DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 9300667   Latitude    27° 43' 4.66
 
Name KR AT COLLEGE HARBOR SKILLED NURSING HOME
4600 54TH AVE S
Longitude    82° 41' 46.13
  SAINT PETERSBURG, FL 33711 LL Method    DPHO
 
Contact JUSTIN MOCK   LL Status    REVIEWED
 
Phone (727) 866-3124   Status Date    08/05/2005
 
Account Owner Information
 
Name RK3 LLC
200 Clearwater Largo Rd S
Largo, FL 33770-3235
Effective Date    08/12/2019
 
Contact Daniel Hollenbeck
 
Phone (727) 259-2171
 
Email DHOLLENBECK@KRMANAGEMENT.COM
  Placard # / Date    687765 - 06/13/2024
Property Owner Information
 
Name RK3 LLC
200 Clearwater Largo Rd S
Largo, FL 33770-3235
Effective Date    08/12/2019
 
Contact Daniel Hollenbeck
 
Phone (727) 259-2171
 
Email DHOLLENBECK@KRMANAGEMENT.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
2 2000 Emerg Generator Diesel (G) 08/01/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(I) Suction piping system
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
3 1500 Emerg Generator Diesel (G) 08/01/2019 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(I) Suction piping system
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 2000 Emerg Generator Diesel (G) 07/01/1986 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   12/18/2022 12/18/2023 ACE AMERICAN INSURANCE COMPANY
INSURANCE   12/18/2020 12/18/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   12/18/2019 12/18/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   12/18/2018 12/18/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/17/1994 05/17/1996 PLUS
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 02/26/2025 Major Out of Compliance PUHR_NM_1 2/0 Routine Compliance
 
Electronic Communication 02/24/2025 Satisfied PUHR_NM_1 Routine Compliance
 
Letter 11/14/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 11/14/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 05/21/2021 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 05/21/2021 Major Out of Compliance COLSON_NJ_1 2/0 Routine Compliance
 
Electronic Communication 04/01/2021 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 06/26/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 06/26/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 10/31/2019 Minor Out of Compliance COLSON_NJ_1 2/0 Installation
 
Letter 10/31/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/24/2025 7091 Minor 3.15 Exterior Coatings not maintained to prevent corrosion. *Need to replace the spill bucket and provide documentation to this office. *Need to treat the corrosion on T3 (1500 gallon).
 
02/24/2025 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. *Need to replace the spill bucket and provide documentation to this office.
 
02/24/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, *Submit the missing documents if found; otherwise, have testing completed and submit results to this office for review. Be sure to include any test results and an indication of whether the tested device PASSED/FAILED.
 
02/24/2025 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. *Submit two new consecutive months of tank visual inspections with the needed updates and alarm history if any.
 
02/24/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Violation observed with the completion of testing.
 
02/24/2025 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. *Need to provide the FR for the missing dates. *Need to provide the current Part D and P Form.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/31/1997   COMPLETED 6