District South   Type    Fuel user/Non-retail
 
County Collier   Status    OPEN
 
ID 9300394   Latitude    26° 9' 57
 
Name SUNCOAST BEVERAGE SALES LLLP
4747 PROGRESS AVE
Longitude    81° 45' 6
  NAPLES, FL 34104-7032 LL Method    AGPS
 
Contact TIM MITCHELL   LL Status    REVIEWED
 
Phone (239) 334-3520   Status Date    04/14/2003
 
Account Owner Information
 
Name SUNCOAST BEVERAGE SALES LLLP
2996 HANSON ST
FORT MYERS, FL 33916
Effective Date    08/26/2022
 
Contact TIM MITCHELL / CLAYTON HARRISON
 
Phone (941) 334-3520
 
Email CLAYTONH@SUNCOASTBEV.COM
  Placard # / Date    685389 - 06/07/2024
Property Owner Information
 
Name CMT VENTURES LLC
2996 HANSON ST
FORT MYERS, FL 33916
Effective Date    08/26/2022
 
Contact TIM MITCHELL
 
Phone (239) 334-3520
 
Email TIMM@SUNCOASTBEV.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
3 1790 Emerg Generator Diesel (G) 08/01/2015 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(N) Approved synthetic material
(F) Monitor dbl wall tank space
(R) Monitor tank bottom space
 
 
Tank Tank Size Content Installed Placement Status
1 12000 Vehicular Diesel (D) 04/01/1993 ABOVEGROUND Moved to New Site (M)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(I) Suction piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Unleaded Gas (B) 04/01/2001 ABOVEGROUND Moved to New Site (M)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
(X) Concrete
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
NONE  
INSURANCE   07/12/2018 07/12/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/12/2017 07/12/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/12/2016 07/12/2017 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/12/2015 07/12/2016 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/12/2014 07/12/2015 COMMERCE & INDUSTRY
INSURANCE   07/12/2012 07/12/2013 COMMERCE & INDUSTRY
INSURANCE   07/12/2010 07/12/2011 COMMERCE & INDUSTRY
INSURANCE   07/12/2009 07/12/2010 COMMERCE & INDUSTRY
INSURANCE   07/12/2008 07/12/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCR 01/23/2006 01/23/2006 IN-COMPLIANCE OWEN_JA 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSED #'S 2017, 2110 & 2124. DISPENSER LINERS SUFFICIENT, LEAKING SWIVEL REPLACED AND STORMWATER DRAINED FROM DIKEFIELD.
 
CWOE 01/23/2006 01/23/2006 OWEN_JA 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes FACILITY TOOK NECESSARY CORRECTIVE ACTION. TCR ON 1/23/06 CLOSED VIOLATION #'S 2017, 2110, 2124
 
TCI 10/11/2005 11/15/2005 SIGNIFICANT OUT-OF-COMPLIANCE OWEN_J 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes DISPENSER LINERS HAVE REPAIR WINDOW CUT INTO THEM, HOSE CONNECTION IS WEEPING, AND SHEEN IS PRESENT ON TOP OF THE WATER IN THE DIKE FIELD AREA.
 
TCI 11/05/2004 11/08/2004 IN-COMPLIANCE KOLANDA 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS
 
TCI 07/22/2003 07/22/2003 IN-COMPLIANCE KOLANDA 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: SW STEEL
 
TCI 07/30/2002 07/30/2002 IN-COMPLIANCE KOLANDA 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS
 
TCR 08/27/2001 08/27/2001 IN-COMPLIANCE HOGAN_S 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes ISOLATION VALVES ARE LOCATED BETWEEN TANK AND DISPENSERS.
 
CWOE 08/27/2001 08/27/2001 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSE 70/N
 
NCLI 08/06/2001 08/14/2001 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NCLI FOR 8/3/01 TCI
 
TCI 08/03/2001 08/03/2001 MINOR OUT-OF-COMPLIANCE HOGAN_S 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes 12000 GALLON TANK NEEDS ISOLATION VALVES
 
TIN 08/03/2001 08/03/2001 IN-COMPLIANCE HOGAN_S 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes ALL EQUIPMENT IS INSTALLED. TANK NEEDS MOUNTED AND ELECTRICITY NEEDS TURNED ON BEFORE FILLING TANK. ALSO TANK MUST BE ADDED TO INSURANCE POLICY.
 
TCI 08/16/2000 08/17/2000 IN-COMPLIANCE SNYDERBURN_P 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes IN COMPLIANCE
 
TCI 08/20/1999 08/26/1999 IN-COMPLIANCE SILLERY_W 1/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 09/21/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/21/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/02/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/02/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/02/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 08/26/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Enforcement Referral 04/28/2022 Accepted HERNANDEZ_N_5 Enforcement
 
Electronic Communication 03/21/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 03/01/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 01/28/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 01/04/2022 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Letter 12/10/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Site Inspection 12/10/2021 Major Out of Compliance HERNANDEZ_N_5 1/0 Routine Compliance
 
Electronic Communication 12/06/2021 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Site Inspection 12/10/2018 In Compliance BATES_TD_1 1/0 Routine Compliance
 
Letter 12/10/2018 Satisfied BATES_TD_1 Routine Compliance
 
Electronic Communication 12/06/2018 Satisfied BATES_TD_1 Routine Compliance
 
Site Inspection 08/24/2016 In Compliance BATES_TD_1 1/0 Routine Compliance
 
Site Inspection 03/29/2016 In Compliance SNYDERBURN_PJ_2 1/0 Installation
 
Site Inspection 09/07/2015 In Compliance SNYDERBURN_PJ_2 2/0 Closure
 
Site Inspection 09/26/2014 Minor Out of Compliance SPARKS_JD_1 2/0 Routine Compliance
 
Letter 09/26/2014 Satisfied SPARKS_JD_1 Non-Compliance
 
Site Inspection 02/11/2013 In Compliance SPARKS_JD_1 2/0 Routine Compliance
 
Site Inspection 05/25/2011 In Compliance SPARKS_JD_1 2/0 Routine Compliance
 
Site Inspection 06/10/2010 In Compliance NOVAK_KM_1 2/0 Routine Compliance
 
Site Inspection 05/18/2009 In Compliance SPARKS_JD_1 2/0 Routine Compliance
 
Site Inspection 04/22/2008 In Compliance POTTS_CR 2/0 Routine Compliance
 
Record Document 06/07/2007 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Letter 04/13/2007 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 04/13/2007 Minor Out of Compliance SNYDERBURN_PJ_2 2/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/09/2021 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Perform the test to the designated primary overfill device (Rochester and/or high level alarm) and send test results by email to the County inspector.
 
12/09/2021 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. For the next two months (January and February) perform the visual inspection to the storage tank and components and send by email to the County inspector.
 
12/08/2021 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. A storage tank system where financial responsibility is not maintained and demonstrated, pursuant to rule 62-762.421, F.A.C., within 90 days of termination shall be closed in place or removed from site. Provide proof of financial responsibility by email to the County inspector. This violation is considered top priority (SNC-A), per FDEP Level of Effort Guidance, facility will be referred for enforcement.
 
12/08/2021 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Perform the test to the Krueger Leak Gauge and provide copy of the test results by email to the County inspector.
 
 
 
No Discharges Found