Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||
Cover Page Report | |||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||
District | Southeast | Type | Fuel user/Non-retail | ||||
County | Miami-Dade | Status | OPEN | ||||
ID | 9400168 | Latitude | 25° 57' .1004 | ||||
Name |
REGENTS PARK AT AVENTURA 18905 NE 25TH AVE |
Longitude | 80° 9' .2203 | ||||
NORTH MIAMI BEACH, FL 33180 | LL Method | DPHO | |||||
Contact | ALEX HERRERA | LL Status | REVIEWED | ||||
Phone | (305) 932-6360 | Status Date | 10/29/2024 | ||||
Account Owner Information | |||||||
Name | OAKWOOD TERRACE SKILLED NURSING 18905 NE 25TH AVE NORTH MIAMI BEACH, FL 33180 |
Effective Date | 02/10/1994 | ||||
Contact | JON C AARON | ||||||
Phone | (305) 932-6360 | ||||||
Placard # / Date | 700738 - 08/19/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 1000 | Emerg Generator Diesel (G) | 04/01/2010 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (R) Double wall - tank jacket (X) Concrete |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating |
(F) Monitor dbl wall tank space (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs (V) Suction pump check valve |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 1000 | Emerg Generator Diesel (G) | 07/01/1985 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (M) Spill containment bucket |
(C) Fiberglass (I) Suction piping system (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (C) Groundwater Monitoring Plan (N) Groundwater monitoring |
|||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 01/10/2020 | 01/10/2021 | ACE AMERICAN INSURANCE COMPANY | ||||
INSURANCE | 01/01/2019 | 01/10/2020 | ACE AMERICAN INSURANCE COMPANY | ||||
INSURANCE | 01/10/2018 | 01/10/2019 | ACE AMERICAN INSURANCE COMPANY | ||||
INSURANCE | 01/10/2017 | 01/10/2018 | ACE AMERICAN INSURANCE COMPANY | ||||
INSURANCE | 03/30/2014 | 03/30/2015 | COMMERCE & INDUSTRY | ||||
INSURANCE | 03/30/2013 | 03/30/2014 | COMMERCE & INDUSTRY | ||||
INSURANCE | 05/01/2012 | 05/01/2013 | COMMERCE & INDUSTRY | ||||
INSURANCE | 05/01/2010 | 05/01/2011 | COMMERCE & INDUSTRY | ||||
INSURANCE | 05/01/2009 | 05/01/2010 | COMMERCE & INDUSTRY | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 04/14/2006 | 04/17/2006 | IN-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
RRBD | 05/20/2005 | 05/27/2005 | COMPLIANCE ASSURANCE | ||||
TCI | 05/19/2005 | 05/26/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 03/17/2004 | 03/19/2004 | IN-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCR | 04/17/2003 | 04/21/2003 | IN-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCR | 04/02/2003 | 04/08/2003 | MINOR OUT-OF-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 03/24/2003 | 03/27/2003 | MINOR OUT-OF-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 04/18/2002 | 04/29/2002 | IN-COMPLIANCE | SHER_R | 0/1 | COMPLIANCE ASSURANCE | |
RRBD | 06/01/2001 | 06/21/2001 | SHER, R | 1/0 | COMPLIANCE ASSURANCE | ||
TCI | 05/03/2001 | 06/01/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | SHER, R | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 05/17/2000 | 05/24/2000 | IN-COMPLIANCE | SHER, R | 0/0 | COMPLIANCE ASSURANCE | |
UTCI | 08/06/1998 | 01/11/1999 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Letter | 10/29/2024 | Satisfied | DEZAYAS_A_1 | Compliance Assistance | |||
Electronic Communication | 10/29/2024 | Satisfied | DEZAYAS_A_1 | Routine Compliance | |||
Site Inspection | 10/29/2024 | Major Out of Compliance | DEZAYAS_A_1 | 1/0 | Routine Compliance | ||
Electronic Communication | 10/01/2024 | Satisfied | DEZAYAS_A_1 | Routine Compliance | |||
Site Inspection | 01/21/2020 | In Compliance | SANPEDRO_A_2 | 1/0 | Routine Compliance | ||
Letter | 01/21/2020 | Satisfied | SANPEDRO_A_2 | Routine Compliance | |||
Electronic Communication | 01/07/2020 | Satisfied | SANPEDRO_A_2 | Routine Compliance | |||
Electronic Communication | 01/25/2017 | Satisfied | DEZAYAS_A_1 | Non-Compliance | |||
