Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | County Government | ||||||||
County | Broward | Status | OPEN | ||||||||
ID | 9203081 | Latitude | 26° 7' 23.0102 | ||||||||
Name |
BROWARD CNTY-W REGNL COURTHOUSE 100 N PINE ISLAND RD |
Longitude | 80° 15' 44.9348 | ||||||||
PLANTATION, FL 33324 | LL Method | DPHO | |||||||||
Contact | HAL DONOVAN | LL Status | REVIEWED | ||||||||
Phone | (954) 336-7685 | Status Date | 12/10/2003 | ||||||||
Account Owner Information | |||||||||||
Name | BROWARD CNTY BD OF COMMISSIONERS 115 S ANDREWS AVE #501RP Fort Lauderdale, FL 33301-1801 |
Effective Date | 12/08/1992 | ||||||||
Contact | SCOTT CAMPBELL | G BARRASSO 954-357-5535 | ||||||||||
Phone | (954) 357-6470 | ||||||||||
SCAMPBELL@BROWARD.ORG | |||||||||||
Placard # / Date | 678152 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | BROWARD CNTY BD OF COMMISSIONERS 115 S ANDREWS AVE #501RP Fort Lauderdale, FL 33301-1801 |
Effective Date | 12/08/1992 | ||||||||
Contact | SCOTT CAMPBELL | G BARRASSO 954-357-5535 | ||||||||||
Phone | (954) 357-6470 | ||||||||||
SCAMPBELL@BROWARD.ORG | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 550 | Emerg Generator Diesel (G) | 11/01/1991 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (M) Double wall - pipe jacket |
(I) Not required (N) Groundwater monitoring |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 287 | Other Non Regulated (Z) | 11/01/1991 | UNDERGROUND | NonReg De-mimimus (Z) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(B) Steel/galvanized metal (M) Double wall - pipe jacket |
(I) Not required (N) Groundwater monitoring |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/01/2024 | 10/01/2025 | IRONSHORE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/27/2023 | 12/27/2025 | INDIAN HARBOR INSURANCE COMPANY | ||||||||
INSURANCE | 09/28/2021 | 09/28/2023 | INDIAN HARBOR INSURANCE COMPANY | ||||||||
INSURANCE | 09/28/2017 | 09/28/2019 | INDIAN HARBOR INSURANCE COMPANY | ||||||||
INSURANCE | 09/28/2015 | 09/28/2016 | INDIAN HARBOR INSURANCE COMPANY | ||||||||
INSURANCE | 09/28/2012 | 09/28/2013 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 09/28/2011 | 09/28/2012 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 09/28/2010 | 09/28/2011 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 09/28/2009 | 09/28/2010 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 06/28/2007 | 06/30/2008 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 02/28/1994 | 02/28/1997 | PLUS | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/18/2006 | IN-COMPLIANCE | HUMPHRIES_F | 0/2 | COMPLIANCE ASSURANCE | ||||||
TCI | 06/09/2005 | 06/26/2005 | IN-COMPLIANCE | BUSEN_K | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 03/18/2005 | 03/22/2005 | IN-COMPLIANCE | HUMPHRIES_F | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 05/21/2004 | 06/14/2004 | IN-COMPLIANCE | BUSEN_K | 0/2 | COMPLIANCE ASSURANCE | |||||
TCI | 03/27/2003 | 04/02/2003 | IN-COMPLIANCE | HUMPHRIES_F | 0/2 | COMPLIANCE ASSURANCE | |||||
CASV | 08/16/2000 | 08/25/2000 | HUMPHRIES_F | 0/2 | COMPLIANCE ASSURANCE | ||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 04/14/2025 | Satisfied | SABIR_A | Compliance Assistance | |||||||
Site Inspection | 02/25/2025 | Major Out of Compliance | SABIR_A | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/14/2022 | In Compliance | WILLIAMS_CEW | 0/1 | Routine Compliance | ||||||
Enforcement Referral | 03/05/2020 | Accepted | DOLAN_J | Enforcement | |||||||
Enforcement Tracking | 03/05/2020 | Closed Without Enforcement | MALONEY_D | Enforcement | |||||||
Enforcement Referral | 03/05/2020 | Cancelled | DOLAN_J | Enforcement | |||||||
Letter | 11/07/2019 | Satisfied | MALONEY_D | Compliance Assistance | |||||||
Record Document | 11/04/2019 | Satisfied | MALONEY_D | Compliance Assistance | |||||||
Letter | 06/10/2019 | Satisfied | PHIPPS_V | Compliance Assistance | |||||||
Site Inspection | 06/05/2019 | Minor Out of Compliance | PHIPPS_V | 0/2 | Routine Compliance | ||||||
Electronic Communication | 06/04/2019 | Satisfied | PHIPPS_V | Routine Compliance | |||||||
Electronic Communication | 06/04/2019 | Satisfied | PHIPPS_V | Routine Compliance | |||||||
Site Inspection | 06/23/2016 | In Compliance | DOLAN_J | 0/2 | Routine Compliance | ||||||
Site Inspection | 06/06/2013 | In Compliance | WILLIAMS_CEW | 0/2 | Routine Compliance | ||||||
Site Inspection | 02/03/2012 | In Compliance | BROWN_SE | 0/2 | Routine Compliance | ||||||
Site Inspection | 03/17/2011 | In Compliance | DOLAN_J | 0/2 | Routine Compliance | ||||||
Site Inspection | 04/27/2010 | In Compliance | WILLIAMS_CEW | 0/2 | Routine Compliance | ||||||
Site Inspection | 07/07/2008 | In Compliance | DOLAN_J | 0/2 | Routine Compliance | ||||||
Phone Conversation | 04/30/2008 | Satisfied | DOLAN_J | Routine Compliance | |||||||
Site Inspection | 04/30/2007 | In Compliance | CUBINSKI_K | 0/2 | Routine Compliance | ||||||
Site Inspection | 08/21/2006 | In Compliance | GARBEE_M | 0/2 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/17/2025 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Submit the records for the piping sump and overspill containment sump testing for Tank #1 for the years 2022, 2023, 2024 and 2025. | |||||||
02/17/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Submit the records for annual operability overfill protection testing for Tank #1 for the years 2023, 2024, and 2025. | |||||||
02/17/2025 | 6002 | Minor | 2.1 Operator Training records not available. | Submit the operator training certificates for A/B/C Operators. | |||||||
02/17/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Submit the monthly monitoring and alarm history records for Tank #1 for the years 2023, 2024, and 2025. | |||||||
02/17/2025 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Submit the records for certificate of financial responsibility for Tank #1 for the years 2023, 2024, and 2025. | |||||||
02/14/2025 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove the excess water and provide documentation for the disposal activity. | |||||||
02/14/2025 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Submit all of the records for annual operability release detection, annual operability overfill protection, piping sump integrity testing, overspill containment sump integrity testing, monthly monitoring, alarm history, operator training certificates, and certificates of financial responsibility for Tank #1 for the years 2023, 2024, and 2025. | |||||||
No Discharges Found |