Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Pasco | Status | OPEN | ||||||||
ID | 9103522 | Latitude | 28° 15' 29.949 | ||||||||
Name |
FADI MALKI INC 6927 LITTLE RD |
Longitude | 82° 40' 28.9271 | ||||||||
NEW PORT RICHEY, FL 34655-1011 | LL Method | DGPS | |||||||||
Contact | FADI MALKI | LL Status | REVIEWED | ||||||||
Phone | (727) 842-8666 | Status Date | 09/22/2003 | ||||||||
Account Owner Information | |||||||||||
Name | FADI MALKI INC 6927 LITTLE RD NEW PORT RICHEY, FL 34655 |
Effective Date | 12/15/2009 | ||||||||
Contact | FADI MALKI | ||||||||||
Phone | (727) 842-8666 | ||||||||||
FADIMALKI@VERIZON.NET | |||||||||||
Placard # / Date | 682200 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | FADI MALKI INC 6927 LITTLE RD NEW PORT RICHEY, FL 34655 |
Effective Date | 12/15/2009 | ||||||||
Contact | FADI MALKI | ||||||||||
Phone | (727) 842-8666 | ||||||||||
FADIMALKI@VERIZON.NET | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 12000 | Unleaded Gas (B) | 11/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 12000 | Unleaded Gas (B) | 11/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 12000 | Unleaded Gas (B) | 11/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 03/13/2021 | 03/13/2022 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/13/2020 | 03/13/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/13/2019 | 03/13/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/13/2018 | 03/13/2019 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/13/2017 | 03/13/2018 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 07/16/2012 | 07/16/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/16/2011 | 07/16/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/16/2010 | 07/16/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 12/02/2009 | 07/16/2010 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 02/28/2007 | 02/28/2008 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 03/24/2006 | CONDOLEON, G J | 0/0 | COMPLIANCE ASSURANCE | |||||||
NCLI | 02/14/2006 | 02/14/2006 | CONDOLEON, G J | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCR | 02/08/2006 | 02/14/2006 | IN COMPLIANCE | CONDOLEON, G J | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes SAME VIOLATIONS EXIST FROM 12/15/05 TCI | |||||||||||
TCI | 12/15/2005 | MINOR OUT-OF-COMPLIANCE | CONDOLEON, G J | 0/4 | COMPLIANCE ASSURANCE | ||||||
TCI | 12/02/2004 | 12/23/2004 | MINOR OUT-OF-COMPLIANCE | RODRIGUEZ, IVAN | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 09/10/2003 | 09/26/2003 | MINOR OUT-OF-COMPLIANCE | RODRIGUEZ, IVAN | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 05/17/2003 | 05/22/2003 | IN-COMPLIANCE | HANSEN, DAVID | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 11/27/2002 | 12/06/2002 | COMPLIANCE ASSURANCE | ||||||||
TCI | 10/21/2002 | 10/23/2002 | MINOR OUT-OF-COMPLIANCE | HANSEN, DAVID | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 09/24/2001 | 09/28/2001 | IN-COMPLIANCE | HANSEN | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 12/22/2000 | 12/27/2000 | IN-COMPLIANCE | HARRIS | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 10/18/2000 | 10/18/2000 | HARRIS | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/13/2000 | 10/18/2000 | MINOR OUT-OF-COMPLIANCE | HARRIS | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 09/02/1999 | 09/10/1999 | MINOR OUT-OF-COMPLIANCE | PETERSON | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 02/19/1999 | 03/23/1999 | PETERSON_JE | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/16/1999 | 03/23/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | PETERSON_JE | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 06/19/2024 | Accepted | JUARISTIC_GK_1 | Enforcement | |||||||
Site Inspection | 05/30/2024 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Record Document | 05/17/2024 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Phone Conversation | 05/17/2024 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Phone Conversation | 05/16/2024 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Phone Conversation | 05/16/2024 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Meeting | 05/16/2024 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Electronic Communication | 05/15/2024 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Enforcement Tracking | 12/09/2022 | Closed Without Enforcement | PEDIGO_L | Enforcement | |||||||
Site Inspection | 03/23/2022 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/23/2022 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Electronic Communication | 03/07/2022 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Letter | 12/04/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Site Inspection | 12/04/2019 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 10/28/2019 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Incident | 08/09/2019 | Has not led to Discharge | LASHBROOK_SJ_1 | Incident | |||||||
Phone Conversation | 05/26/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Letter | 05/10/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 05/10/2017 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 04/12/2017 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Site Inspection | 04/20/2015 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Letter | 04/20/2015 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 06/11/2014 | Major Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Letter | 06/11/2014 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Phone Conversation | 05/07/2014 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Enforcement Referral | 10/17/2013 | Accepted | PEDIGO_L | Enforcement | |||||||
Letter | 09/18/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 11/01/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 11/01/2012 | Major Out of Compliance | LONGEN_JL_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 10/10/2012 | Major Out of Compliance | LONGEN_JL_1 | 0/3 | Non-Compliance | ||||||