Site Inspection | 01/25/2017 | In Compliance | DEZAYAS_A_1 | 1/0 | Non-Compliance | ||
Electronic Communication | 01/25/2017 | Satisfied | DEZAYAS_A_1 | Routine Compliance | |||
Site Inspection | 01/09/2017 | Major Out of Compliance | DEZAYAS_A_1 | 1/0 | Routine Compliance | ||
Letter | 01/09/2017 | Satisfied | DEZAYAS_A_1 | Non-Compliance | |||
Phone Conversation | 01/05/2017 | Satisfied | DEZAYAS_A_1 | Routine Compliance | |||
Electronic Communication | 01/05/2017 | Satisfied | DEZAYAS_A_1 | Routine Compliance | |||
Site Inspection | 02/19/2015 | In Compliance | HOSU_C_1 | 1/0 | Routine Compliance | ||
Phone Conversation | 02/05/2015 | Satisfied | HOSU_C_1 | Routine Compliance | |||
Phone Conversation | 02/20/2013 | Satisfied | DASHTAKI_K_1 | Routine Compliance | |||
Site Inspection | 02/20/2013 | In Compliance | DASHTAKI_K_1 | 1/0 | Routine Compliance | ||
Enforcement Tracking | 10/24/2012 | Closed Without Enforcement | SHER_RC_1 | Enforcement | |||
Site Inspection | 04/28/2011 | In Compliance | SHER_RC_1 | 1/0 | Routine Compliance | ||
TCAR | 07/29/2010 | Satisfied | MAS_JR_1 | Closure | |||
Site Inspection | 04/21/2010 | In Compliance | SHER_RC_1 | 1/0 | Installation | ||
Meeting | 04/07/2010 | Satisfied | SHER_RC_1 | Routine Compliance | |||
Meeting | 04/07/2010 | Satisfied | SHER_RC_1 | Routine Compliance | |||
Site Inspection | 03/09/2010 | In Compliance | SHER_RC_1 | 0/1 | Closure | ||
Document Management | 02/08/2010 | Complete | CORREA_LI_1 | Routine Compliance | |||
Meeting | 01/13/2010 | Satisfied | SHER_RC_1 | Routine Compliance | |||
Site Inspection | 10/23/2009 | In Compliance | SHER_RC_1 | 0/1 | Non-Compliance | ||
Site Inspection | 09/21/2009 | Minor Out of Compliance | SHER_RC_1 | 0/1 | Non-Compliance | ||
Site Inspection | 08/31/2009 | Major Out of Compliance | SHER_RC_1 | 0/1 | Routine Compliance | ||
Letter | 08/31/2009 | Satisfied | SHER_RC_1 | Non-Compliance | |||
Issue Document | 08/31/2009 | Satisfied | SHER_RC_1 | Enforcement | |||
Enforcement Referral | 08/31/2009 | Accepted | SHER_RC_1 | Enforcement | |||
Site Inspection | 11/06/2008 | In Compliance | SHER_RC_1 | 0/1 | Routine Compliance | ||
Site Inspection | 03/19/2008 | In Compliance | SHER_RC_1 | 0/1 | Routine Compliance | ||
Site Inspection | 04/27/2007 | In Compliance | SHER_RC_1 | 0/1 | Routine Compliance | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
10/29/2024 | 7076 | SNC-A | 3.2 Not repaired component or piping which has cause a discharge or release. | Make necessary repairs to the aboveground storage tank to prevent water/liquid intrusion into the tank interstice. | |||
10/29/2024 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide Monthly Maintenance Visual logs for the AST and components for the last 36 months. | |||
10/29/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide a current and passing Annual Operability Test for Overfill Protection device (mechanical fuel gauge). | |||
10/29/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide a current and passing Annual Operability Test for Release Detection device (mechanical leak gauge). | |||
10/29/2024 | 7007 | Minor | 3.1 Incident Notification Form (INF) not received in a timely manner. | Provide a completed Incident Notification Form (INF) investigating the cause of the liquid within the tank interstice and the corrective actions being taken to correct the issue. | |||
10/29/2024 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Provide an updated FDEP Storage Tank Registration form updating Sections A, B, and C. | |||
10/29/2024 | 7090 | Minor | 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. | Remove liquid within the tank interstice. | |||
10/29/2024 | 7009 | SNC-B | 1.7 No financial responsibility instrument or expired instrument for < 180 days. | Provide a current Certificate of Financial Responsibility - Pollution Liability Insurance. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
09/14/1994 | COMPLETED | 5 | |||||