
Letter 03/19/2019 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 03/12/2019 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Document Management 01/06/2017 Satisfied JUARISTIC_GK_1 Discharge
 
Record Document 01/06/2017 Satisfied JUARISTIC_GK_1 Discharge
 
Discharge Reporting 01/06/2017 Satisfied JUARISTIC_GK_1 Discharge
 
Document Management 01/06/2017 Satisfied JUARISTIC_GK_1 Discharge
 
Electronic Communication 01/03/2017 Satisfied JUARISTIC_GK_1 Non-Compliance
 
TCAR 12/23/2016 Satisfied JUARISTIC_GK_1 Closure
 
Letter 12/23/2016 Satisfied JUARISTIC_GK_1 Closure
 
Letter 12/21/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 12/21/2016 Minor Out of Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Electronic Communication 12/01/2016 Satisfied JUARISTIC_GK_1 Closure
 
Electronic Communication 12/01/2016 Satisfied JUARISTIC_GK_1 Closure
 
Phone Conversation 12/01/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 11/10/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Record Document 10/26/2016 Satisfied JUARISTIC_GK_1 Installation
 
Record Document 10/26/2016 Satisfied JUARISTIC_GK_1 Closure
 
Site Inspection 10/12/2016 Major Out of Compliance JUARISTIC_GK_1 0/3 Installation
 
Letter 10/12/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 09/28/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 09/28/2016 Major Out of Compliance JUARISTIC_GK_1 0/3 Closure
 
Phone Conversation 09/23/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 09/23/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 09/23/2016 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Site Inspection 07/22/2016 Major Out of Compliance JUARISTIC_GK_1 0/3 Routine Compliance
 
Letter 07/22/2016 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Electronic Communication 07/05/2016 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Electronic Communication 01/29/2015 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 01/29/2015 In Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Meeting 01/09/2015 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 12/17/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Record Document 12/08/2014 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Letter 12/05/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 12/04/2014 Major Out of Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Site Inspection 10/07/2014 Minor Out of Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Letter 10/07/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 09/17/2014 Minor Out of Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Letter 09/17/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 09/09/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 09/09/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Record Document 06/09/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 06/03/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Site Inspection 06/03/2014 Major Out of Compliance JUARISTIC_GK_1 0/3 Non-Compliance
 
Site Inspection 03/25/2014 Major Out of Compliance JUARISTIC_GK_1 0/3 Routine Compliance
 
Letter 03/25/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Electronic Communication 03/25/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 01/29/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Phone Conversation 01/29/2014 Satisfied JUARISTIC_GK_1 Non-Compliance
 
Letter 04/05/2013 Satisfied SOWERS_JA_1 Non-Compliance
 
Site Inspection 04/05/2013 Minor Out of Compliance SOWERS_JA_1 0/3 Routine Compliance
 
Letter 04/19/2012 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 04/19/2012 Minor Out of Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Emergency Preparedness Information 04/18/2012 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Record Document 03/18/2011 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Letter 02/18/2011 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 02/18/2011 Major Out of Compliance CONDOLEON_GJ_1 0/3 Non-Compliance
 
Site Inspection 12/17/2010 In Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Letter 12/17/2010 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Emergency Preparedness Information 12/17/2010 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Enforcement Tracking 03/24/2010 Closed With Enforcement MEETZE_A Enforcement
 
Emergency Preparedness Information 01/28/2010 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Site Inspection 01/28/2010 In Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Record Document 10/08/2009 Satisfied MEETZE_A Enforcement
 
Phone Conversation 10/01/2009 Satisfied MEETZE_A Enforcement
 
Meeting 09/18/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Record Document 08/31/2009 Satisfied MEETZE_A Enforcement
 
Meeting 08/31/2009 Satisfied MEETZE_A Enforcement
 
Phone Conversation 08/24/2009 Satisfied MEETZE_A Enforcement
 
Enforcement Referral 08/03/2009 Accepted MEETZE_A Enforcement
 
Record Document 06/16/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Record Document 05/22/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Letter 05/14/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Record Document 05/12/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 05/06/2009 Major Out of Compliance MEETZE_A 0/3 QA/QC
 
Letter 05/06/2009 Satisfied MEETZE_A Non-Compliance
 
Letter 04/09/2009 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Emergency Preparedness Information 04/09/2009 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Site Inspection 04/09/2009 Major Out of Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Record Document 04/29/2008 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Record Document 04/07/2008 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 03/19/2008 Major Out of Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Letter 03/19/2008 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Letter 01/10/2007 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
Site Inspection 01/10/2007 Minor Out of Compliance CONDOLEON_GJ_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/28/2006 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Meeting 09/28/2006 Satisfied CONDOLEON_GJ_1 Routine Compliance
 
Record Document 06/19/2006 Satisfied CONDOLEON_GJ_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/14/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide test results for (3) UDC's and (3) STP sumps due 4/8/22.
 
05/14/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Ensure document release detection “Electronic Monitoring” by pulling liquid status tapes monthly not to exceed 35 days. This violation will be resolved with the issuance of a compliance assistance offer letter.
 
05/13/2024 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Provide documentation of financial responsibility for the past 3 years dating back to 7/23/21.
 
07/23/2021 4041 SNC-B 4.18 Shear valve not installed properly. This violation may lead to Placard Revocation and Delivery Prohibition. Provide a manufacturer statement that this is an acceptable repair. If the manufacturer doesn't accept this repair, replace the shear valve in UDC 3/4.
 
07/23/2021 4067 Minor 4.2 Release detection devices not tested annually. Test the L4 sensor and submit the test results to this office.
 
07/23/2021 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. Provide proof of FR, with required FR Part Forms.
 
07/23/2021 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Investigate the High Liquid Alarm and determine if a discharge has occurred. If the RUL tank requires repair but cannot be repaired within 90 days, the tank shall be taken out-of-service. If the system cannot be repaired within 365 days after being taken out-of-service, it shall be permanently closed.
 
07/23/2021 4001 Minor 2.2 Operator certification requirements not met. Owners and operators of underground storage tank system facilities must maintain required training certification documentation. Provide Class A/B and C training certificates.
 
07/23/2021 4019 Minor 2.3 All incident records, including test results not kept until storage tank system closure. All alarms must be investigated. The results must be maintained and made available at the time of the routine compliance inspection.
 
07/23/2021 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Investigate the High Liquid Alarm and determine if a discharge has occurred. Submit an Incident Notification Form.
 
07/23/2021 4012 Minor 2.3 For an incident, notification not received in a timely manner. A record of alarms, investigation results, and resolutions shall be maintained for all alarms. All alarms are an incident and shall be investigated within 24-hours, to determine if a discharge has occurred. Notification of the discovery of any incident shall be made to the county on an INF within 72 hours of the discovery. In cases where an INF is required to be submitted, the investigation shall be completed within 14 days of the date of discovery of the incident. Provide an explanation and resolution for the above documented fuel/sensor out/high liquid/low liquid alarms.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
10/10/2016   COMPLETED 30