DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District South   Type    Retail Station
 
County Collier   Status    OPEN
 
ID 9502948   Latitude    26° 12' 39.123
 
Name SUNSHINE #801
5098 AIRPORT PULLING RD N
Longitude    81° 46' 1.7966
  NAPLES, FL 34105-2428 LL Method    DPHO
 
Contact KEVIN HASAN   LL Status    REVIEWED
 
Phone (239) 261-8067   Status Date    04/23/2003
 
Account Owner Information
 
Name SUNSHINE GASOLINE DISTRIBUTORS INC
1650 NW 87TH AVE
Doral, FL 33172-2614
Effective Date    02/19/2016
 
Contact MARIO ZAMORA / VANESSA PALACIOS/BARBIE RUIZ
 
Phone (786) 606-0917
 
Email MZAMORA@SUNSHINEGASOLINE.COM
  Placard # / Date    694692 - 06/25/2024
Property Owner Information
 
Name SUNSHINE GASOLINE DISTRIBUTORS INC
1650 NW 87TH AVE
Doral, FL 33172-2614
Effective Date    06/21/2017
 
Contact MARIO ZAMORA / VANESSA PALACIOS/BARBIE RUIZ
 
Phone (786) 606-0917
 
Email MZAMORA@SUNSHINEGASOLINE.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 09/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 09/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(N) Approved synthetic material
(1) Continuous electronic sensing
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   09/25/2021 09/25/2024 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2020 09/25/2021 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2019 09/25/2020 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2018 09/25/2019 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2017 09/25/2018 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2016 09/25/2017 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2016 09/25/2017 NATIONAL INSURANCE CO
INSURANCE   06/20/2015 06/20/2016 COMMERCE & INDUSTRY
INSURANCE   06/20/2014 06/20/2015 COMMERCE & INDUSTRY
INSURANCE   06/20/2013 06/20/2014 COMMERCE & INDUSTRY
INSURANCE   06/20/2011 06/20/2012 COMMERCE & INDUSTRY
INSURANCE   06/20/2010 06/20/2011 COMMERCE & INDUSTRY
INSURANCE   06/20/2008 06/20/2009 COMMERCE & INDUSTRY
INSURANCE   12/08/1995 12/08/1997 PLUS
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 01/19/2006 01/27/2006 MINOR OUT-OF-COMPLIANCE OWEN_J 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes MLLDS AND SENSORS NEED ANNUAL TESTING. THE SPILL BUCKETS APPEAR DAMANGED AND NEED HYDROS.
 
TCI 01/18/2005 01/24/2005 IN-COMPLIANCE KOLANDA 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS
 
NCLI 04/23/2004 04/26/2004 KOLANDA 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes NEEDS ANNUAL OPERABILITY TESTS FOR INTERSTITIAL SENSORS & MLLD
 
TCI 04/22/2004 04/22/2004 MINOR OUT-OF-COMPLIANCE KOLANDA 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: DW BLACK PRIMARY -- YELLOW SECONDARY
 
TCPI 12/05/2003 12/11/2003 IN-COMPLIANCE LUCAS 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes COMPLAINT OF WATER IN TANK - NO WATER FOUND
 
TCR 05/05/2003 05/05/2003 IN-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes PRODUCT WAS PREMOVED FROM DISPENSER LINER #5. LLD PASSED OPERABILITY. DISPENSER HOSE ON #9 WAS REPLACED.
 
CWOE 05/05/2003 05/05/2003 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
NCLI 03/20/2003 03/26/2003 HOGAN_S 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NCLI FOR TCI DATED 3/20/03
 
TCI 03/20/2003 03/20/2003 MINOR OUT-OF-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LLD NEED ANNUAL TEST. REMOVE FUEL FROM DISPENSER LINER #5. REPLACE DISPENSER HOSE. DISPENSER #1 IS BEING REPLACED BY ST&P, DAMAGED BY A VEHICLE. NO RELEASE TO ENVIRONMENT.
 
TCI 03/15/2002 03/21/2002 IN-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes IN COMPLIANCE
 
CWOE 06/04/2001 06/04/2001 HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSE 92/N 92/N 157/N 157/N
 
TCR 06/04/2001 06/04/2001 IN-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes MONITORING WELLS PROPERLY ABANDONED AND LLDS TESTED.
 
