Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/20/2025 Last Data Refresh: 04/19/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 9602201 | Latitude | 28° 0' 49 | ||||||||
Name |
REPUBLIC SERVICES 3820 MAINE AVE |
Longitude | 81° 52' 51 | ||||||||
LAKELAND, FL 33801-9757 | LL Method | DPHO | |||||||||
Contact | David Cooper | LL Status | REVIEWED | ||||||||
Phone | (863) 665-1489 | Status Date | 06/10/2003 | ||||||||
Account Owner Information | |||||||||||
Name | REPUBLIC SERVICE OF FLORIDA LLC 3820 Maine Ave Lakeland, FL 33801-9757 |
Effective Date | 08/29/2006 | ||||||||
Contact | BILL SMITH | ||||||||||
Phone | (863) 669-4810 | ||||||||||
WSMITH@REPUBLICSERVICES.COM | |||||||||||
Placard # / Date | 700644 - 08/13/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | REPUBLIC SERVICE OF FLORIDA LLC 3820 Maine Ave Lakeland, FL 33801-9757 |
Effective Date | 08/29/2006 | ||||||||
Contact | BILL SMITH | ||||||||||
Phone | (863) 669-4810 | ||||||||||
WSMITH@REPUBLICSERVICES.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 20000 | Vehicular Diesel (D) | 10/01/1996 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (J) Pressurized piping system (K) Dispenser liners |
(1) Continuous electronic sensing (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
NONE | |||||||||||
INSURANCE | 06/30/2019 | 06/30/2020 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 06/30/2018 | 06/30/2019 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 06/30/2017 | 06/30/2018 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 06/30/2016 | 06/30/2017 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 06/30/2015 | 06/30/2016 | ADMIRAL INSURANCE COMPANY | ||||||||
INSURANCE | 06/30/2013 | 06/30/2014 | ACE | ||||||||
INSURANCE | 06/30/2012 | 06/30/2013 | INDIAN HARBOR | ||||||||
INSURANCE | 06/30/2011 | 06/30/2012 | INDIAN HARBOR | ||||||||
INSURANCE | 06/30/2010 | 06/30/2011 | INDIAN HARBOR | ||||||||
INSURANCE | 06/30/2009 | 06/30/2010 | INDIAN HARBOR | ||||||||
INSURANCE | 06/30/2008 | 06/30/2009 | GREENWICH | ||||||||
INSURANCE | 06/30/2003 | 03/30/2004 | GREENWICH | ||||||||
INSURANCE | 06/30/2001 | 11/01/2002 | AMERICAN ALTERNATIVE INSURANCE | ||||||||
INSURANCE | 06/30/2000 | 06/30/2002 | GREENWICH | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
NCLI | 04/06/2006 | 04/06/2006 | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: TWO MONTHLY VISUAL INSPECTIONS. | |||||||||||
NCLI | 04/06/2006 | 04/06/2006 | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/13/2006 | 04/06/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 14 PHOTOS. PIPING: SINGLE-WALLED ABOVEGROUND GALVANIZED STEEL PIPING WITH THE APPROPRIATE VALVES. VIOLATIONS RESOLVED: 2059, 2064. | |||||||||||
TIN | 02/13/2006 | 04/06/2006 | MINOR OUT-OF-COMPLIANCE | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 14 PHOTOS. INSTALLED: TWO DISPENSER LINERS, PNEUMERCATOR, ISOLATION & ANTI-SIPHON VALVE. | |||||||||||
SV | 10/10/2005 | 10/17/2005 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes FOLLOW UP ON FACILITY THAT HAD BEEN REFERRED FOR DEP ENFORCEMENT. | |||||||||||
CRDE | 12/29/2004 | 12/29/2004 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/12/2004 | 01/05/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | CROWELL_M | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes 6 PHOTOS TAKEN. PIPING: PAINTED SINGLE WALL STEEL. | |||||||||||
TCI | 08/22/2003 | 08/25/2003 | IN-COMPLIANCE | HUGHES_J | 1/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. | |||||||||||
NCLI | 09/30/2002 | 10/01/2002 | HAUSCHILD_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/23/2002 | 10/01/2002 | MINOR OUT-OF-COMPLIANCE | HAUSCHILD_T | 1/0 | COMPLIANCE ASSURANCE | |||||
CWOE | 05/08/2002 | 05/10/2002 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 05/08/2002 | 05/10/2002 | IN-COMPLIANCE | NEWBERG_D | 1/0 | COMPLIANCE ASSURANCE | |||||
NCLI | 01/26/2001 | 01/29/2001 | MURRAY_K | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 01/11/2001 | 01/29/2001 | MINOR OUT-OF-COMPLIANCE | MURRAY_K | 1/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 09/15/2000 | 09/20/2000 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
