Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Southeast   Type    County Government
 
County Miami-Dade   Status    OPEN
 
ID 9600034   Latitude    25° 47' 38.03
 
Name MIAMI-DADE AVIATION DEPT MDAD GSA VFF
4300 NW 20TH ST BLDG 3051 MIA
Longitude    80° 16' 5.4754
  MIAMI, FL 33159 LL Method    DPHO
 
Contact PEDRO F HERNANDEZ   LL Status    REVIEWED
 
Phone (305) 876-7928   Status Date    04/09/2003
 
Account Owner Information
 
Name MIAMI-DADE AVIATION DEPT
PO BOX 25504
Miami, FL 33102-5504
Effective Date    01/11/1996
 
Contact GABRIEL GARCIA
 
Phone (305) 869-3615
 
Email GAGARCIA@FLYMIA.COM
  Placard # / Date    698325 - 07/01/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
10A 10000 Vehicular Diesel (D) 12/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(B) Site Suitabilitiy Plan exemption
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
11A 10000 Unleaded Gas (B) 12/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(B) Site Suitabilitiy Plan exemption
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
12A 10000 Unleaded Gas (B) 12/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(B) Site Suitabilitiy Plan exemption
(F) Monitor dbl wall tank space
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2024 01/31/2025
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2023 01/31/2024
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2022 01/31/2023
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2021 01/31/2022
LOCAL GOVERNMENTS - BOND RATING TEST   02/01/2018 01/31/2019
LOCAL GOVERNMENTS - BOND RATING TEST   01/15/2015 07/21/2016
LOCAL GOVERNMENTS - BOND RATING TEST   01/01/2012 12/31/2014
LOCAL GOVERNMENTS - BOND RATING TEST   01/01/2012 02/05/2014
LOCAL GOVERNMENTS - BOND RATING TEST   10/01/2010 12/31/2011
LOCAL GOVERNMENTS - FINANCIAL TEST   01/01/2006 12/31/2006
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 09/28/2005 10/17/2005 IN-COMPLIANCE ECT/BUSEN_K 3/0 COMPLIANCE ASSURANCE
 
MEET 05/04/2005 05/06/2005 COMPLIANCE ASSURANCE
 
TCI 09/28/2004 11/04/2004 SIGNIFICANT OUT-OF-COMPLIANCE BUSEN_K 3/0 COMPLIANCE ASSURANCE
 
RRBD 07/03/2003 07/07/2003 COMPLIANCE ASSURANCE
 
TCI 06/03/2003 06/09/2003 MINOR OUT-OF-COMPLIANCE RAINEY_A 3/0 COMPLIANCE ASSURANCE
 
TCI 02/24/2003 02/24/2003 IN-COMPLIANCE RAINEY_A 1/0 COMPLIANCE ASSURANCE
 
 Completion Notes TCI ENTERED ONLY TO CLOSE VIOLATIONS AND ENTER CWOE; NO PHYSICAL INSPECTION PERFORMED
 
TCI 10/01/1999 10/04/1999 SIGNIFICANT OUT-OF-COMPLIANCE RAINEY_A 3/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Meeting 12/03/2024 Satisfied MAIB_R Enforcement
 
Enforcement Referral 10/23/2024 Accepted MAIB_R Enforcement
 
Site Inspection 08/08/2024 Major Out of Compliance MAIB_R 3/0 Routine Compliance
 
Electronic Communication 08/30/2022 Satisfied BORGESPADRO_A Routine Compliance
 
Electronic Communication 08/30/2022 Satisfied BORGESPADRO_A Routine Compliance
 
Letter 10/19/2021 Satisfied WILLIAMS_CEW Compliance Assistance
 
Electronic Communication 08/05/2021 Satisfied WILLIAMS_CEW Routine Compliance
 
Site Inspection 07/21/2021 Major Out of Compliance WILLIAMS_CEW 3/0 Routine Compliance
 
Letter 11/16/2018 Satisfied WILLIAMS_CEW Compliance Assistance
 
Letter 11/16/2018 Satisfied WILLIAMS_CEW Routine Compliance
 
Site Inspection 09/12/2018 Minor Out of Compliance WILLIAMS_CEW 3/0 Routine Compliance
 
Site Inspection 06/22/2016 In Compliance DOLAN_J 3/0 Routine Compliance
 
Record Document 04/05/2013 Satisfied RAHRIG_T Routine Compliance
 
Electronic Communication 04/04/2013 Satisfied RAHRIG_T Routine Compliance
 
Site Inspection 04/02/2013 In Compliance RAHRIG_T 3/0 Routine Compliance
 
Electronic Communication 03/28/2013 Satisfied RAHRIG_T Routine Compliance
 
Meeting 10/16/2012 Satisfied RAHRIG_T Non-Compliance
 
Electronic Communication 09/05/2012 Satisfied RAHRIG_T Non-Compliance
 
Record Document 09/05/2012 Satisfied RAHRIG_T Non-Compliance
 
Issue Document 06/22/2012 Satisfied RAHRIG_T Routine Compliance
 
Letter 06/15/2012 Satisfied RAHRIG_T Non-Compliance
 
Site Inspection 06/08/2012 Major Out of Compliance RAHRIG_T 3/0 Routine Compliance
 
Electronic Communication 05/17/2012 Satisfied RAHRIG_T Routine Compliance
 
Electronic Communication 10/20/2010 Satisfied RAHRIG_T Non-Compliance
 
Electronic Communication 10/19/2010 Satisfied RAHRIG_T Routine Compliance
 
Letter 10/19/2010 Satisfied RAHRIG_T Non-Compliance
 
Site Inspection 10/19/2010 Minor Out of Compliance RAHRIG_T 3/0 Routine Compliance
 
Site Inspection 09/26/2006 In Compliance BUSEN_K 3/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
07/31/2024 7012 SNC-B 3.3 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. An incident investigation needs to be performed, and an incident notification form needs to be submitted to the department.
 
07/18/2024 7095 Minor 1.14 Records requiring 3 year documentation period not kept by facility. Repair records for the tank system need to be provided.
 
07/16/2024 7076 SNC-A 3.2 Not repaired component or piping which has cause a discharge or release. The dispenser sumps need to be taken out of service, repairs completed, and an investigation shall be conducted in accordance with F.A.C 62-762.801 and Instructions for Conducting Sampling During Aboveground Storage Tank Closure, July 2019 Edition, to ensure the discharge did not enter the environment.
 
07/16/2024 7022 Minor 3.4 Secondary containment constructed of concrete not in accordance with standards or not impervious. The remote fill concrete spill containment needs to be repaired and integrity test performed.
 
07/16/2024 7083 SNC-B 3.8 Storage tank system not taken out-of-service when repairs cannot be made within 90 days. The six dispenser sumps, piping sump and spill containment for the remote fill need to be taken out of service until the proper repairs are made and integrity testing completed.
 
07/16/2024 7047 SNC-B 3.11 Piping sumps not meeting performance requirements or installed to allow for release detection. The piping sump need to be repaired to manufacturer standards and integrity test performed.
 
07/16/2024 7045 Minor 3.6 Dispensers not installed and maintained according to standards. The six dispenser sumps need to be repaired to manufacturer standards and integrity tests performed.
 
07/16/2024 7081 SNC-B 3.7 Piping that is damaged which has not caused a discharge is not replaced. The ASTs STP piping and integral piping needs to be repaired to manufacturer standards.
 
07/16/2024 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. The testing boots in the piping sump need to be pulled back.
 
 
 
No Discharges Found