TCR 05/14/2001 05/14/2001 MINOR OUT-OF-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes OVERFILL IS INSTALLED, LLDS TESTED. NEEDS TO CLOSE WELLS AND TEST TANK INTERSTICE SENSORS
 
TCI 04/13/2001 04/16/2001 SIGNIFICANT OUT-OF-COMPLIANCE HOGAN_S 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSE WELLS, VERIFY OR INSTALL OVERFILL, RD DEVICES ANNUAL TEST
 
TCI 03/21/2000 03/23/2000 IN-COMPLIANCE SILLERY_W 0/2 COMPLIANCE ASSURANCE
 
CWOE 08/17/1999 08/17/1999 LAWSON_D 0/0 COMPLIANCE ASSURANCE
 
RRBD 08/17/1999 08/17/1999 LAWSON_D 0/0 COMPLIANCE ASSURANCE
 
TCR 07/21/1999 08/02/1999 MINOR OUT-OF-COMPLIANCE LAWSON_D 0/2 COMPLIANCE ASSURANCE
 
WLI 06/18/1999 08/17/1999 LAWSON_D 0/0 COMPLIANCE ASSURANCE
 
NCLI 04/23/1999 08/17/1999 LAWSON_D 0/0 COMPLIANCE ASSURANCE
 
TCI 04/12/1999 04/22/1999 MINOR OUT-OF-COMPLIANCE LAWSON_D 0/2 COMPLIANCE ASSURANCE
 
UTCI 06/18/1998 06/24/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 Completion Notes ROUTINE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/12/2024 Accepted STANDIFORD_JA Enforcement
 
Record Document 02/29/2024 Satisfied STANDIFORD_JA Routine Compliance
 
Letter 12/06/2023 Satisfied STANDIFORD_JA Compliance Assistance
 
Site Inspection 11/29/2023 Major Out of Compliance STANDIFORD_JA 0/2 Routine Compliance
 
Letter 11/10/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 11/10/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 11/08/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 11/08/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 10/14/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 10/12/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/27/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Electronic Communication 09/14/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Letter 09/10/2021 Satisfied HERNANDEZ_N_5 Compliance Assistance
 
Site Inspection 09/10/2021 Major Out of Compliance HERNANDEZ_N_5 0/2 Routine Compliance
 
Electronic Communication 09/02/2021 Satisfied HERNANDEZ_N_5 Routine Compliance
 
Incident 06/18/2020 Has not led to Discharge HERNANDEZ_N_5 Incident
 
Electronic Communication 06/18/2020 Satisfied BATES_TD_1 Compliance Assistance
 
Letter 06/18/2020 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 06/09/2020 Satisfied BATES_TD_1 Compliance Assistance
 
Electronic Communication 11/06/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Letter 09/30/2019 Satisfied BATES_TD_1 Compliance Assistance
 
Site Inspection 09/30/2019 Major Out of Compliance BATES_TD_1 0/2 Routine Compliance
 
Document Management 09/26/2019 Satisfied BATES_TD_1 Incident
 
Electronic Communication 09/26/2019 Satisfied BATES_TD_1 Routine Compliance
 
Enforcement Tracking 04/01/2019 Closed Without Enforcement HERNANDEZ_N Enforcement
 
Issue Document 04/01/2019 Satisfied HERNANDEZ_N Enforcement
 
Electronic Communication 03/29/2019 Satisfied HERNANDEZ_N Enforcement
 
Site Inspection 03/29/2019 In Compliance HERNANDEZ_N 0/2 Enforcement
 
Electronic Communication 10/18/2018 Satisfied HERNANDEZ_N Enforcement
 
Electronic Communication 04/13/2018 Satisfied HERNANDEZ_N Enforcement
 
Phone Conversation 04/13/2018 Satisfied HERNANDEZ_N Enforcement
 
Enforcement Referral 04/13/2018 Accepted STANDIFORD_JA_2 Enforcement
 
Electronic Communication 04/13/2018 Satisfied HERNANDEZ_N Enforcement
 
Phone Conversation 04/13/2018 Satisfied HERNANDEZ_N Enforcement
 
Record Document 02/09/2018 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Record Document 02/08/2018 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Letter 12/04/2017 Satisfied STANDIFORD_JA_2 Compliance Assistance
 
Site Inspection 11/30/2017 Major Out of Compliance STANDIFORD_JA_2 0/2 Routine Compliance
 