WLI | 06/02/2000 | 07/11/2000 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/09/1999 | 08/17/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | MEDER_R | 1/0 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 08/16/2022 | Satisfied | HYPPOLITE_LX_1 | Routine Compliance | |||||||
Electronic Communication | 02/17/2020 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 02/15/2020 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Site Inspection | 02/15/2020 | Major Out of Compliance | CASSELS_CR_2 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 02/15/2020 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Letter | 02/15/2020 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 12/08/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Letter | 12/08/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Letter | 12/08/2017 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Site Inspection | 12/07/2017 | Minor Out of Compliance | CASSELS_CR_2 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 11/29/2017 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 11/28/2017 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 01/15/2016 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||||||
Site Inspection | 01/15/2016 | In Compliance | MERRYMAN_DT_1 | 1/0 | Non-Compliance | ||||||
Electronic Communication | 12/29/2015 | Satisfied | MERRYMAN_DT_1 | Routine Compliance | |||||||
Site Inspection | 12/29/2015 | Minor Out of Compliance | MERRYMAN_DT_1 | 1/0 | Routine Compliance | ||||||
Letter | 12/29/2015 | Satisfied | MERRYMAN_DT_1 | Non-Compliance | |||||||
Letter | 12/20/2013 | Satisfied | NEWBERG_DR_1 | Non-Compliance | |||||||
Electronic Communication | 12/20/2013 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Site Inspection | 12/20/2013 | Minor Out of Compliance | NEWBERG_DR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 03/30/2012 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 03/18/2011 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 03/31/2010 | In Compliance | WINN_JP_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 01/29/2009 | In Compliance | NEWBERG_DR_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 01/29/2009 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Site Inspection | 05/12/2008 | In Compliance | CASSELS_CR_1 | 1/0 | Routine Compliance | ||||||
Enforcement Tracking | 10/22/2007 | Closed With Enforcement | RANDOLPH_L | Enforcement | |||||||
Meeting | 10/22/2007 | Satisfied | RANDOLPH_L | Enforcement | |||||||
Enforcement Referral | 09/18/2007 | Accepted | RANDOLPH_L | Enforcement | |||||||
Site Inspection | 06/01/2007 | In Compliance | DERY_WC_1 | 1/0 | Routine Compliance | ||||||
Phone Conversation | 05/03/2007 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/14/2020 | 5126 | Minor | 3.16 Spill containment, sumps, and interstices not accessible. Water/regulated substance not timely removed for shop fabricated storage tank systems. Petroleum contact water not properly managed. | The fuel in the South dispenser liner must be removed and properly disposed and the Department notified. | |||||||
02/14/2020 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | The South dispenser must be repaired to stop the leaking and the Department notified. | |||||||
02/14/2020 | 5097 | SNC-B | 3.5 Electronic release detection devices not inspected monthly for shop fabricated storage tank systems. | Copies of the next two months (March & April 2020) of electronic release detection monitoring reports (System Status, Liquid Status, & Alarm History Reports) must be submitted to the Department as each one is performed. | |||||||
02/14/2020 | 5127 | Minor | 3.17 Exterior Coatings not maintained to prevent corrosion for shop fabricated storage tank systems. | Any moderate or heavy corrosion must be removed and the steel components re-painted to maintain corrosion protection, and the Department notified. | |||||||
02/14/2020 | 5114 | Minor | 3.4 Shop fabricated storage tank system has a not repaired component which has or could cause a release or discharge. | The leaking hoses must be repaired, and the Department notified. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
11/30/2023 | INACTIVE | Wimberly, Evan | 8134705720 | ||||||||