District Northwest   Type    Marine/Coastal Fuel Storage
 
County Okaloosa   Status    OPEN
 
ID 9400009   Latitude    30° 24' 9.342
 
Name LEGENDARY MARINA AT MIDBAY
4601 LEGENDARY MARINA DR
Longitude    86° 25' 27.9947
  DESTIN, FL 32541 LL Method    DPHO
 
Contact JEREMY HOLCOMB   LL Status    REVIEWED
 
Phone (850) 337-8200   Status Date    09/02/2009
 
Account Owner Information
 
Name SUNTEX MARINA INVESTORS LLC
4603 LEGENDARY MARINA DR
DESTIN, FL 32541
Effective Date    12/16/2022
 
Contact MICHELLE GATLIN
 
Phone (850) 419-4718
 
Email MICHELLE.GATLIN@SUNTEX.COM
  Placard # / Date    684619 - 06/06/2024
Property Owner Information
 
Name SUNTEX MARINA INVESTORS LLC
4603 LEGENDARY MARINA DR
DESTIN, FL 32541
Effective Date    12/16/2022
 
Contact MICHELLE GATLIN
 
Phone (850) 419-4718
 
Email MICHELLE.GATLIN@SUNTEX.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
7 20000 Vehicular Diesel (D) 05/01/2001 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(D) Unknown
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(J) Monitor piping/liner space
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 5000 Vehicular Diesel (D) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(Q) Visual inspection of ASTs
(V) Suction pump check valve
 
 
Tank Tank Size Content Installed Placement Status
2 550 Waste Oil (L) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact
(B) Steel/galvanized metal
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 550 New/Lube Oil (O) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact
(B) Steel/galvanized metal
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
4 1000 New/Lube Oil (O) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact
(B) Steel/galvanized metal
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
5 1000 New/Lube Oil (O) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact
(B) Steel/galvanized metal
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
6 20000 Unleaded Gas (B) ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(D) SPCC Plan
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   04/01/2024 04/01/2025 IRONSHORE SPECIALTY INSURANCE COMPANY
INSURANCE   04/01/2022 04/01/2023 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   11/16/2020 11/16/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   04/11/2018 04/11/2019 CONTINENTAL CASUALTY INSURANCE COMPANY
INSURANCE   11/16/2015 11/16/2016 COMMERCE & INDUSTRY
INSURANCE   11/16/2013 11/16/2014 COMMERCE & INDUSTRY
INSURANCE   11/16/2012 11/16/2013 COMMERCIAL INSURANCE
INSURANCE   11/16/2010 11/16/2011 COMMERCE & INDUSTRY
INSURANCE   01/01/2010 01/01/2011 COMMERCE & INDUSTRY
INSURANCE   01/01/2008 01/01/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 09/02/2005 09/09/2005 IN-COMPLIANCE JOHN S. STEVENSON 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes HURRICANE KATRINA DAMAGE ASSESSMENT INSPECTION. NO DAMAGE FROM RECENT STORMS WAS IDENTIFIED AT UST, PIPING OR DISPENSERS. SYSTEM IS FUNCTIONING NORMALLY.
 
TCI 07/20/2005 07/25/2005 IN-COMPLIANCE J. SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes HURRICANE DENNIS DAMAGE ASSESSMENT INSPECTION. NO APPARENT RELEASE AND SYSTEM IS OPERABLE. NO DAMAGE.
 
TIN 04/20/2005 05/05/2005 IN-COMPLIANCE J. SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes SPILL BUCKET INSTALLATION. CLOSURE ASSESSMENT DUE IN 60 DAYS.
 
TXI 04/20/2005 05/05/2005 IN-COMPLIANCE J. SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes FILL BUCKET REMOVAL. CONTRACTOR LAURITZ SPANN PCC045053.
 
TCI 04/06/2005 04/19/2005 MINOR OUT-OF-COMPLIANCE SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
TCI 09/28/2004 10/05/2004 IN-COMPLIANCE J. SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes POST HURRICANE IVAN INSPECTION. TANK AND PIPING SYSTEM SHOWED VERY LITTLE DAMAGE. PIPING NEEDS TO BE SECURED AND WESTERN MOST DISPENSER NEEDS PANELS REPLACED. NO DISCHARGE SYSTEM OPERATIONAL.
 