Document Management 01/30/2017 Satisfied SNYDERBURN_PJ_2 Closure
 
TCAR 01/30/2017 Satisfied SNYDERBURN_PJ_2 Closure
 
Letter 01/30/2017 Satisfied SNYDERBURN_PJ_2 Closure
 
Incident 01/30/2017 Has not led to Discharge SNYDERBURN_PJ_2 Incident
 
Site Inspection 01/30/2017 In Compliance SNYDERBURN_PJ_2 0/2 Closure
 
Document Management 01/30/2017 Satisfied SNYDERBURN_PJ_2 Incident
 
Site Inspection 01/30/2017 In Compliance SNYDERBURN_PJ_2 0/2 Installation
 
Site Inspection 12/08/2015 In Compliance STANDIFORD_JA_2 0/2 Routine Compliance
 
Site Inspection 05/20/2014 In Compliance SPARKS_JD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 07/22/2013 Satisfied SPARKS_JD_1 Routine Compliance
 
Emergency Preparedness Information 07/22/2013 Satisfied SPARKS_JD_1 Routine Compliance
 
Letter 06/28/2013 Satisfied SPARKS_JD_1 Non-Compliance
 
Site Inspection 06/28/2013 Minor Out of Compliance SPARKS_JD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 08/25/2012 Satisfied SPARKS_JD_1 Routine Compliance
 
Site Inspection 12/07/2011 In Compliance SNYDERBURN_PJ_2 0/2 Non-Compliance
 
Record Document 10/18/2011 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 10/10/2011 Major Out of Compliance SNYDERBURN_PJ_2 0/2 Routine Compliance
 
Letter 10/10/2011 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Letter 01/17/2011 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Site Inspection 01/16/2011 Minor Out of Compliance SNYDERBURN_PJ_2 0/2 Routine Compliance
 
Record Document 09/03/2010 Satisfied NOVAK_KM_1 Non-Compliance
 
Document Management 03/08/2010 Complete NOVAK_KM_1 Non-Compliance
 
Record Document 01/22/2010 Minor Out of Compliance NOVAK_KM_1 Non-Compliance
 
Record Document 11/19/2009 Satisfied NOVAK_KM_1 Non-Compliance
 
Letter 11/18/2009 Satisfied NOVAK_KM_1 Non-Compliance
 
Record Document 11/18/2009 Satisfied NOVAK_KM_1 Non-Compliance
 
Site Inspection 11/18/2009 Major Out of Compliance NOVAK_KM_1 0/2 Routine Compliance
 
Site Inspection 12/19/2008 In Compliance NOVAK_KM_1 0/2 Non-Compliance
 
Site Inspection 10/29/2008 Minor Out of Compliance WILSON_KM 0/2 Routine Compliance
 
Emergency Preparedness Information 10/29/2008 Satisfied WILSON_KM Routine Compliance
 
Letter 10/29/2008 Satisfied WILSON_KM Non-Compliance
 
TCAR 07/08/2008 Satisfied SNYDERBURN_PJ_2 Closure
 
Site Inspection 07/08/2008 In Compliance POTTS_CR 0/2 Non-Compliance
 
Record Document 02/25/2008 Satisfied SNYDERBURN_PJ_2 Non-Compliance
 
Phone Conversation 12/11/2007 Satisfied POTTS_CR Non-Compliance
 
Record Document 11/13/2007 Satisfied POTTS_CR Non-Compliance
 
Letter 10/26/2007 Satisfied POTTS_CR Non-Compliance
 
Phone Conversation 10/22/2007 Satisfied POTTS_CR Non-Compliance
 
Site Inspection 09/19/2007 Major Out of Compliance POTTS_CR 0/2 Routine Compliance
 
Letter 09/19/2007 Satisfied POTTS_CR Non-Compliance
 
Emergency Preparedness Information 09/10/2007 Satisfied POTTS_CR Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied POTTS_CR Routine Compliance
 
Emergency Preparedness Information 09/29/2006 Satisfied SNYDERBURN_PJ_2 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/29/2023 7089 Minor 1.11 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Perform integrity testing and provide the associated test record to the Inspector within 90 days of the inspection date. Ensure integrity testing is performed every 3 years (on or before 3 year date) as required by rule.
 
11/29/2023 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. Within 90 days of the inspection date: Please perform an integrity test and provide the completed test record via email to the Inspector. If the integrity test fails, submit an INF. The Incident will then be investigated to determine if a discharge occurred. If a discharge occurred, please submit a DRF and then initiate a site assessment to include sampling.
 
 
 
No Discharges Found