DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    Retail Station
 
County Miami-Dade   Status    OPEN
 
ID 9700097   Latitude    25° 48' 40.8623
 
Name SUNSHINE #368
10690 NW 41ST ST
Longitude    80° 22' 8.6964
  MIAMI, FL 33178 LL Method    DPHO
 
Contact MAXIMO ALVAREZ   LL Status    REVIEWED
 
Phone (305) 477-5800   Status Date    02/21/2024
 
Account Owner Information
 
Name SUNSHINE GASOLINE DISTRIBUTORS INC
1650 NW 87TH AVE
Doral, FL 33172-2614
Effective Date    07/08/2013
 
Contact MARIO ZAMORA / VANESSA PALACIOS/BARBIE RUIZ
 
Phone (786) 606-0917
 
Email MZAMORA@SUNSHINEGASOLINE.COM
  Placard # / Date    694699 - 06/25/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 12000 Ethanol E10 (8) 09/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 12000 Ethanol E10 (8) 09/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
3 12000 Ethanol E10 (8) 09/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
(N) Groundwater monitoring
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   09/25/2023 09/25/2024 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2022 09/25/2023 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2021 09/25/2022 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2018 09/25/2019 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2017 09/25/2018 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2016 09/25/2017 NAUTILUS INSURANCE COMPANY
INSURANCE   09/25/2015 09/25/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   09/25/2014 09/25/2015 LIBERTY SURPLUS INSURANCE CORP
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2012 04/30/2013
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2011 04/30/2012
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2010 04/30/2011
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/28/2008 04/30/2009
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCR 03/02/2006 03/09/2006 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 02/22/2006 02/23/2006 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCI 01/17/2006 01/27/2006 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 04/25/2005 05/03/2005 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 03/01/2005 03/08/2005 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCI 01/25/2005 01/27/2005 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 09/25/2003 09/29/2003 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCI 08/21/2003 08/25/2003 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 01/15/2003 01/22/2003 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCI 12/17/2002 12/19/2002 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 06/14/2002 06/20/2002 IN-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCI 05/21/2002 06/03/2002 MINOR OUT-OF-COMPLIANCE PADRON, J 0/3 COMPLIANCE ASSURANCE
 
TCR 03/17/2000 03/27/2000 IN-COMPLIANCE SANTANA, E 0/3 COMPLIANCE ASSURANCE
 
TCI 02/28/2000 03/03/2000 MINOR OUT-OF-COMPLIANCE SANTANA, E 0/3 COMPLIANCE ASSURANCE
 
TCDI 02/09/1999 05/19/1999 IN-COMPLIANCE SANTANA, E 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 10/31/2023 Satisfied PAAN_GE_1 Compliance Assistance
 
Site Inspection 10/30/2023 Major Out of Compliance PAAN_GE_1 0/3 Routine Compliance
 
Electronic Communication 10/24/2023 Satisfied PAAN_GE_1 Routine Compliance
 
Site Inspection 12/21/2022 In Compliance RODRIGUEZ_F 0/3 Compliance Assistance
 
Letter 12/21/2022 Satisfied RODRIGUEZ_F Compliance Assistance
 
Site Inspection 08/31/2021 Major Out of Compliance RODRIGUEZ_F 0/3 Routine Compliance
 
Letter 08/31/2021 Satisfied RODRIGUEZ_F Non-Compliance
 
Electronic Communication 08/27/2021 Satisfied RODRIGUEZ_F Routine Compliance
 
Letter 04/19/2019 Satisfied CABRERA_VE_1 Compliance Assistance
 
Letter 04/19/2019 Satisfied CABRERA_VE_1 Compliance Assistance
 
Electronic Communication 04/19/2019 Satisfied CABRERA_VE_1 Compliance Assistance
 
Electronic Communication 03/07/2019 Satisfied CABRERA_VE_1 Compliance Assistance
 
Site Inspection 03/06/2019 Major Out of Compliance CABRERA_VE_1 0/3 Routine Compliance
 
Electronic Communication 02/25/2019 Satisfied CABRERA_VE_1 Routine Compliance
 
Site Inspection 09/29/2016 In Compliance CRUZ_I_2 0/3 Routine Compliance
 
Electronic Communication 09/29/2016 Satisfied CRUZ_I_2 Routine Compliance
 
Electronic Communication 09/09/2016 Satisfied CRUZ_I_2 Routine Compliance
 
Phone Conversation 10/29/2014 Satisfied RUNTE_C_3 Routine Compliance
 
Site Inspection 10/28/2014 In Compliance RUNTE_C_3 0/3 Routine Compliance
 
Emergency Preparedness Information 10/28/2014 Satisfied RUNTE_C_3 Routine Compliance
 
Emergency Preparedness Information 01/10/2012 Satisfied PADRON_JE_1 Routine Compliance
 
Site Inspection 11/30/2011 In Compliance PADRON_JE_1 0/3 Routine Compliance
 
Site Inspection 12/13/2010 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Site Inspection 07/09/2010 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Letter 07/09/2010 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 05/18/2010 In Compliance PADRON_JE_1 0/3 Routine Compliance
 
Enforcement Tracking 02/18/2010 Closed Without Enforcement PADRON_JE_1 Enforcement
 
Site Inspection 06/02/2009 In Compliance PADRON_JE_1 0/3 Non-Compliance
 
Site Inspection 06/01/2009 Minor Out of Compliance PADRON_JE_1 0/3 Non-Compliance
 
Letter 06/01/2009 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 03/18/2009 Minor Out of Compliance PADRON_JE_1 0/3 Non-Compliance
 
Letter 03/18/2009 Satisfied PADRON_JE_1 Non-Compliance
 
Enforcement Referral 01/05/2009 Accepted PADRON_JE_1 Enforcement
 
Site Inspection 01/05/2009 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Issue Document 01/05/2009 Satisfied PADRON_JE_1 Enforcement
 
Letter 01/05/2009 Satisfied PADRON_JE_1 Non-Compliance
 
Letter 05/17/2007 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 05/17/2007 Minor Out of Compliance PADRON_JE_1 0/3 Non-Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied PADRON_JE_1 Routine Compliance
 
Letter 01/16/2007 Satisfied PADRON_JE_1 Non-Compliance
 
Site Inspection 01/16/2007 Minor Out of Compliance PADRON_JE_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied PADRON_JE_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/24/2023 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Test sensors to ensure functionality and calibrate Veeder-Root TLS-350 panel so that it correctly functions as release detection.
 
10/24/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Pump out or remove liquid such that the STP sumps are emptied.
 
10/24/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide current and passing Integrity Testing for Single-walled Spill Buckets.
 
10/24/2023 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Repair or replace Dispenser Liner frames such that corrosion and rust have been removed, further corrosion is prevented, and structural stability is maintained.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/31/1998   COMPLETED 11 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE