DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southeast   Type    County Government
 
County Miami-Dade   Status    OPEN
 
ID 9200477   Latitude    25° 46' 32.7903
 
Name DADE CNTY COURTHOUSE CENTER
175 NW 1ST AVE
Longitude    80° 11' 41.6799
  MIAMI, FL 33130 LL Method    DPHO
 
Contact ROBBEN HARDUARSINGH   LL Status    REVIEWED
 
Phone (305) 349-5505   Status Date    05/27/2003
 
Account Owner Information
 
Name MIAMI DADE CNTY-GSA
175 NW 1ST AVE #152
MIAMI, FL 33128
Effective Date    06/26/2002
 
Contact ROBBEN HARDUARSINGH
 
Phone (305) 349-5505
 
Email JCIZQ@MIAMIDADE.GOV
  Placard # / Date    667934 - 07/10/2023
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
2 2500 Emerg Generator Diesel (G) 09/01/1998 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
  (B) Steel/galvanized metal
(I) Suction piping system
(M) Double wall - pipe jacket
(F) Monitor dbl wall tank space
(I) Not required
(K) Monitor dbl wall pipe space
(N) Groundwater monitoring
 
 
Tank Tank Size Content Installed Placement Status
1 550 Emerg Generator Diesel (G) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass   (B) Steel/galvanized metal (I) Not required
(N) Groundwater monitoring
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2024 01/31/2025
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2023 01/31/2024
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2022 01/31/2023
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2021 01/31/2022
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2018 01/31/2019
LOCAL GOVERNMENTS - BOND RATING TEST   05/05/2015 05/05/2016
LOCAL GOVERNMENTS - BOND RATING TEST   02/05/2013 02/05/2014
LOCAL GOVERNMENTS - FINANCIAL TEST   11/21/2005 11/20/2006
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 11/15/2004 12/11/2004 IN-COMPLIANCE BUSEN_K 0/1 COMPLIANCE ASSURANCE
 
CWOE 06/05/2003 06/06/2003 JENNIFER SMITH 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/05/2003 06/06/2003 JENNIFER SMITH 0/0 COMPLIANCE ASSURANCE
 
TCI 04/29/2003 05/23/2003 SIGNIFICANT OUT-OF-COMPLIANCE JENNIFER SMITH/NICOLE KUEHLE 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 10/16/2024 Accepted SABIR_A Enforcement
 
Site Inspection 09/25/2024 Major Out of Compliance SABIR_A 0/1 Routine Compliance
 
Electronic Communication 05/21/2024 Satisfied SABIR_A Routine Compliance
 
Electronic Communication 10/19/2021 Satisfied WILLIAMS_CEW Routine Compliance
 
Electronic Communication 10/19/2021 Satisfied WILLIAMS_CEW Routine Compliance
 
Letter 10/19/2021 Satisfied WILLIAMS_CEW Compliance Assistance
 
Letter 09/17/2021 Satisfied LANDFIELD_J Routine Compliance
 
Electronic Communication 09/16/2021 Satisfied WILLIAMS_CEW Routine Compliance
 
Site Inspection 06/21/2021 Major Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Phone Conversation 08/09/2018 Satisfied WILLIAMS_CEW Routine Compliance
 
Letter 08/08/2018 Satisfied WILLIAMS_CEW Compliance Assistance
 
Site Inspection 06/27/2018 Minor Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Site Inspection 09/14/2015 In Compliance BROWN_SE 0/1 Routine Compliance
 
Phone Conversation 09/03/2015 Satisfied BROWN_SE Routine Compliance
 
Site Inspection 01/03/2014 In Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Letter 03/13/2013 Satisfied WILLIAMS_CEW Non-Compliance
 
Site Inspection 03/07/2013 Minor Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Phone Conversation 04/04/2012 Satisfied WILLIAMS_CEW Routine Compliance
 
Letter 10/26/2010 Satisfied WILLIAMS_CEW Non-Compliance
 
Site Inspection 10/26/2010 Minor Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Record Document 07/26/2010 Satisfied JACKSON_ME Routine Compliance
 
Letter 11/23/2009 Satisfied JACKSON_ME Non-Compliance
 
Site Inspection 11/19/2009 Major Out of Compliance JACKSON_ME 0/1 Routine Compliance
 
Site Inspection 04/17/2007 Minor Out of Compliance WHITE_CM 0/1 Routine Compliance
 
Record Document 04/16/2007 Satisfied WHITE_CM Routine Compliance
 
Issue Document 04/16/2007 Satisfied WHITE_CM Routine Compliance
 
Record Document 03/09/2007 Satisfied QURESHI_SA Non-Compliance
 
Letter 02/27/2007 Satisfied QURESHI_SA Non-Compliance
 
Record Document 02/27/2007 Satisfied QURESHI_SA Non-Compliance
 
Site Inspection 07/09/2006 Major Out of Compliance BARATH_J 0/2 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/21/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Submit the integrity testing for the overspill containment sump dated after 8/7/2021.
 
05/21/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide the integrity test for the piping containment sump dated after 8/7/2021.
 
05/08/2024 6002 Minor 2.1 Operator Training records not available. Submit the operator training certificate for the designated person(s) at the facility in accordance with 62-761.350 Operator Training and Certification. 62-761.350 Operator Training and Certification. (1) Owners or operators shall identify and designate for each in-service underground storage tank system facility, including unmanned facilities, at least one named individual for each class of operator – Class A, Class B, and Class C. All individuals designated as a Class A, B or C operator shall, at a minimum, be trained and certified in accordance with this rule.
 
04/30/2024 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Complete an Incident Notification Form and conduct investigation to determine the source and cause of the apparent release. Keep the document as a part of the storage tank system's permanent records.
 
04/30/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Provide the annual operability overfill protection testing for the storage tank dated after 8/7/2021, 2022, and 2023.
 
04/30/2024 6062 Minor 2.5 Release detection devices not tested annually. Provide the release detection operability testing for the storage tank dated after 8/7/2021,2022, and 2023.
 
 
 
No Discharges Found