Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | County Government | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9602348 | Latitude | 25° 36' 41.9376 | ||||||||
Name |
DADE CNTY-METRO ZOO 12400 SW 152ND ST |
Longitude | 80° 23' 55.9921 | ||||||||
MIAMI, FL 33177 | LL Method | DGPS | |||||||||
Contact | WILLIAM ELGAR | LL Status | REVIEWED | ||||||||
Phone | (305) 251-0400 | Status Date | 01/21/2004 | ||||||||
Account Owner Information | |||||||||||
Name | DADE CNTY PARKS & RECREATION 275 NW 2ND ST MIAMI, FL 33128-1741 |
Effective Date | 01/25/2019 | ||||||||
Contact | TMORGAN/ MRICHARD 3053653015 / MNARDI/3057557800 | ||||||||||
Phone | (305) 755-7910 | ||||||||||
TOM.MORGAN@MIAMIDADE.GOV | |||||||||||
Placard # / Date | 699318 - 07/10/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | DADE CNTY PARKS & RECREATION 275 NW 2ND ST MIAMI, FL 33128-1741 |
Effective Date | 01/25/2019 | ||||||||
Contact | TMORGAN/ MRICHARD 3053653015 / MNARDI/3057557800 | ||||||||||
Phone | (305) 755-7910 | ||||||||||
TOM.MORGAN@MIAMIDADE.GOV | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 898 | Emerg Generator Diesel (G) | 09/01/2007 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 1000 | Unleaded Gas (B) | 02/01/1997 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (P) Internal pipe/internal sump riser (X) No piping associated w/tank |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 1000 | Emerg Generator Diesel (G) | 08/01/2002 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment (M) Spill containment bucket (P) Level gauges/alarms (X) Concrete |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(6) External piping monitoring (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 560 | Vehicular Diesel (D) | 04/01/2018 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal (X) No piping associated w/tank |
(F) Monitor dbl wall tank space (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 640 | Emerg Generator Diesel (G) | 01/01/2009 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 1000 | Emerg Generator Diesel (G) | 02/01/2014 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 1500 | Emerg Generator Diesel (G) | 05/01/2007 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 1768 | Emerg Generator Diesel (G) | 11/01/2007 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 3000 | Vehicular Diesel (D) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2024 | 01/31/2025 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2023 | 01/31/2024 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2022 | 01/31/2023 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2021 | 02/01/2022 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2020 | 01/31/2021 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/01/2018 | 02/01/2019 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 03/17/2016 | 03/17/2017 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 08/14/2012 | 08/14/2013 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 07/13/2010 | 07/01/2011 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 02/22/2008 | 02/21/2009 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 12/05/2005 | 02/09/2006 | MINOR OUT-OF-COMPLIANCE | ECT/BARATH_J | 2/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes ONE 1,000 GALLON COMPARTMENTED TANK NOT REGISTERED; NO MONTHLY VISUAL INSPECTION LOGS; FILL PORTS NOT COLOR COORDINATED, NEED TO PAINT. | |||||||||||
LTR | 11/17/2005 | 02/09/2006 | ECT/BARATH_J | 2/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NOTIFICATION FOR TCI ON 11/28/05 AT 12:45 PM. ACTUAL TCI OCCURRED 12/05/05. | |||||||||||
LTR | 08/04/2005 | 08/04/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes SERIES OF E-MAILS CONCERNING WHETHER OR NOT THE 1000 GALLON AST IS REGULATED DUE TO IT BEING DIVIDED BY A SINGLE INTER-WALL. RULE INTERPRETATION IS THAT SINCE THE INTER-WALL IS A SINGLE WALL AND DOEN'T ALLOW FOR INTERSTITIAL MONITORING, IT IS REGULATED. | |||||||||||