RRBD 06/14/2004 06/17/2004 COMPLIANCE ASSURANCE
 
TCI 05/13/2004 05/17/2004 SIGNIFICANT OUT-OF-COMPLIANCE J. SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
DPRI 10/23/2003 10/28/2003 IN-COMPLIANCE JOHN B. HOLLINGSHEAD 0/1 TERMINAL FACILITY PROJECT
 
 Completion Notes DPRC CERTIFICATE NUMBER 98772
 
TCI 03/18/2003 03/25/2003 IN-COMPLIANCE SCOTT HALE 0/1 COMPLIANCE ASSURANCE
 
TCI 06/04/2002 06/13/2002 IN-COMPLIANCE V. PAUL HUTCHERSON 0/1 COMPLIANCE ASSURANCE
 
DPRI 05/07/2002 05/23/2002 IN-COMPLIANCE JOHN B. HOLLINGSHEAD 0/1 TERMINAL FACILITY PROJECT
 
 Completion Notes CERTIFICATE 98753
 
TIN 06/14/2001 06/14/2001 IN-COMPLIANCE HOLLINGSHEAD_JB 0/1 COMPLIANCE ASSURANCE
 
RRBD 04/03/2001 04/17/2001 COMPLIANCE ASSURANCE
 
TCI 11/15/2000 11/20/2000 SIGNIFICANT OUT-OF-COMPLIANCE THAYER_JD 0/5 COMPLIANCE ASSURANCE
 
RRBD 02/18/2000 02/18/2000 THAYER_JD 0/0 COMPLIANCE ASSURANCE
 
TCI 01/14/2000 02/01/2000 SIGNIFICANT OUT-OF-COMPLIANCE THAYER_JD 1/0 COMPLIANCE ASSURANCE
 
RRBD 12/20/1999 12/20/1999 THAYER_JD 0/0 COMPLIANCE ASSURANCE
 
TCI 04/16/1999 05/03/1999 SIGNIFICANT OUT-OF-COMPLIANCE THAYER_J 1/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 01/03/2025 Satisfied ELLIOTT_EV_1 Routine Compliance
 
Letter 12/17/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Site Inspection 12/16/2024 Major Out of Compliance ELLIOTT_EV_1 0/1 Routine Compliance
 
Enforcement Tracking 04/18/2023 Closed Without Enforcement BRISTOL_S Enforcement
 
Enforcement Referral 03/08/2023 Accepted GARTIN_D Enforcement
 
Electronic Communication 03/02/2023 Satisfied GARTIN_D Compliance Assistance
 
Electronic Communication 02/08/2023 Satisfied GARTIN_D Compliance Assistance
 
Electronic Communication 02/03/2023 Satisfied GARTIN_D Compliance Assistance
 
Electronic Communication 12/13/2022 Satisfied GARTIN_D Routine Compliance
 
Electronic Communication 12/13/2022 Satisfied GARTIN_D Routine Compliance
 
Site Inspection 12/13/2022 Major Out of Compliance GARTIN_D 0/1 Routine Compliance
 
Letter 12/13/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 04/09/2021 In Compliance PANGAHAS_RL_1 0/1 Routine Compliance
 
