DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    County Government
 
County Miami-Dade   Status    OPEN
 
ID 9400170   Latitude    25° 46' 28.7387
 
Name DADE CNTY CENTRAL SUPPORT FACILITY
200 NW 1ST ST
Longitude    80° 11' 52.163
  MIAMI, FL 33128 LL Method    DPHO
 
Contact DANIEL DOUGLASS   LL Status    REVIEWED
 
Phone (305) 375-7072   Status Date    04/21/2010
 
Account Owner Information
 
Name DADE CNTY METRO CENTRAL SUPPORT
200 NW 1ST ST
MIAMI, FL 33128-1759
Effective Date    07/25/2000
 
Contact CULTURAL MGMT GROUP
 
Phone (305) 375-1072
 
Email ISD-FIMDCMG@MIAMIDADE.GOV
  Placard # / Date    701454 - 09/18/2024
Property Owner Information
 
Name DADE CNTY METRO CENTRAL SUPPORT
200 NW 1ST ST
MIAMI, FL 33128-1759
Effective Date    02/17/2010
 
Contact CULTURAL MGMT GROUP
 
Phone (305) 375-1072
 
Email ISD-FIMDCMG@MIAMIDADE.GOV
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Emerg Generator Diesel (G) 06/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(R) Double wall - tank jacket   (F) Double wall (H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Emerg Generator Diesel (G) 07/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(N) Flow shut-Off
  (J) Pressurized piping system
(M) Double wall - pipe jacket
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(I) Not required
(K) Monitor dbl wall pipe space
(N) Groundwater monitoring
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2025 01/31/2026
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2022 01/31/2023
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2019 01/31/2020
LOCAL GOVERNMENTS - BOND RATING TEST   03/18/2016 03/18/2017
LOCAL GOVERNMENTS - BOND RATING TEST   02/05/2013 02/05/2014
LOCAL GOVERNMENTS - BOND RATING TEST   02/03/2010 02/02/2011
LOCAL GOVERNMENTS - BOND RATING TEST   12/21/2008 12/31/2009
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 11/15/2004 12/11/2004 IN-COMPLIANCE BUSEN_K 0/1 COMPLIANCE ASSURANCE
 
CWOE 06/05/2003 06/06/2003 JENNIFER SMITH 0/0 COMPLIANCE ASSURANCE
 
NCLI 06/03/2003 06/03/2003 COMPLIANCE ASSURANCE
 
TCI 04/29/2003 05/23/2003 SIGNIFICANT OUT-OF-COMPLIANCE JENNIFER SMITH/NICOLE KUEHLE 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 03/07/2025 Major Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Letter 09/30/2022 Satisfied WILLIAMS_CEW Compliance Assistance
 
Letter 09/21/2022 Satisfied WILLIAMS_CEW Compliance Assistance
 
Site Inspection 05/31/2022 Major Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Letter 04/08/2020 Satisfied WILLIAMS_CEW Routine Compliance
 
Electronic Communication 03/05/2020 Satisfied WILLIAMS_CEW Routine Compliance
 
Electronic Communication 08/29/2019 Satisfied WILLIAMS_CEW Routine Compliance
 
Issue Document 06/18/2019 Satisfied WILLIAMS_CEW Routine Compliance
 
Electronic Communication 06/18/2019 Satisfied WILLIAMS_CEW Routine Compliance
 
Letter 06/10/2019 Satisfied WILLIAMS_CEW Compliance Assistance
 
Site Inspection 06/04/2019 Minor Out of Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Site Inspection 08/29/2016 In Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Site Inspection 01/03/2014 In Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
Site Inspection 01/25/2011 In Compliance WILLIAMS_CEW 0/1 Routine Compliance
 
TCAR 08/23/2010 Satisfied MAS_JR_1 Closure
 
Site Inspection 02/22/2010 In Compliance JACKSON_ME 0/1 Routine Compliance
 
TCAR 09/17/2009 Incomplete MAS_JR_1 Closure
 
Site Inspection 06/17/2009 In Compliance SHER_RC_1 0/1 Installation
 
Site Inspection 06/04/2009 In Compliance SHER_RC_1 0/1 Installation
 
Site Inspection 05/28/2009 In Compliance SHER_RC_1 0/1 Installation
 
Site Inspection 05/26/2009 In Compliance SHER_RC_1 0/1 Closure
 
Letter 05/07/2009 Satisfied RAHRIG_T Non-Compliance
 
Site Inspection 05/04/2009 Minor Out of Compliance RAHRIG_T 0/1 Routine Compliance
 
Record Document 04/22/2009 Satisfied RAHRIG_T Routine Compliance
 
Phone Conversation 03/13/2009 Satisfied RAHRIG_T Routine Compliance
 
Record Document 03/05/2009 Satisfied RAHRIG_T Closure
 
Issue Document 01/30/2009 Satisfied RAHRIG_T Routine Compliance
 
Letter 07/03/2008 Satisfied RAHRIG_T Non-Compliance
 
Issue Document 07/03/2008 Satisfied RAHRIG_T Routine Compliance
 
Site Inspection 07/01/2008 Minor Out of Compliance RAHRIG_T 0/1 Routine Compliance
 
Issue Document 04/25/2007 Satisfied WHITE_CM Routine Compliance
 
Site Inspection 04/17/2007 In Compliance WHITE_CM 0/1 Routine Compliance
 
Record Document 04/16/2007 Satisfied WHITE_CM Routine Compliance
 
Issue Document 04/16/2007 Satisfied WHITE_CM Routine Compliance
 
Record Document 02/01/2007 Satisfied RAHRIG_T Non-Compliance
 
Site Inspection 02/01/2007 In Compliance RAHRIG_T 0/1 Non-Compliance
 
Record Document 01/29/2007 Satisfied RAHRIG_T Non-Compliance
 
Record Document 01/29/2007 Satisfied RAHRIG_T Non-Compliance
 
Letter 01/29/2007 Satisfied RAHRIG_T Non-Compliance
 
Issue Document 01/26/2007 Satisfied RAHRIG_T Non-Compliance
 
Phone Conversation 01/25/2007 Satisfied RAHRIG_T Non-Compliance
 
Site Inspection 07/09/2006 Minor Out of Compliance BARATH_J 0/1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/07/2025 6062 Minor 2.5 Release detection devices not tested annually. Please provide the annual line leak detection test for 2023.
 
03/07/2025 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Please provide three years of integrity test for the spill bucket.
 
03/07/2025 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Please update the contact information.
 
03/07/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Please provide pictures of cleaned spill bucket.
 
03/07/2025 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Please perform and provide the monthly visual inspections and the alarm checks.
 
 
 
No Discharges Found