CWOE | 06/30/2005 | 06/30/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
LTR | 06/30/2005 | 06/30/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 06/30/2005 | 06/30/2005 | IN-COMPLIANCE | SELF_M | 0/0 | COMPLIANCE ASSURANCE | |||||
RRBD | 06/20/2005 | 06/30/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
CALL | 06/06/2005 | 06/06/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 04/12/2005 | 06/03/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
MEET | 04/07/2005 | 04/07/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 02/25/2005 | 03/14/2005 | SELF_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 12/14/2004 | 02/08/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | CUBINSKI_K | 2/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes TANK 3 IS A 1,000 GALLON COMPARTMENTED TANK (500 EACH SIDE) THAT IS USED TO FUEL VEHICLES. THIS TANK WAS MISTAKENLY REMOVED FROM LIST OF REGISTERED TANKS. | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 12/02/2024 | Major Out of Compliance | SABIR_A | 8/0 | Routine Compliance | ||||||
Site Inspection | 10/21/2024 | Major Out of Compliance | SABIR_A | 5/0 | Installation | ||||||
Site Inspection | 12/13/2021 | Major Out of Compliance | LANDFIELD_J | 3/0 | Routine Compliance | ||||||
Electronic Communication | 11/08/2021 | Satisfied | LANDFIELD_J | Routine Compliance | |||||||
Letter | 01/23/2019 | Satisfied | WILLIAMS_CEW | Routine Compliance | |||||||
Letter | 01/04/2019 | Satisfied | WILLIAMS_CEW | Compliance Assistance | |||||||
Site Inspection | 01/02/2019 | Minor Out of Compliance | WILLIAMS_CEW | 2/0 | Routine Compliance | ||||||
Site Inspection | 03/18/2016 | In Compliance | WILLIAMS_CEW | 2/0 | Routine Compliance | ||||||
Site Inspection | 03/20/2013 | In Compliance | WILLIAMS_CEW | 2/0 | Routine Compliance | ||||||
Site Inspection | 11/04/2010 | In Compliance | DOLAN_J | 2/0 | Routine Compliance | ||||||
Record Document | 02/12/2009 | Satisfied | DOLAN_J | Non-Compliance | |||||||
Record Document | 07/10/2008 | Satisfied | LARA_MX | Non-Compliance | |||||||
Letter | 06/26/2008 | Satisfied | LARA_MX | Non-Compliance | |||||||
Site Inspection | 06/23/2008 | Major Out of Compliance | LARA_MX | 2/0 | Routine Compliance | ||||||
Site Inspection | 04/25/2007 | Minor Out of Compliance | WHITE_CM | 1/0 | Routine Compliance | ||||||
Record Document | 09/19/2006 | Satisfied | QURESHI_SA | Non-Compliance | |||||||
Letter | 07/28/2006 | Satisfied | QURESHI_SA | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/22/2024 | 7125 | SNC-A | 1.17 Owner, operator, or supplier deposited motor fuel into storage tank without current valid registration placard. | Notify The Department of any installation activities minimum 30-45 days prior to the work being done | |||||||
04/22/2024 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide certificates of responsibility to Tanks 4, 6, 7, 8, 9, 10. | |||||||
04/22/2024 | 7040 | SNC-B | 3.8 Overfill protection not provided. Fuel transfer not monitored. Alarms not installed. | Install an FDEP approved equipment gauge or high level and high fuel alarms that are either visible or audible to the operator at 90 and 95% fill capacity. | |||||||
04/22/2024 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide monthly monitoring to Tank 4. | |||||||
04/22/2024 | 7079 | Minor | 3.5 Repairs not completed per applicable standards. | Repair the component. | |||||||
04/22/2024 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | Test the interstice in Tanks 6,7,8,9,10. | |||||||
03/26/2024 | 7075 | SNC-B | 3.1 Not repaired component or piping which has not caused a discharge or release. | Repair or replace the components. Tank 5 Krueger Gauge Replaced. - 4/3/2024. | |||||||
03/26/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Submit the document. | |||||||
03/26/2024 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide proof of insurance. | |||||||
No Discharges Found |