Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Local Government | ||||||||
County | Desoto | Status | OPEN | ||||||||
ID | 9103119 | Latitude | 27° 13' 1.8857 | ||||||||
Name |
ARCADIA CITY-TYSON WWTP 223 S PARKER AVE |
Longitude | 81° 52' 25.8542 | ||||||||
ARCADIA, FL 34266 | LL Method | DPHO | |||||||||
Contact | STEVE UNDERWOOD | LL Status | REVIEWED | ||||||||
Phone | (863) 990-0907 | Status Date | 08/29/2003 | ||||||||
Account Owner Information | |||||||||||
Name | ARCADIA CITY 223 S PARKER AVE Arcadia, FL 34266 |
Effective Date | 10/17/1991 | ||||||||
Contact | STEVE UNDERWOOD | ||||||||||
Phone | (863) 990-0907 | ||||||||||
WWTP@ARCADIA-FL.GOV | |||||||||||
Placard # / Date | 698487 - 07/02/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | ARCADIA CITY 223 S PARKER AVE Arcadia, FL 34266 |
Effective Date | 10/17/1991 | ||||||||
Contact | STEVE UNDERWOOD | ||||||||||
Phone | (863) 990-0907 | ||||||||||
WWTP@ARCADIA-FL.GOV | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
21038 | 4000 | Emerg Generator Diesel (G) | 07/30/2021 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (I) Double wall (M) Spill containment bucket (W) Built on supports |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(J) Monitor piping/liner space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 550 | Waste Oil (L) | 08/01/1991 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (C) Fiberglass (F) Double wall |
(F) Monitor dbl wall tank space (G) Electronic line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Emerg Generator Diesel (G) | 08/01/1991 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (C) Fiberglass (F) Double wall |
(F) Monitor dbl wall tank space (G) Electronic line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 1500 | Hazardous Substance (T) | 01/01/2001 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(K) AST containment (M) Spill containment bucket (Y) Polyethylene |
(D) External protective coating (L) Bulk product system (N) Approved synthetic material (P) Internal pipe/internal sump riser |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (Q) Visual inspection of ASTs (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 150 | Waste Oil (L) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 3000 | Fuel Oil - Onsite Heat (M) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (I) Not required | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 04/22/2022 | 04/09/2023 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2020 | 04/09/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2019 | 04/09/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2018 | 04/09/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2017 | 04/09/2018 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2016 | 04/09/2017 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 04/09/2014 | 04/09/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 04/09/2011 | 04/09/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 01/20/2000 | 04/09/2010 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCR | 02/21/2006 | 03/07/2006 | IN-COMPLIANCE | DURRANCE_W | 1/1 | COMPLIANCE ASSURANCE | |||||
TCI | 09/20/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | DURRANCE_W | 1/2 | COMPLIANCE ASSURANCE | ||||||
RRBD | 02/14/2005 | 03/07/2005 | IN-COMPLIANCE | HARRISON_BL | 1/2 | COMPLIANCE ASSURANCE | |||||
TCI | 01/25/2005 | 02/03/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | HARRISONBL | 1/2 | COMPLIANCE ASSURANCE | |||||
RRBD | 12/01/2003 | 12/01/2003 | COMPLIANCE ASSURANCE | ||||||||
TCI | 11/24/2003 | 11/24/2003 | MINOR OUT-OF-COMPLIANCE | KEENE_K | 1/2 | COMPLIANCE ASSURANCE | |||||
TCI | 12/16/2002 | 01/06/2003 | IN-COMPLIANCE | KEENE_K | 2/1 | COMPLIANCE ASSURANCE | |||||
TCI | 01/29/2002 | 01/30/2002 | MINOR OUT-OF-COMPLIANCE | KEENE_K | 1/2 | COMPLIANCE ASSURANCE | |||||
TCI | 12/14/2000 | 12/19/2000 | IN-COMPLIANCE | KEENE_K | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 01/20/1999 | 05/12/1999 | IN-COMPLIANCE | JOYCE_T | 0/1 | COMPLIANCE ASSURANCE | |||||
UTCI | 06/12/1997 | 06/13/1997 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 11/06/2024 | Accepted | PARKS_J_4 | Enforcement | |||||||
Phone Conversation | 08/16/2022 | Satisfied | PARKS_J_4 | Routine Compliance | |||||||
Site Inspection | 08/16/2022 | Major Out of Compliance | PARKS_J_4 | 1/0 | Routine Compliance | ||||||
Letter | 06/03/2022 | Satisfied | KLEINMANN_K_1 | Compliance Assistance | |||||||
Site Inspection | 09/09/2020 | Major Out of Compliance | SAUTTER_MA_2 | 0/2 | Routine Compliance | ||||||
Letter | 07/17/2018 | Satisfied | ZIMMERMAN_CA_1 | Routine Compliance | |||||||
Site Inspection | 07/16/2018 | In Compliance | ZIMMERMAN_CA_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 07/29/2016 | In Compliance | ZIMMERMAN_CA_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 07/08/2014 | In Compliance | ZIMMERMAN_CA_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 10/06/2011 | In Compliance | DURRANCE_WK_1 | 0/2 | Closure | ||||||
Site Inspection | 06/21/2011 | In Compliance | DURRANCE_WK_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 09/22/2009 | In Compliance | DURRANCE_WK_1 | 1/2 | Routine Compliance | ||||||
Letter | 09/30/2008 | Satisfied | DURRANCE_WK_1 | Non-Compliance | |||||||
Site Inspection | 09/30/2008 | Minor Out of Compliance | DURRANCE_WK_1 | 1/2 | Routine Compliance | ||||||
Site Inspection | 09/26/2007 | In Compliance | DURRANCE_WK_1 | 1/2 | Routine Compliance | ||||||
Letter | 11/15/2006 | Satisfied | DURRANCE_WK_1 | Non-Compliance | |||||||
Site Inspection | 10/27/2006 | Minor Out of Compliance | DURRANCE_WK_1 | 1/4 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
08/16/2022 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | An AST was installed without notification or testing. FDEP to determine corrective actions. | |||||||
08/16/2022 | 7082 | SNC-A | 3.6 Piping that is damaged which has caused a discharge is not replaced. | Corroded pipe fittings are leaking diesel onto the soil. The piping is highly corroded. Replace or repair the fittings and the pipes. | |||||||
08/16/2022 | 7018 | SNC-A | 3.8 Actions not taken immediately to contain, remove, and abate the discharge. | Petroleum impacted soil surrounds the area where the leaking pip fittings are located. FDEP to determine corrective actions. | |||||||
08/16/2022 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | The Krueger leak gauge showed at leak at the time of inspection. FDEP to determine corrective actions. | |||||||
08/16/2022 | 7005 | Minor | 1.5 Notification of installation, closure, or change in service status not received in required timeframes. | An Underground tank was removed without notification or a TCAR and an AST was installed without notification. | |||||||
No Discharges Found |