Letter | 10/10/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 10/09/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 10/09/2012 | Major Out of Compliance | LONGEN_JL_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 01/17/2012 | Minor Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 01/17/2012 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 01/12/2012 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Record Document | 02/28/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/22/2011 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Record Document | 02/17/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Record Document | 02/17/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Letter | 02/09/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Meeting | 01/06/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Record Document | 01/06/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 12/01/2010 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 12/01/2010 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Enforcement Tracking | 12/18/2009 | Closed Without Enforcement | MEETZE_A | Enforcement | |||||||
Letter | 12/16/2009 | Satisfied | MAGUIRE_KG_1 | Non-Compliance | |||||||
Site Inspection | 12/16/2009 | Minor Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Record Document | 12/16/2009 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Phone Conversation | 10/09/2009 | Satisfied | MEETZE_A | Enforcement | |||||||
Issue Document | 08/17/2009 | Satisfied | MEETZE_A | Enforcement | |||||||
Issue Document | 04/10/2009 | Satisfied | MEETZE_A | Enforcement | |||||||
Enforcement Referral | 03/05/2009 | Accepted | MEETZE_A | Enforcement | |||||||
Emergency Preparedness Information | 11/19/2008 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 11/19/2008 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Site Inspection | 11/19/2008 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 11/19/2008 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 11/15/2007 | Minor Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 11/15/2007 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 11/13/2007 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Meeting | 03/29/2007 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Letter | 03/05/2007 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Meeting | 02/23/2007 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/13/2007 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Meeting | 01/19/2007 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Meeting | 12/28/2006 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Record Document | 11/20/2006 | Satisfied | CONDOLEON_GJ_1 | Discharge | |||||||
Letter | 11/20/2006 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 11/20/2006 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Letter | 08/22/2006 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Record Document | 08/22/2006 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 06/16/2006 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/3 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/23/2024 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Provide last three years of release detection records to this office. | |||||||
05/23/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide the last three years of release detection records, and the next two consecutive months to this office. | |||||||
05/23/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Provide integrity test results for the STP/piping sumps, UDCs, and DW spill buckets. Shall be tested at least once every 36 months. | |||||||
05/23/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Properly conduct an integrity test on all three spill buckets. | |||||||
05/23/2024 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Immediately obtain financial responsibility. | |||||||
05/23/2024 | 6079 | SNC-B | 4.10 USTs not closed with 90 days of discovery, or not meeting requirements, unable to be repaired or no FR. | A storage tank system where financial responsibility is not maintained and demonstrated, pursuant to Rule 62-761.420, F.A.C., within 90 days of termination of the financial mechanism, must be permanently closed. Immediately provide proof of financial responsibility, or permanently close all three tanks. | |||||||
05/23/2024 | 6076 | Minor | 4.7 Requirements not met for out-of-service systems. | Register the tank out-of-service as soon as the other out-of-service requirements are met. Remove all regulated substances so that no more than one inch in depth or 0.3 percent by weight of regulated substances remains in the storage tank. | |||||||
05/23/2024 | 6002 | Minor | 2.1 Operator Training records not available. | Provide proof of certification to this office. | |||||||
05/23/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide test results for all release detection devices (line leak detectors, liquid sensors/monitoring panel, and OPW VisiGauges) and overfill protection devices (flow shut-off valves). Shall be tested annually. | |||||||
05/23/2024 | 6029 | Minor | 4.1 Any component(s) of the storage tank system not installed according to manufacturer's instructions. | The sensors were adjusted at the time of inspection. Violation resolved with the issue of a non-compliance letter. | |||||||
05/23/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove and dispose of the free product in UDC 3/4 and 9/10. | |||||||
05/23/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Repair the leaks and properly remove and dispose of the free product in UDC 3/4 and 9/10. | |||||||
05/23/2024 | 6079 | SNC-B | 4.10 USTs not closed with 90 days of discovery, or not meeting requirements, unable to be repaired or no FR. | A storage tank system that fails to meet the Storage Tank System Requirements of Rule 62-761.500, F.A.C., within 90 days of discovery must be permanently closed. Permanently close FDEP Tank ID 2 (87 North Silver). Tank FDEP Tank ID 3 out-of-service, and investigate fuel in tank interstice. | |||||||
05/23/2024 | 6023 | Minor | 4.1 Secondary containment or integral piping not installed to allow for monitoring point. | Provide a monitoring point for the DW piping interstice in each sump. | |||||||
05/23/2024 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | During hours of operation, facilities must have at least one certified operator (either a Class A, Class B, or Class C operator) present at the facility. Ensure store employees onsite are trained and certified with at least a Class C UST Operator Training Certificate. Provide proof of certification to this office. | |||||||
05/23/2024 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Use the API Color-Symbol System to identify the substances (regular (low-grade 87 octane) gas) stored in the 87 South Blue tank. | |||||||
No Discharges Found |