Letter 04/09/2021 Satisfied WILSON_ML_1 Routine Compliance
 
Issue Document 04/09/2021 Satisfied WILSON_ML_1 Routine Compliance
 
Phone Conversation 04/07/2021 Satisfied PANGAHAS_RL_1 Routine Compliance
 
Electronic Communication 04/07/2021 Satisfied PANGAHAS_RL_1 Routine Compliance
 
Electronic Communication 04/07/2021 Satisfied PANGAHAS_RL_1 Routine Compliance
 
Incident 11/01/2019 Has not led to Discharge PANGAHAS_RL_1 Incident
 
TCAR 10/31/2019 Satisfied PAYNE_CL_1 Closure
 
Letter 10/31/2019 Satisfied WILSON_ML_1 Closure
 
Issue Document 10/31/2019 Satisfied WILSON_ML_1 Closure
 
Document Management 10/17/2019 Satisfied WILSON_ML_1 Closure
 
Letter 10/04/2019 Satisfied WILSON_ML_1 Installation
 
Issue Document 10/04/2019 Satisfied WILSON_ML_1 Installation
 
Site Inspection 10/03/2019 In Compliance PANGAHAS_RL_1 0/1 Installation
 
Document Management 09/05/2019 Satisfied PANGAHAS_RL_1 Incident
 
Letter 09/27/2018 Satisfied WILSON_ML_1 Routine Compliance
 
Issue Document 09/27/2018 Satisfied WILSON_ML_1 Routine Compliance
 
Phone Conversation 09/27/2018 Satisfied PANGAHAS_RL_1 Routine Compliance
 
Site Inspection 09/27/2018 In Compliance PANGAHAS_RL_1 0/1 Routine Compliance
 
Electronic Communication 09/27/2018 Satisfied PANGAHAS_RL_1 Routine Compliance
 
Site Inspection 03/04/2016 In Compliance KHAN_MR_1 0/1 Routine Compliance
 
Phone Conversation 03/01/2016 Satisfied KHAN_MR_1 Routine Compliance
 
Enforcement Tracking 11/20/2014 Closed Without Enforcement MERRITT_S Enforcement
 
Electronic Communication 11/20/2014 Satisfied MERRITT_S Non-Compliance
 
Electronic Communication 11/20/2014 Satisfied MERRITT_S Non-Compliance
 
Electronic Communication 11/20/2014 Satisfied MERRITT_S Non-Compliance
 
Electronic Communication 11/14/2014 Satisfied KHAN_MR_1 Non-Compliance
 
Enforcement Referral 11/14/2014 Accepted MERRITT_S Enforcement
 
Electronic Communication 11/14/2014 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 05/19/2014 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 05/16/2014 Minor Out of Compliance KHAN_MR_1 0/1 Routine Compliance
 
Site Inspection 05/22/2013 In Compliance KHAN_MR_1 0/1 Non-Compliance
 
Record Document 05/17/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 12/10/2012 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 12/07/2012 Major Out of Compliance KHAN_MR_1 0/1 Routine Compliance
 
Site Inspection 03/24/2011 In Compliance PORTER_AJ_1 0/1 Routine Compliance
 
Record Document 10/21/2010 Satisfied THAYER_JD_1 Non-Compliance
 
Electronic Communication 06/23/2010 Satisfied THAYER_JD_1 Non-Compliance
 
Phone Conversation 06/23/2010 Satisfied THAYER_JD_1 Non-Compliance
 
Discharge Reporting 06/16/2010 Satisfied THAYER_JD_1 Discharge
 
Document Management 06/16/2010 Complete THAYER_JD_1 Discharge
 
Phone Conversation 06/14/2010 Satisfied THAYER_JD_1 Non-Compliance
 
Record Document 06/07/2010 Satisfied KHAN_MR_1 Routine Compliance
 
Letter 05/10/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 05/06/2010 Minor Out of Compliance THAYER_JD_1 0/1 Routine Compliance
 
Record Document 02/02/2009 Satisfied THAYER_JD_1 Non-Compliance
 
Letter 01/07/2009 Satisfied THAYER_JD_1 Non-Compliance
 
Record Document 01/07/2009 Satisfied THAYER_JD_1 Routine Compliance
 
Site Inspection 12/30/2008 Minor Out of Compliance THAYER_JD_1 0/1 Routine Compliance
 
Phone Conversation 02/29/2008 Satisfied KHAN_MR_1 Routine Compliance
 
Record Document 02/29/2008 Satisfied KHAN_MR_1 Routine Compliance
 
Letter 02/15/2008 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 02/14/2008 Major Out of Compliance KHAN_MR_1 0/1 Routine Compliance
 
Record Document 11/30/2006 Satisfied THAYER_JD_1 Non-Compliance
 
Site Inspection 10/18/2006 Minor Out of Compliance THAYER_JD_1 6/1 Routine Compliance
 
Proof of Contamination 10/10/2006 Satisfied THAYER_JD_1 Discharge
 
TCAR 10/10/2006 Rejected THAYER_JD_1 Closure
 
Record Document 09/06/2006 Satisfied THAYER_JD_1 Closure
 
TCAR 09/06/2006 Incomplete THAYER_JD_1 Closure
 
Record Document 08/14/2006 Satisfied THAYER_JD_1 Closure
 
TCAR 08/07/2006 Rejected THAYER_JD_1 Closure
 
Site Inspection 07/21/2006 In Compliance HALE_JS_1 0/1 Routine Compliance
 
Site Inspection 06/01/2006 In Compliance TISSINGTON_AB_1 0/1 Routine Compliance
 
Site Inspection 05/23/2006 In Compliance TISSINGTON_AB_1 0/1 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/16/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Have a certified technician test the Ball Floats for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Remove the liquid from the secondary and re-install or replace the interstitial gauge as necessary. The integrity of the premium spill bucket must be tested before it brought back into service. If the spill bucket needs to be replaced, contact the inspector prior to work beginning. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the spill containment gauges for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from the diesel STP sump. Email a copy of the work invoice to the inspector for review and pictures. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the STP Sumps. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the Double Wall Spill Containments. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov.
 
12/16/2024 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the ATG System for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the dispenser sumps. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/16/2024 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the Line Leak Detectors for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone