Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9301086 | Latitude | 25° 46' 38.5439 | ||||||||
Name |
Quattro Miami 700 NW 107TH AVE |
Longitude | 80° 22' 14.0637 | ||||||||
MIAMI, FL 33172-3161 | LL Method | DPHO | |||||||||
Contact | Esteban Acosta | LL Status | REVIEWED | ||||||||
Phone | (305) 229-0800 | Status Date | 08/30/2021 | ||||||||
Account Owner Information | |||||||||||
Name | Four 700 LLC 760 NW 107 AVE STE 108 Miami, FL 33172 |
Effective Date | 05/04/2022 | ||||||||
Contact | Esteban Acosta | ||||||||||
Phone | (305) 229-0800 | ||||||||||
esteban@quattro.miami | |||||||||||
Placard # / Date | 670928 - 10/12/2023 | ||||||||||
Property Owner Information | |||||||||||
Name | Four 700 LLC 760 NW 107 AVE STE 108 Miami, FL 33172 |
Effective Date | 05/04/2022 | ||||||||
Contact | Esteban Acosta | ||||||||||
Phone | (305) 229-0800 | ||||||||||
esteban@quattro.miami | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 6000 | Emerg Generator Diesel (G) | 01/01/1992 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket |
(C) Fiberglass (F) Double wall |
(8) Manually sampled wells (G) Electronic line leak detector |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 01/01/2021 | 01/01/2022 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 01/01/2020 | 01/01/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 10/04/2018 | 10/04/2019 | PHOENIX INSURANCE COMPANY | ||||||||
INSURANCE | 10/04/2017 | 10/04/2018 | PHILADELPHIA INSURANCE CO | ||||||||
INSURANCE | 09/29/2016 | 09/29/2017 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/29/2014 | 09/29/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/29/2013 | 09/29/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/29/2012 | 09/29/2013 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/29/2011 | 09/29/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 11/29/2009 | 11/29/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/25/2007 | 09/25/2008 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/17/2006 | 04/24/2006 | MINOR OUT-OF-COMPLIANCE | PADRON, J | 0/1 | COMPLIANCE ASSURANCE | |||||
TCR | 06/29/2005 | 06/30/2005 | IN-COMPLIANCE | PADRON, J | 0/1 | COMPLIANCE ASSURANCE | |||||
TCR | 06/16/2005 | 06/21/2005 | MINOR OUT-OF-COMPLIANCE | PADRON, J | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 05/24/2005 | 05/26/2005 | MINOR OUT-OF-COMPLIANCE | PADRON, J | 0/1 | COMPLIANCE ASSURANCE | |||||
RRBD | 10/23/2003 | 11/03/2003 | SMITH , C | 1/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 10/10/2003 | 10/17/2003 | MINOR OUT-OF-COMPLIANCE | SMITH, C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 10/07/2003 | 10/10/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | SMITH, C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 01/07/2003 | 01/16/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | SMITH, C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 01/30/2002 | 02/07/2002 | SIGNIFICANT OUT-OF-COMPLIANCE | SMITH, C | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 01/28/2000 | 02/07/2000 | IN-COMPLIANCE | RONDON, K | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 03/26/1999 | 04/23/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | GARCIA, A | 0/1 | COMPLIANCE ASSURANCE | |||||
RRBD | 03/26/1999 | 06/18/1999 | GARCIA, A | 0/0 | COMPLIANCE ASSURANCE | ||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 10/19/2023 | Satisfied | RODRIGUEZ_F | Compliance Assistance | |||||||
Site Inspection | 10/19/2023 | Major Out of Compliance | RODRIGUEZ_F | 0/1 | Routine Compliance | ||||||
Electronic Communication | 10/19/2023 | Satisfied | RODRIGUEZ_F | Routine Compliance | |||||||
Letter | 08/31/2021 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Site Inspection | 08/31/2021 | In Compliance | GODWIN_MR_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 07/29/2021 | Satisfied | GODWIN_MR_1 | Routine Compliance | |||||||
Letter | 06/07/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Compliance Assistance | |||||||
Enforcement Tracking | 06/07/2019 | Closed Without Enforcement | FERNANDEZBANGO_CE_1 | Enforcement | |||||||
Electronic Communication | 06/05/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Compliance Assistance | |||||||
Electronic Communication | 06/05/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Compliance Assistance | |||||||
Letter | 03/12/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Compliance Assistance | |||||||
Enforcement Referral | 03/05/2019 | Accepted | DASHTAKI_K_1 | Enforcement | |||||||
Electronic Communication | 01/28/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Routine Compliance | |||||||
Site Inspection | 01/28/2019 | Major Out of Compliance | FERNANDEZBANGO_CE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 01/22/2019 | Satisfied | FERNANDEZBANGO_CE_1 | Routine Compliance | |||||||
Electronic Communication | 09/30/2016 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Site Inspection | 09/30/2016 | In Compliance | CABRERA_VE_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 09/23/2016 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Phone Conversation | 09/23/2016 | Satisfied | CABRERA_VE_1 | Routine Compliance | |||||||
Phone Conversation | 10/29/2014 | Satisfied | LINCHETA_CR_1 | Routine Compliance | |||||||
Site Inspection | 10/20/2014 | In Compliance | LINCHETA_CR_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 03/18/2013 | In Compliance | RUNTE_C_3 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 03/05/2013 | Satisfied | RUNTE_C_3 | Routine Compliance | |||||||
Site Inspection | 01/24/2011 | In Compliance | PADRON_JE_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 01/12/2010 | In Compliance | PADRON_JE_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 11/12/2008 | In Compliance | PADRON_JE_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 10/11/2007 | In Compliance | PADRON_JE_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 04/23/2007 | In Compliance | PADRON_JE_1 | 0/1 | Routine Compliance | ||||||
Record Document | 07/03/2006 | Satisfied | PADRON_JE_1 | Non-Compliance | |||||||
Site Inspection | 06/19/2006 | In Compliance | PADRON_JE_1 | 0/1 | Non-Compliance | ||||||
Site Inspection | 06/09/2006 | Minor Out of Compliance | PADRON_JE_1 | 0/1 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/19/2023 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Provide a current Certificate of Financial Responsibility (tank insurance) | |||||||
10/19/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Provide current and passing Integrity test of single-wall spill containment bucket. | |||||||
10/19/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Provide current and passing Integrity test of the piping sump. | |||||||
10/19/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide current and passing operability test of the release detection device. | |||||||
10/19/2023 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide the monthly inspection logs for the previous three (3) years. Monitoring well log (monitoring wells should be visually inspected monthly and documented) Visual log (monthly visual inspection of storage tank system, includes sumps, fill ports, etc.) 3 years’ worth of records will need to be kept on site for review. | |||||||
10/19/2023 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Remove/repair the corrosion on the above ground steel product piping. | |||||||
10/19/2023 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Provide Training Certification for A/B and C Operators | |||||||
10/19/2023 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide current and passing operability test of the overfill protection device. | |||||||
No Discharges Found |